background image

16  

INSTALLATION MANUAL

INPUTS

 

Each controller can monitor the state of up to 16 inputs such as magnetic contacts, motion detectors, temperature

 

sensors or other devices. The following are examples of the type of inputs that can be monitored:

 

Magnetic Door Contact: 

Permits supervision of door “status” (opened, closed, opened too long, forced open).

 

Inputs 1 and 9 are assigned by default as the door contact of doors 1 and 2 respectively.

 

When using defaults, you can easily swap terminals when troubleshooting.

 

Request for Exit (REX): 

The device used can be a push button, vertical-view motion detector or floor mat sensor.

 

 

The door can then be programmed to unlock on a REX detection. Not required if there is a reader/keypad on both  

 

sides of the door. When a magnetic door contact is installed, the system can differentiate between a door forced  

 

open and an authorized exit. Inputs 2 and 10 (3 and 11 for NC Input Connection above) are, by default, assigned  

 

to REX of doors 1 and 2 respectively.

 

Inputs can be installed to a maximum distance of 1000m (3300ft.) from the controller when using AWG #22. Only

 

one of the following input connections can be used per controller (see Figure 13).

 

NC INPUT CONNECTION (8 INPUTS)

 

When using this method, only one device can be connected to each input for a total of eight input devices. All

nputs on the selected controller must be connected using the NC Input Connection Method described in

 

Figure 13. This setup will not support tamper and wire fault (short circuit) recognition, but will generate an

 

alarm condition when the state of the input is breached. Only odd numbered inputs (1, 3, 5...) need to be

 

programmed.

 

ATZ 2R CONNECTION (16 INPUTS)

 

This method allows you to connect two devices to each controller input for a total of 16 input devices. All

nputs on the selected controller must be connected using the ATZ 2R Input Connection Method described in

 

Figure 13. This setup will not support wire fault (short circuit) recognition, but will generate an alarm condition

 

when the state of the input or its tamper switch is breached. Since an EOL resistor is not installed in this

 

configuration, if the line is cut, a tamper alarm will be generated.

 

 

ATZ 3R CONNECTION (16 INPUTS)

 

This method allows you to connect two devices to each controller input for a total of 16 input devices. All

 

inputs on the selected controller must be connected using the ATZ 3R Input Connection Method described in

 

Figure 13. This setup will generate an alarm condition when the state of the input or its tamper switch is

 

breached. An alarm condition will also be generated when a wire fault (short circuit) occurs. 

Figure 13: Input Connection Methods

RELAYS

 

Each  controller  has  two  30VDC,  110VAC,  5A  resistive  form  “C”  relays  with  a  “normally  open”  and  a  “normally 

 

closed” contact. These relays can be used to activate alarm sounders or other devices such as lighting control, air 

 

conditioning. An additional 14 relays can be added per controller by connecting two CA-A460 Relay Expansion 

 

modules to the controller’s E-Bus. The relays can be programmed to activate or deactivate according to a schedule,  

 

input or event.

www.cdvgroup.com

Summary of Contents for CT-V900

Page 1: ...CT V900 Controller Installation Manual...

Page 2: ......

Page 3: ...kup 7 LED Indicators 7 Upon Power Up 7 Battery Indications 7 Jumper Settings 8 BATT ON OFF 8 EOL Controller Network 8 12V 24V Lock 1 8 12V 24V Lock 2 9 High Low Network Impedance 9 EOL E Bus Network 9...

Page 4: ...our web site at www postech ca ACCESSORY MODULES POSIPROX CARD READER CR R880 Proximity technology will never be the same again PosiProx sets exacting new standards in design reliability and affordabi...

Page 5: ...allowing the card holder to selectthedesiredfloor TheDestinationControlledModeoffersafarsuperioreventtrailanduseraccountability by permitting the card holder to make only one floor selection upon pre...

Page 6: ...m 2 5 wide 10cm 4 deep Multiple Conduit Knock outs Two 25mm 1 or 31mm 1 25 and one 12mm 0 5 or 19mm 0 75 on each side Minimum Clearance For Cabinet 25cm 10 clear space around all sides 38cm 15 clear s...

Page 7: ...strobe during this one minute period LED INDICATORS For location of LEDs refer to Figure 2 on page 8 UPON POWER UP The AC PRESENT LED should be on The READER 5 VOLT LED should be on The 12 VOLT SUPPL...

Page 8: ...er to off until the the battery is replaced Note however if a complete power loss occurs the time and date as well as all controller programming will be lost EOL CONTROLLER NETWORK Places the EOL term...

Page 9: ...ntrollers each Using Table 1 on page 10 set the dip switches to the desired controller address Each of these loops is assigned to a specific COM port Controllers connected to the selected COM port wil...

Page 10: ...F OFF OFF ON OFF OFF 31 OFF ON ON ON ON OFF 53 OFF OFF ON OFF ON ON 10 ON OFF OFF ON OFF OFF 32 ON ON ON ON ON OFF 54 ON OFF ON OFF ON ON 11 OFF ON OFF ON OFF OFF 33 OFF OFF OFF OFF OFF ON 55 OFF ON O...

Page 11: ...CA 360 converter as shown in Figure 5 If the access control server is located less than 25 feet from the first controller you can connect the access control server directly to the controller s RS 232...

Page 12: ...assigned by the dip switches on each controller see page 9 do not have to correspond to the actual order of controller placement along the RS 485 network However we recommend that this is done to faci...

Page 13: ...CT V900 CONTROLLER 13 Figure 9 Overview of Access Control System Using Centaur 3 0 www cdvgroup com...

Page 14: ...free exit Controlled entry and exit by using 2 readers per door no entry or exit registration Controlled entry and exit by using 2 readers and 2 keypads per door no entry or exit registration Reader...

Page 15: ...ts are protected by fuseless technology and will shutdown if the current exceeds 800mA 12 24VDC If you have one door with a reader on each side of the door you can use either lock output You can progr...

Page 16: ...nd wire fault short circuit recognition but will generate an alarm condition when the state of the input is breached Only odd numbered inputs 1 3 5 need to be programmed ATZ 2R CONNECTION 16 INPUTS Th...

Page 17: ...ators 2 Floors per Elevator 64 Schedules per Floor per Elevator Yes Floor Groups 128 Inputs Readers 2 Wiegand or Track 2 Magnetic Swipe Card Readers Keypads 2 Wiegand and or BCD Keypads Multi Purpose...

Page 18: ...nk Distributed Architecture 100 off line operation Local Anti passback Dynamic Memory Adjustment Operates with all Centaur Software Applications E Bus for Plug and Play expansion modules Ethernet or N...

Page 19: ...CT V900 CONTROLLER 19 DIAGRAMS SYSTEM DIAGRAM Figure 14 Overview of Controller Connections www cdvgroup com...

Page 20: ...the door is monitored by installing a magnetic door contact reed switch Separate wire runs must be installed for each card reader door contact and door locking device With this configuration a card a...

Page 21: ...used so that the system can differentiate between a door forced open and an authorized exit The REX can be programmed for free exit according to a specific schedule otherwise a door forced open event...

Page 22: ...wise including without limitation any implied warranty of merchantability and fitness for a particular purpose are expressly excluded Because Seller does not install or connect the products and becaus...

Page 23: ...31 avenue du G n ral Leclerc 93500 PANTIN T l 33 0 1 48 91 01 02 Fax 33 0 1 48 91 21 21 www cdvgroup com...

Reviews: