Display Units
*
Units that are displayed on the gauges
–
Calibration Zero Offset
*
Offset to calibrate the 4 mA value (plus or minus 5%)
•
Low Warning Alarm
–
Value in display units that will generate a Low warning
•
Low Shutdown Alarm
–
Value in display units that will generate a Low shutdown
•
High Warning Alarm
–
Value in display units that will generate a High warning
•
High Shutdown Alarm
–
Value in display units that will generate a High shutdown
7.6 Scheduler
Setting the “Start/Stop with” to be “Scheduler Only” causes the engine to be started and stopped based on the
schedule defined by the
Autostart
→
Behavior
→
Start/Stop with
→
Scheduler Only
menu.
Next, set the Scheduler Method to Override by going to the
Autostart
→
Scheduler
→
Method
menu. Using the
Override method will override any autostart settings.
The Scheduler mode starts and stops the engine based on time and date. Up to 16 unique scheduled run cycles
can be configured offering multiple run cycles per day, and those run cycles can differ depending on the day of
the week.
The Scheduler has another method called Allowed Times. Unlike the Override method, this method marries the
Autostart setting with the Scheduler, allowing the autostart to only occur during the allowed times. For example,
with this method the panel can be configured to only autostart on Mondays, Wednesdays and Fridays between
the times of 12:00 p.m. and 3:00 p.m. Up to 16 unique allowed times can be configured.
7.7 Timed Run
The Timed Run mode allows for a manually-initiated start with the stop event being automatically triggered
based on running time. This mode allows the operator to walk away from a running system knowing that it will
automatically stop after a predetermined amount of time. There are no automatic restarts in this mode. All starts
are manually initiated by pressing the Autostart switch.