14.5 Modules - Parameter List
ID
Name
Description
Min
Default
Max
Unit
System
CF1
Topology
Select the topology based upon the system
design.
-
-
-
-
CF6
Number Of Phases
Enter the number of phases based upon the
system input/output power.
1
1
3
-
Converters
CF41
Allow Full Remote
Control
It allows to shut down all the converters in the
system.
-
False
-
AC Outputs
CF111
Saturation Level
Alarm Set
The saturation is an event defined in the
percentage of the Installed Power with
Parameter CF121 when the output power
crosses the threshold.
0
80
100
%
CF112
Saturation Level
Alarm Clear
The saturation is an event defined in the
percentage of the Power to clear the saturation
level.
0
70
100
%
CF121
Configured
Converters
The number of converters configured in the
output of phase 1.
1
1
5
-
CF122
Redundant
Converters
The number of redundant converters configured
in the output of phase 1.
1
1
4
-
CF123
Nominal Phase
Shift
The angle of phase shift at phase 1.
0
0
240
Deg
CF124
Nominal Voltage
The nominal voltage at AC output of phase 1.
100
120
130
V
CF141
Configured
Converters
The number of converters configured in the
output of phase 2.
1
1
5
-
CF142
Redundant
Converters
The number of redundant converters configured
in the output of phase 2.
1
1
4
-
CF143
Nominal Phase
Shift
The angle of phase shift at phase 2.
0
120
120
Deg
CF144
Nominal Voltage
The nominal voltage at AC output of phase 2.
100
120
130
V
CF161
Configured
Converters
The number of converters configured in the
output of phase 3.
1
1
5
-
CF162
Redundant
Converters
The number of redundant converters configured
in the output of phase 3.
1
1
4
-
CF163
Nominal Phase
Shift
The angle of phase shift at phase 3.
0
240
240
Deg
CF164
Nominal Voltage
The nominal voltage at AC output of phase 3.
100
120
130
V
CF1016
Nominal
Set the converters system frequency. This
frequency is used when the system is not
synchronized on AC input.
47
60
63
Hz
62
– Sierra 10 - 48/120 VAC – User Manual – v1.1
Appendix