background image

Published and distributed by: 
CBS ArcSafe®

 

2616 Sirius Road 
Denton, Texas 76208 

A division of: 
GroupCBS, Inc.® 
P.O. Box 1557 
Gainesville, Texas 76241 

Copyright CBS ArcSafe

®

 2013 

Printed in the United States of America 
Reproduction, adaptation, or translation without prior written permission is prohibited except as is allowed by law. 

 

 

 

 

RSA-138A 

 

In

st

allat

io

n an

d O

pe

rat

io

2616 Sirius Road 

|

 Denton, TX 76208 

|

 (877) 4-SAFETY 

|

 www.cbsarcsafe.com 

Allis-Chalmers/Siemens-Allis LBS-SE2 

Rev. 1/31/2019 

Distance

 

is

 

Safety

®

 

WE 

DO. 

WHA T  STA ND S  

BETWEE N YOU A ND  

ARC-F LASH  DA NGE R? 

Summary of Contents for RSA-138A

Page 1: ...inted in the United States of America Reproduction adaptation or translation without prior written permission is prohibited except as is allowed by law RSA 138A Installation and Operation 2616 Sirius Road Denton TX 76208 877 4 SAFETY www cbsarcsafe com Allis Chalmers Siemens Allis LBS SE2 Rev 1 31 2019 DistanceisSafety WE DO WHAT STANDS BETWEEN YOU AND ARC FLASH DANGER ...

Page 2: ...y install and remove a particular type of circuit breaker safely while stationed safely outside of the arc flash boundary during the potentially dangerous operation The lightweight and compactdesignofthe RRS 3 systems makes them ideal for hard to access areas where space is at a premium RRS 4 PLC Based Universal Remote Racking System Rotary The CBS ArcSafe RRS 4 universal remote racking system is ...

Page 3: ... stickers and or placards may interfere with the proper installation of theRSA Please remove or reposition these itemsbeforeinstallingtheRSA 1 Ensure that theswitch is free from anyobstructionthatmayinterferewiththeproperinstallationofthe RSA 2 Align the RSA to the handle escutcheon on the opposite side of the switch s operating handle then slide the handle adapter of the RSA over the switch handl...

Page 4: ...e that the upper locator on the RSA is flush with the top and side of the switch escutcheon as shown 4 Turn the handles of the twit lock magnets 180 clockwise to lock the RSA in place 5 Install the interlock defeat onto the switch handle as shown ...

Page 5: ...RSA 138A Installation and Operation 3 The RSA is now ready for remote operation ...

Page 6: ...RSO I AR please see the RSO I AR Manual 1 Ensure that theRSA is properly installed SeeSection3 for detailed instructions 2 Plug the RSO I AR into the motor control box 3 Exit the arc flash boundary 4 Turn the power switch on the RSO I AR to the ON posi tion 5 Ensure that the Auto Retract AR function is OFF 6 If the breaker is CLOSEDandneedstobeopened press and hold the TRIP button on the RSO I AR ...

Page 7: ...y be done on de energized and isolated equipment to prevent possible damage or injury 3 1 Locator Adjustment The depth of the handlelocator on the RSA can be adjusted in order to avoid interference from items mounted to the switchgear door 1 Loosen the two bolts on the locator plate as shown below 2 Slide the locators up or down as necessary to position them flush to the upper and side edgeoftheha...

Page 8: ... breaker 1 Install the RSA on the face of the breaker as described in the Installation section 2 Loosen the lock screws on the backs of the two switch wheels 3 With the RSA operator arm in the OPEN position rotate the outer limit switch cam in the direction of travel for the arm until a slight click is heard Re tighten the lock screw ...

Page 9: ... Installation and Operation 7 4 With the RSA operator arm in the CLOSED position rotate the inner limit switch cam in the direction of travel for the arm until a slight click is heard Re tighten the lock screw ...

Page 10: ......

Page 11: ...RSA 138A Installation and Operation 9 Notes ...

Page 12: ...ith that they are correctlystationedoutsidethearcflash boundary and that they comply with all applicable Federal State Local and In house safety regulations and procedures Attention should begiven to distance angle and personal protec tive equipment PPE 2616 Sirius Road Denton TX 76208 Tel 877 4 SAFETY Fax 940 382 9435 Website www CBSArcSafe com Email info CBSArcSafe com ...

Reviews: