24
REVO C
2PH from 60A to 800A - 690V
User’s manual
Wiring instructions
The Thyristor unit could be susceptible to interferences lost by near equipments or by the power supply, for
this reason in accord to the fundamental practices rules is opportune take some precautions:
•
The coil contactor, the relays and other inductive loads must be equipped with opportune RC filter.
• Use shielded bipolar cables for all the input and output signals.
• The signal cables must not be near and parallel to the power cables.
• Local regulations regarding electrical installation should be rigidly observed.
Use 75°C copper (CU) conductor only or use copper bus bars sized for field wiring connection, wire ranges
(AWG), wire terminal type (ZMVV), tightening torque in the tables below.
8.1 Removing the cover
Instructions for open the thyristor unit
8
8.2 Line power and Load cable/bar dimensions and torque (suggested)
Current
Connector Type
Torque
Cable
Cable Terminal
Bar
Lb-in
Nm
AWG
mm
2
kcmil
60A (S11)
Screw M8
177
20.0
5
16
33.1
UL Listed (ZMVV)
Copper Tube Crimp. Lug
-
90A (S11)
177
20.0
3
25
52.6
-
120A (S13)
177
20.0
2
35
66.4
-
150A (S13)
177
20.0
0
50
106
-
180A (S13)
177
20.0
00
70
133
-
210A (S13)
177
20.0
000
90
168
-
300A (S14)
Power field wiring Bus
Bar with M10 screw
265
30.0
2 x 1/0
2 x 70
350
Bus bar
30x5 mm
400A (S14)
265
30.0
2 x 3/0
2 x 95
600
Bus bar
66x4mm
450A (S14)
265
30.0
2 x 4/0
2 x 95
700
Bus bar
66x6 mm
500A (S14)
265
30.0
-
2 x 150
2x250
900
Bus bar
66x6 mm
600A (S14)
265
30.0
-
2 x 185
2x350
1500
Bus bar
66x6 mm
700A (S14)
265
30.0
-
2 x 300
2x500
Bus bar
66x6 mm
800A (S16)
265
30.0
-
2 x 300
2x500
Bus bar
66x6 mm