2.0 Opening/Closing the Breaker 

 

Step 1

: Open the RSO-IIID lid by disengaging the two latches on the front of the case, this will 

expose the user interface panel and the cord storage area.  

  

 

 

     

Step 2

: Remove the three pin twist-lock style cable from the RSO-IIID cord storage area and 

connect the cable to the corresponding plug on the RSA-80A. 
 

ATTENTION! 

Please ensure that all cables are clear of moving parts.  Failure to do so could damage 

cables and/or actuator. 

 

Step 3: 

Verify the unit is properly installed on the switchgear and connected to the RSO-IIID as 

previously described. 

 

Step 4:

 Turn the switch on the RSA-80A motor control box to the corresponding operation to be 

performed (Either Close or Trip). 

 
Step 5

: Turn the power switch on the RSO-IIID to the “ON” position and input the settings based 

on the placard on the RSA-80A based on the corresponding operation to be performed.  Exit the 
arc flash boundary. 

 

ATTENTION 

Please ensure that either the batteries on the unit are fully charged or the unit is plugged 

into AC power. 

 

Step 6

: If equipped with the wireless remote option, ensure users turn the green activation 

switch past the “ON” indication to the “START” indication in the window of the activation 

switch. 

 

Step 7: 

Press the “CHARGE/CLOSE” button to operated the RSA-80A in the applicable CLOSE or 

TRIP direction.  NOTE: Pressing the “TRIP” button will yield no operation on the RSA.  Users 
must press the “CHARGE/CLOSE” button to operate even in the “TRIP” direction.  Users choose 
the operation to be performed on the selector switch on the RSA-80A motor control box prior 
to operation. 
 

 
 

 

 

Summary of Contents for RSA-80A

Page 1: ...CBS ArcSafe RSA 80A For Westinghouse DB 25 CBS ArcSafe Inc 2616 Sirius Road Denton TX 76208 940 382 4411 www cbsarcsafe com Installation and Operation...

Page 2: ...uctions around the switch that will interfere with RSA installation as shown below ATTENTION The location of certain items such as mimic bus stickers and or placards may interfere with the installatio...

Page 3: ...ise Step 5 When installed make sure that both magnets are sitting flush with the door and that the RSA 80A is sitting level with respect to the horizontal plane A small bubble level on the backside of...

Page 4: ...lowing image which shows travel stop adjustments Step 2 Another adjustment which may need to be made is the location of the RSA 80A motor assembly Adjusting the motor assembly may be necessary in the...

Page 5: ...ep 3 The height of the RSA 80A motor assembly may also be adjusted to account for varying depths of doors or breaker CLOSE TRIP switches See the following image for details This procedure will have to...

Page 6: ...be performed Either Close or Trip Step 5 Turn the power switch on the RSO IIID to the ON position and input the settings based on the placard on the RSA 80A based on the corresponding operation to be...

Page 7: ...RSA 80A Installation and Operation Page 7...

Page 8: ...they are correctly stationed outside the arc flash boundary and that they comply with all applicable Federal State Local and In house safety regulations and procedures Attention should be given to dis...

Reviews: