5] WIRING DIAGRAM

CONNECTINg ThE BOx TAMPER SWITChES

Connecting the tamper switches allows the 2-Door Controller to detect when the cabinet door is opened and/or 

when the cabinet is removed from the wall. To install the tamper switches, see “Installing the Tamper Switches”.
To use both switches:

1. 

Connect one end of the supplied wire, the one with a log at each end, to the door tamper switch 

 

terminal and the other end to the wall tamper switch terminal.

2. 

Connect the other terminal of the door tamper switch to the “TMP” terminals using the 

 

supplied wire.

3. 

Connect the other terminal of the wall tamper switch to the “GND” terminals using the 

 

supplied wire.

To use only one switch:

1. 

Connect one terminal of the tamper switch to the “TMP” terminals using the supplied wire.

2. 

Connect the other terminal of the same tamper switch to the “GND” terminals using the 

 

supplied wire.

If you do not use the tamper switch, connect a wire between the “TMP” and “GND” terminals.

12V AND SMK TERMINALS

The 12V and SMK terminals are reseved for future use to connect 2-wire smoke detectors.

READER 2

INPUTS

LOCAL

BUS

READER 1

BA

TT

.

POWER

SUPPL

Y

BELL

DOOR 2

12V

Z6

GND

Z7

Z8

C1

NO1

NC1

C2

NO2

NC2

GND

Z9

Z10

12V

Z1

GND

Z2

Z3

GND

Z4

Z5

AC22

2-Door Controller

Metal Box

Door Tamper Switch

(N.C.)

Metal Box

Wall Tamper Switch

(N.C.)

 

1

2

Summary of Contents for ATRIUM AC22

Page 1: ...The installer s choice cdvigroup com ENGLISH EN AC22 2 Door Controller...

Page 2: ...4 Free Technical Support 4 Recommended Wiring 5 Specifications 5 3 PACKAGE CONTENTS 7 Content of the 2 Door Controller 7 Location and Mounting 8 4 MOUNTING INSTRUCTIONS 9 Installing the Tamper Switch...

Page 3: ...with four AX22 2 door expanders Embedded Web Server On board Ethernet Port with AES 256 bit encryption Auto detect hardware modules No DIP Switches Quick and easy card enrollment procedure Multi purpo...

Page 4: ...gand 26 bit 30 bit and 40 bit mag stripe up to 32 digits Use of a UL recognized tamper switch on every housing cabinet for the AC22 2 Door Controller Use only UL listed cables Use only UL listed adapt...

Page 5: ...r Copper Clad Aluminium Do not use any switch controlled outlets to power the system System Resources Doors 2 expandable to 10 doors Cards and users Up to 10 000 cards and users Schedules Up to 250 Sc...

Page 6: ...VLK 12Vdc 750mA AUX 12Vdc 1A BELL 12Vdc 3A up to 40W Battery Against reversal short current limited monitored Power output specifications Battery Backup Battery Capacity 12Vdc 7Ah rechargeable acid le...

Page 7: ...tal Box kit Installation kit If any item is missing please notify your distributor immediately Wall Switch and a white wire 115mm with a log at each end Bolts and Nuts Wall Switch Spacer Door Switch a...

Page 8: ...n Accommodate One 12Vdc 4 5AH or 7AH gel cell type batteries and wiring connections 15cm 6 high 6cm 2 5 wide 9 cm 3 54 deep Battery Model Voltage Capacity Length Width Height YUASA NP7 12 12 Volt 7 Ah...

Page 9: ...prepared before fixing it to its location Installing the Tamper Switches Installing tamper switches allows the AC22 to detect when the cabinet door is opened and or when the cabinet is removed from th...

Page 10: ...e Side View Enclosure Door Nut Spacer Spacer Screw Spacer Install the wall tamper switch using the supplied bolts and nuts as shown in the following picture Install the tamper switch plastic spacer on...

Page 11: ...mounting flange Door Tamper Switch Bracket Door Tamper Switch Mounting Flange Install the door tamper switch by aligning the switch holes to the pre installed plastic bracket pins Press firmly to sec...

Page 12: ...door knock out 2 Insert the lock in the hole 3 Slide the U metal part into the lock groove as shown in the following picture to secure the lock in place Alternatively or complementary to the box lock...

Page 13: ...he Box to its Location Install the box to its location using 4 screws not supplied as shown in the following picture If the wall tamper switch is used make sure that the tamper switch arm moves freely...

Page 14: ...com EN ATRIUM 2 Door Controller INSTALLATION MANUAL Installing the 2 Door Controller PC board Install the 7 fasteners PCB holder supplied respectively to the box holes identified in red in the follow...

Page 15: ...troller PCB by aligning the fasteners with the corresponding PCB holes and pressing firmly to secure the PCB in place READER 2 INPUTS LOCAL BUS READER 1 BATT POWER SUPPLY BELL DOOR 2 12V Z6 GND Z7 Z8...

Page 16: ...other terminal of the door tamper switch to the TMP terminals using the supplied wire 3 Connect the other terminal of the wall tamper switch to the GND terminals using the supplied wire To use only o...

Page 17: ...on Automatic shutdown of bell output on over current Programmable Automatic restore either on next deactivation activation cycle or after a programmable reset delay Connect the bell s and or siren s o...

Page 18: ...ternal sounding device will inform the card user that the door has been left open after a valid access or the door has been forced open The functions of all these outputs are programmable through the...

Page 19: ...ew motion detector or floor mat sensor The door can then be programmed to unlock on a REX detection Not required if there is a reader keypad on both sides of the door When a magnetic door contact is i...

Page 20: ...per INPUT in Software as described in the following figure This setup will not support WIRE CUT supervision but offers WIRE SHORT supervision and will generate an alarm condition when the state of th...

Page 21: ...l support WIRE CUT supervision but not WIRE SHORT supervision and will generate an alarm condition when the state of one of the input is breached WIRE SHORT supervision NO WIRE CUT supervision YES Det...

Page 22: ...that the current specifications are not exceeded Always consult the regulatory agency in your area for existing regulations regarding doors designated as emergency exits Jumper Settings The jumpers L...

Page 23: ...0V Electromagnetic Option Door Strike Option Lock Outputs 750mA 12Vdc INPUTS LOCAL BUS DOOR 2 DOOR 1 12V Z6 GND Z7 Z8 C1 NO1 NC1 C2 NO2 NC2 GND Z9 Z10 N C DRY CONTACT A B C PowerSupply PowerSupply N O...

Page 24: ...t the pre installed green power LED to the 2 Door Controller DC Power Supply and terminals in parallel with the AC DC power supply The red wire goes on the terminal and the white on the terminal Make...

Page 25: ...se type 250VAC 2 5 A Time Lag Slow Blow Operating Temperature 55oC to 125oC Permitted replacements a Littelfuse P N 021802 5MXP b Schurter P N 0034 3121 c Various means any type from any manufacturer...

Page 26: ...2Vdc 7Ah rechargeable acid lead or gel cell backup battery UL ULC YUASA NP7 12 recommended Europe CDVI B7AH recommended Ensure proper polarity Various means any type from any manufacturer that complie...

Page 27: ...Flash rapidly Firmware is upgrading Blink once per 3 seconds Card enrollment mode DC IN DC IN Green LED 2 Door Controller is powered properly Red LED No primary power BATT BATT Green LED Primary power...

Page 28: ...ection from a local PC or interconnect to an existing LAN WAN Connect the Ethernet 10 100 Mbps port of the ATRIUM 2 Door Controller to a LAN or WAN network using an UTP cable maximum 100m 300ft READER...

Page 29: ...wires Connect the expander module s using these topologies cdvigroup com cdvigroup com cdvigroup com cdvigroup com cdvigroup com AC22 AX22 AX22 AX22 AX22 cdvigroup com cdvigroup com cdvigroup com cdv...

Page 30: ...in sequence 2 Red flashes 2 Green 3 Present cards one by one to the reader NEW cards will be ADDED Green LED will flash and a pulsed beep will be emitted Each new card will create a user and attribut...

Page 31: ...s one by one to the reader NEW cards will be ADDED Green LED will flash and a quick beep will be emitted Each new card will create a user and attribute the card to the user EXISTING cards will be DELE...

Page 32: ...in the event of loss or non presentationof the form The 5 Year Warranty only applies to products installed by a skilled and experienced personal with the necessary trade qualifications to install acc...

Page 33: ...sumables such as fuses lights and batteries for example Failure or malfunctioning as a result of an accident poor storage conditions unsuitable assembly bad utilization or handling poor maintenance un...

Page 34: ...34 cdvigroup com EN ATRIUM 2 Door Controller INSTALLATION MANUAL NOTES...

Page 35: ...35 cdvigroup com EN ATRIUM 2 Door Controller INSTALLATION MANUAL NOTES...

Page 36: ...CE EXPORT Phone 33 0 1 48 91 01 02 Fax 33 0 1 48 91 21 21 CDVI AMERICAS CANADA USA LATIN AMERICA Phone 1 450 682 7945 Fax 1 450 682 9590 CDVI BENELUX BELGIUM NETHERLAND LUXEMBOURG Phone 32 0 56 73 93...

Reviews: