24
CD3000S
2PH from 10A to 90A
User’s manual
Firing Setting
8.1 Firing Setting with Analog Input Option
The BF firing performed in Digital mode in the Thyristor unit give a lot of advantages because switches Thyristor
at zero voltage crossing (ZC) without EMC interferences. Analog input is necessary for BF and can be decided
how many complete Cycle we want at 50% of power demand.
This value can be 4, 8 or 16 complete Cycles.
8
Firing Type
JP4
JP5
BF4
Open
Open
BF8
Close
Open
BF16
Open
Close
8.2 Firing Setting with Heater Break Option
ZC firing mode is used with Logic Output from temperature controllers and the Thyristor operates like a
contactor. The Cycle time is performed by temperature controller. ZC minimizes interferences because the
Thyristor unit switches ON-OFF at zero voltage.
SSR from controller
VOLTAGE SUPPLY (V)
LOAD VOLTAGE (V)
JP2
JP3
JP6
G1
K1
K2
G2
JP1
+
+
+
-
JP4
JP5
K1
K2
G2
JP4
35A-90A
JP5
Summary of Contents for CD3000S2PH