1.1

 

RSA-169A Adjustment Locations 

 

Step 1

: Users may adjust the travel of the RSA-80A in either the “CLOSE” and/or “OPEN” 

directions if necessary.  Travel adjustment may be necessary if the RSA does not fully operate 
the breaker to the desired position, or conversely if it over travels the switch.  See the following 
image which shows travel stop adjustments. 

 

 
Step 2

: Another adjustment which may need to be made is the location of the RSA-80A motor 

assembly.  Adjusting the motor assembly may be necessary in the event that a magnet or other 
component on the RSA interferes with a component on the breaker or door.  See the following 
image for directions on adjusting the motor assembly location on the RSA-80A frame. 

 

“CLOSE” Direction stop: 

Move up for more travel; 

move down for less travel 

“OPEN” Direction stop: 

Move down for less travel; 

move up for more travel 

Summary of Contents for RSA-80A

Page 1: ...CBS ArcSafe RSA 80A For Westinghouse DB 25 CBS ArcSafe Inc 2616 Sirius Road Denton TX 76208 940 382 4411 www cbsarcsafe com Installation and Operation...

Page 2: ...uctions around the switch that will interfere with RSA installation as shown below ATTENTION The location of certain items such as mimic bus stickers and or placards may interfere with the installatio...

Page 3: ...ise Step 5 When installed make sure that both magnets are sitting flush with the door and that the RSA 80A is sitting level with respect to the horizontal plane A small bubble level on the backside of...

Page 4: ...lowing image which shows travel stop adjustments Step 2 Another adjustment which may need to be made is the location of the RSA 80A motor assembly Adjusting the motor assembly may be necessary in the...

Page 5: ...ep 3 The height of the RSA 80A motor assembly may also be adjusted to account for varying depths of doors or breaker CLOSE TRIP switches See the following image for details This procedure will have to...

Page 6: ...be performed Either Close or Trip Step 5 Turn the power switch on the RSO IIID to the ON position and input the settings based on the placard on the RSA 80A based on the corresponding operation to be...

Page 7: ...RSA 80A Installation and Operation Page 7...

Page 8: ...they are correctly stationed outside the arc flash boundary and that they comply with all applicable Federal State Local and In house safety regulations and procedures Attention should be given to dis...

Reviews: