REVO SX

 

User’s manual

5

WARNING! 

All service including inspection, installation, wiring, maintenance, troubleshooting, fuse 

or  other  user  serviceable  component  replacement  must  be  performed  only  by  properly  qualified 

personnel. Service personnel must read this manual before proceeding with work. While service is 

being performed unqualified personnel should not work on the unit or be allowed in the immediate 

vicinity.

AVERTISSEMENT! 

Tous les services, y compris l’inspection, l’installation, le câblage, l’entretien, le 

dépannage, le remplacement de fusibles ou d’autres composants pouvant être réparés par l’utilisateur, 

doivent être effectués uniquement par un personnel diment qualifié. Le personnel de service doit lire ce 
manuel avant d’effectuer tout travail. Pendant que l’entretien est exécuté, tout personnel non qualifié ne 
doit effectuer de travail sur l’appareil ni se trouver a proximité.

WARNING!

 When in use the power controller is connected to dangerous voltages. Do not remove the 

protective covers without first disconnecting and preventing power from being restored while servicing 

the unit.

AVERTISSEMENT!

 Au moment de l’utilisation, le régulateur de puissance est connecté a des tensions 

dangereuses. Ne retirer aucun couvercle de protection sans d’abord débrancher l’appareil et ainsi 
empêcher l’alimentation d’être rétablie pendant l’entretien.

WARNING!

 Do not use in aerospace or nuclear applications.

AVERTISSEMENT!

 Ne pas utiliser pour les applications aérospatiales ou nucléaires.

WARNING!

 The units are not developed to manage capacitive and inductive loads.

AVERTISSEMENT!

 Les unités ne sont pas développées pour la conduite de charges capacitives et 

inductives.

WARNING!

 The power controller’s protection rating is IP20 with all covers installed and closed. It must 

be installed in an enclosure that provides all the necessary additional protections appropriate for the 
environment and application.

AVERTISSEMENT!

 L’indice de protection du régulateur de puissance est de IP20 lorsque les couvercles 

sont installés et fermés. L’appareil doit être installé dans une enceinte qui assure toute la protection 
supplémentaire nécessaire pour l’environnement et l’application.

WARNING!

 Ground the power controller via the provided protective earth grounding terminal. Verify 

ground is within impedance specifications. This should be verified periodically.

AVERTISSEMENT!

 Mise a la terre du régulateur de puissance par le biais de la borne de prise de terre 

de protection fournie. Vérifier que la prise de terre est conforme aux spécifications de l’impédance. Cela 
doit être vérifié périodiquement.

WARNING! 

Electric Shock Hazard: when the power controller has been energized, after shutting off the 

power, wait at least one minute for internal capacitors to discharge before commencing work that brings 
you in to contact with power connections or internal components.

AVERTISSEMENT!

  Risque de décharges électriques: lorsque le régulateur de puissance est mis sous 

tension, après avoir été éteint, attendre au moins une minute pour que les condensateurs internes se 
déchargent avant de commencer tout travail incluant le contact avec les connexions électriques ou les 
composants internes.

WARNING!

 The installation must be protected by electromagnetic circuit breakers or by fuses. The 

semiconductor  fuses  located  inside  the  power  controller  are  classified  for  UL  as  supplementary 

protection for semiconductor devices. They are not approved for branch circuit protection.

AVERTISSEMENT!

 L’installation doit être protégée par des disjoncteurs électromagnétiques ou des 

fusibles. Les fusibles pour semi-conducteurs situés a l’intérieur du régulateur de puissance sont classés 
UL comme protection supplémentaire pour les dispositifs pour semi-conducteurs. Ils ne sont pas 
approuvés pour la protection des circuits de dérivation.

WARNING! 

When making live voltage or current measurements, use proper personal protective 

equipment for the voltages and arc-flash potentials involved.

Summary of Contents for REVO SX Series

Page 1: ...L Rev 07 2019 Solid State Relay 4x3 5A 3x4 5A 2x7A 005 M RSX CD Automation S r l Via Picasso 34 36 20025 Legnano MI Italy Tel 39 0331 577479 Fax 39 0331 579479 E mail info cdautomation com Web www cdautomation com ...

Page 2: ......

Page 3: ...ANDARD Electrical safety Standard EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Generic Emission standard EN60947 4 3 2014 Group 1 Class A emissions Generic Immunity standard EN60947 4 3 2014 Industrial Immunity SODDISFA I REQUISITI DELLA NORMA Specifica di sicurezza EN60947 1 2007 A1 2011 A2 2014 EN60947 4 3 2014 Specifica sulle emissioni EN60947 4 3 2014 gruppo 1 emissioni classe A Specifica s...

Page 4: ...witches and equivalent to CSA C22 2 14 For more detail search for File E231578 on www ul com ESD Sensitive product use proper grounding and handling techniques when installing or servicing product Do not throw in trash use proper recycling techniques or consult manufacturer for proper disposal A NOTE marks a short message to alert you to an important detail A CAUTION safety alert appears with info...

Page 5: ... environment and application AVERTISSEMENT L indice de protection du régulateur de puissance est de IP20 lorsque les couvercles sont installés et fermés L appareil doit être installé dans une enceinte qui assure toute la protection supplémentaire nécessaire pour l environnement et l application WARNING Ground the power controller via the provided protective earth grounding terminal Verify ground i...

Page 6: ... thyristor units here described have been designed for use with sinusoidal networks with nominal frequency 50 60 Hz Any application with NON SINUSOIDAL distorted or disturbed networks could compromise the correct operation of the unit ATTENTION Les unités de thyristors décrites ici ont été conçues pour être utilisées avec des réseaux sinusoïdaux d une fréquence nominale de 50 à 60 Hz Toute applica...

Page 7: ... RMA Customers wishing to return any items whether they are incorrectly supplied faulty or damaged in transit must first complete a Return Material Authorisation RMA form to obtain an RMA number from the Service Department A full repair service is available for customers Prior to submitting the RMA form and returning products customers are recommended to contact the technical support team to deter...

Page 8: ... Derating Curve 10 Firing Type 11 Installation 12 Dimensions and Fixing holes 12 Wiring instructions 13 Terminals 230V 13 Terminals 480V 14 Diagram of control connection 4x3 5A 230V 15 Diagram of control connection 4x3 5A 480V 16 Diagram of control connection 3x4 5A 230V 17 Diagram of control connection 3x4 5A 480V 18 Diagram of control connection 2x7A 230V 19 Diagram of control connection 2x7A 48...

Page 9: ...SX R S X _ _ _ _ _ _ _ _ _ _ _ _ _ 2 NUMBER OF ZONES X CURRENT RATING 4 5 6 description code 4 zones 3 5A each 4 0 3 3 zones 4 5A each 3 0 4 2 zones 7A each 2 0 7 MAX VOLTAGE 7 description code 230V 2 480V 4 VOLTAGE SUPPLY AUX 8 description code No Auxiliary Voltage with 230V 0 INPUT 9 description code SSR S FIRING 10 description code Zero Crossing Z Random used with REVO PC R CONTROL MODE 11 desc...

Page 10: ...47 70Hz Power loss I Inom 4x4 2W 3x5 4W 2x8 4W Isolation Voltage Ui 2500Vac Environmental installation conditions Ambient temperature 0 40 C 32 104 F at nominal current Over 40 C use the derating curve Storage temperature 25 C to 70 C 13 F to 158 F Installation place Don t install at direct sun light where there are conductive dust corrosive gas vibration or water and also in salty environmental A...

Page 11: ...ut from temperature controllers and the Thyristor operates like a contactor The Cycle time is performed by temperature controller ZC minimizes interferences because the Thyristor unit switches ON OFF at zero voltage 4 ON OFF Voltage Supply V Load Voltage V SSR from controller ...

Page 12: ...Maintain minimum distances in vertical and in horizontal as represented Don t install in proximity of hot elements and near units generating electromagnetic interferences When more units are mounted in the same cabinet provide air circulation as represented Sometimes it is necessary to provide a fan to have better air circulation Dimensions and Fixing holes 5 cm 15 cm 2 cm AIR AIR 5 36 mm 48 mm 86...

Page 13: ...ble dimensions suggested Each terminal can reach 12A using a wire with 1 5mm of diameter if you use all the 4 zones in the ON condition at the same time connecting more terminals 13 14 15 16 at the line power Power cable torque suggested MAX Current Each terminal Connector Type Torque Lb in Nm Wire Range mm AWG Wire Terminal 12A Estraibile Connectors 4 42 0 5 0 5 1 5 18 14 Rigid Flexible Wire Pin ...

Page 14: ...dc 4 20mA 6 Z2 Control Input SSR 0 10Vdc 4 20mA 7 Z1 Control Input SSR 0 10Vdc 4 20mA 8 Z1 Control Input SSR 0 10Vdc 4 20mA 9 Not connected 10 Not connected 11 Aux Voltage Supply for electronic boards 12 24V AC DC 12 Aux Voltage Supply for electronic boards 12 24V AC DC 13 Load Output Z4 14 Load Output Z3 15 Load Output Z2 16 Load Output Z1 17 Line Input 18 Line Input 19 Line Input 20 Line Input A...

Page 15: ...SR Z2 SSR Z3 SSR Z4 Z3 Z4 LOAD 11 10 9 8 7 6 5 4 3 2 1 Note A suitable device must ensure that the unit can be electrically isolated from the supply this allows the qualified people to work in safety Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources ...

Page 16: ...ted from the supply this allows the qualified people to work in safety Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources Not connected L1 L2 L1 L2 20 19 18 17 16 Z1 Z2 Input SSR Z1 SSR Z2 SSR Z3 SSR Z4 Z3 Z4 LOAD 15 14 13 8 7 10 9 12 11 AUX 12 24 AC DC only with 480V 6 5 4 3 2 1 ...

Page 17: ...t can be electrically isolated from the supply this allows the qualified people to work in safety Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources L1 N L1 N 16 15 14 13 12 Z1 Z2 Input SSR Z1 SSR Z3 SSR Z2 Z3 LOAD 11 10 9 8 7 6 5 4 3 2 1 Not connected ...

Page 18: ...isolated from the supply this allows the qualified people to work in safety Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources Not connected L1 L2 L1 L2 20 19 18 17 16 Z1 Z2 Input SSR Z1 SSR Z2 SSR Z3 Z3 LOAD 15 14 13 8 7 10 9 12 11 AUX 12 24 AC DC only with 480V 6 5 4 3 2 1 ...

Page 19: ...it can be electrically isolated from the supply this allows the qualified people to work in safety Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources L1 N L1 N 16 15 14 13 12 Z1 Z2 Input SSR Z1 SSR Z3 Z3 Z4 LOAD 11 10 9 8 7 6 5 4 3 2 1 Not connected ...

Page 20: ... isolated from the supply this allows the qualified people to work in safety Before connecting or disconnecting the unit check that power and control cables are isolated from voltage sources Not connected L1 L2 L1 L2 20 19 18 17 16 Z1 Z2 Input SSR Z1 SSR Z3 Z3 Z4 LOAD 15 14 13 8 7 10 9 12 11 AUX 12 24 AC DC only with 480V 6 5 4 3 2 1 ...

Page 21: ...r s manual 21 Led status and Alarms 7 FUS ON Z1 FUS ON Z1 FUS ON Z1 FUS ON Z1 FUS RED FUS OFF Fuse OK Fuse Fault ON ON Z1 FUS ON Z1 FUS ON Z1 FUS ON Z1 230V 480V GREEN ON OFF Load is NOT powered Loas IS powered ON ...

Page 22: ...igh speed fuses are used only for the thyristor protection and can not be used to protect the installation Caution The warranty of thyristor is null if no proper fuses are used see table Spare Fuse Order Code REVO 4x3 5A FU5X20 4 Only one pcs Type 5x20 4A 250V fast 0324004 REVO 3x4 5A FU5X20 5 Only one pcs Type 5x20 6A 250V fast 0324005 REVO 2x7A FU5X20 8 Only one pcs Type 5x20 10A 250V fast 03250...

Page 23: ...CD Automation S r l Via Picasso 34 36 20025 Legnano MI Italy Tel 39 0331 577479 Fax 39 0331 579479 E mail info cdautomation com Web www cdautomation com ...