background image

IOM-3381/4381

2

III. PRINCIPLE OF OPERATION

1.  Movement  occurs  as  pressure  variations  regis-

ter on the diaphragm.  The registering pressure 

is the outlet, P

2

, or downstream pressure.  The 

range spring opposes diaphragm movement.  As 

SECTION III

IV. STARTUP

SECTION IV

5.  Slowly open the inlet (upstream) block valve ob-

serving the outlet (downstream) pressure gauge.  

Determine if the regulator is flowing.  If not, slowly 

rotate  the  regulator  adjusting  screw  clockwise 

(CW) until flow begins.

6.  Continue to slowly open the inlet (upstream) block 

valve until fully open.

7.  Continue to slowly open the outlet (downstream) 

block valve, especially when the downstream pip-

ing system isn't pressurized.  If the outlet  (down-

stream) pressure exceeds the desired pressure, 

close the block valve and go to Step 2, then return 

to Step 4.

8.  When flow is established steady enough that the 

outlet (downstream) block valve is fully open, be-

gin to slowly close the bypass valve if installed.

9.  Develop system flow to a level near its expected 

normal rate, and reset the regulator set point by 

turning the adjusting screw CW to increase outlet 

pressure, or CCW to reduce outlet pressure.

10.  Reduce  system  flow  to  a  minimum  level  and 

observe set point.  Outlet pressure will rise from 

the  set  point  of  Step  9.    The  maximum  rise  in 

outlet  pressure  on  decreasing  flow  should  not 

exceed the stated upper limit of the range spring 

by greater than 10%; i.e. 20-80 psig (1.38-5.52 

Barg)  range  spring.    (Example:  at  low  flow  the 

outlet pressure should not exceed 88 psig (6.07 

barg), if it does, consult factory). 

CAUTION

outlet pressure drops, the range spring pushes 

the diaphragm down, opening the port; as outlet 

pressure  increases,  the  diaphragm  pushes  up 

and the port opening closes.

2.  A complete diaphragm failure will cause the regu-

lator to fail open.  

10 A.   Basic Regulator - (Refer to Figure 1, Model 3381 

or 4381):  Regulator may be rotated around the 

pipe axis 360°.  Recommended position is with 

spring  chamber  vertical  upwards.    Orient  such 

that the spring chamber vent hole does not col-

lect rainwater.

10B.  Cryogenic Regulator - Options 3381-5 and 4381-

36 (Refer to Figure 2, Model 3381 or 4381):

a.  Recommended  installation  is  with  spring 

chamber  hanging  directly  below  the  body 

in a vertical downwards orientation.  Allows 

water to drain; etc.

b.  Recommend inert purge gas be supplied to 

spring  chamber  through  vent  hole  and  be 

discharged out drain hole.

11.  Regulators are not to be buried underground.

12.  For insulated piping systems, recommendation is 

to not insulate regulator.

           CAUTION

The maximum outlet pressure is listed on the nameplate 

as the upper range spring pressure level, and is the recom-

mended "upper operative limit" for the sensing diaphragm 

(See Section IV. Startup, Step 7). Higher press ures could 

damage the diaphragm.  (Field hydrostatic tests frequently 

destroy diaphragms.   DO NOT HYDRO STATIC TEST THRU 

AN INSTALLED UNIT; ISOLATE FROM TEST.)

1.  Start  with  the  block  valves  closed.    A  bypass 

valve  may  be  used  to  maintain  outlet  pressure 

in the downstream system without changing the 

following steps.

2.  Relax the range spring by turning the adjusting 

screw  counter  clockwise  (CCW)  a  minimum  of 

three (3) full revolutions.  This reduces the outlet 

(downstream) pressure set point.

3.  If it is a “hot” piping system, and equipped with 

a  bypass  valve,  slowly  open  the  bypass  valve 

to preheat the system piping and to allow slow 

ex pan sion  of  the  piping.    Ensure  proper  steam 

trap operation if installed.  Closely monitor outlet 

(downstream) pressure via gauge to ensure not 

over-pressurizing.  

NOTE:

  

If no bypass valve is 

installed, extra caution should be used in starting 

up a cold system; i.e. do everything slowly.

4.  Crack open the outlet (downstream) block valve.

Summary of Contents for 3381

Page 1: ...n sight 5 Allinstallationsshouldincludeadownstreamrelief device if the inlet pressure could exceed the pres sure rating of any downstream equip ment or the maximum outlet pressure rating of the unit 6...

Page 2: ...mplete diaphragm failure will cause the regu lator to fail open 10 A Basic Regulator Refer to Figure 1 Model 3381 or 4381 Regulator may be rotated around the pipe axis 360 Recommended position is with...

Page 3: ...ultiple metal diaph ragms may be stacked 6 Loosen pusher plate nut 10 and separate all parts 3 4 9 13 15 of the diaphragm subassembly 7 Inspect pressure plate 3 to ensure no deformation due to over pr...

Page 4: ...if worn nickedordepressed Ifintegralseatisnicked useseatlappingcompoundtoremove Valves 8 Remove diaphragm s 13 and diaphragm gasket s 14 9 Clean body 1 and diaphragm flange Do not scratch diaphragm ga...

Page 5: ...develop bubble tight shutoff In general tighter shutoff can be expected with composition seat 11 Pressurize with air and spray liquid leak de tector to test around body cap 6 and body 1 for leakage Te...

Page 6: ...r and Product Code that was stamped on the metal name plate and attached to the unit This information can also be found on the Bill of Material parts list that was provided when unit was originally sh...

Page 7: ...Plate Nut 11 Adjusting Screw Locknut 12 Nameplate 13 Diaphragm 14 Diaphragm Gasket s 15 Pusher Plate Gasket 16 Piston 17 Range Spring 18 Handwheel 19 Mounting Nut Figure 1 Basic Model 3381 with Metal...

Page 8: ...e Spring Chamber Construction Option 2 80 Handwheel NOT available with Option 22 Repair Parts Item No Description Kit B 1 Body 2 Spring Chamber 3 Pressure Plate 4 Pusher Plate 5 Spring Button 6 Body C...

Reviews: