17
Electrical Wiring
The wiring for the power line of indoor unit, the wiring between indoor and outdoor units as well as the wiring between
indoor units is as per the table below:
• The electrical power line and signal lines must be fastened tightly.
• Every indoor unit must have a ground connection.
• The power line should be enlarged if it exceeds the permissible length.
• Shielded lays of all the indoor and outdoor units should be connected together, with the shielded lay at the side of signal
lines of outdoor units grounded at one point.
• The length of signal line should not exceed 1000m.
• The shielding lay of the signal line must be grounded at one end.
• The total length of the signal line shall not be more than 250m.
Signal Wiring of Wired controller
Length of Signal Line (m)
Wiring Dimensions
≤250
0.75mm
2
× core shielding line
Items
Total
Current of
Indoor Units(A)
Cross
Section
(mm
2
)
Length
(m)
Rated
Current of
Overflow
Breaker(A)
Rated current of residual
Circuit Breaker(A)
Ground Fault
Interruptor(mA)
Response time(S)
Cross Sectional
Area of Signal Line
Outdoor -indoor
(mm
2
)
Indoor -indoor
(mm
2
)
<6
2.5
20
6
6A,30mA,0.1S or below
2 cores×0.75-2.0mm
2
shielded line
≥6
and <10
2.5
20
10
10A,30mA,0.1S or below
≥10
and <16
4
25
16
16A,30mA,0.1S or below
≥16
and <25
6
30
25
25A,30mA,0.1S or below
≥25
and <32
10
50
32
32A,30mA,0.1S or below
Summary of Contents for XCT 7 40VD072H-7S-QEE
Page 21: ...14 Installation Procedures Address Indication Indication Indication Indication ENGLISH...
Page 30: ...The manufacturer reserves the right to change any product specifications without notice...
Page 47: ...14 Procedure di installazione Address Indication Indication Indication Indication ITALIANO...
Page 73: ...14 Proc dures d installation Address Indication Indication Indication Indication FRAN AIS...
Page 82: ...Le fabricant se r serve le droit de modifier les sp cifications du produit sans pr avis...
Page 99: ...14 Installationsverfahren Address Indication Indication Indication Indication DEUTSCH...
Page 125: ...14 Procedimientos de instalaci n Address Indication Indication Indication Indication ESPA OL...
Page 151: ...14 Procedimentos de Instala o Address Indication Indication Indication Indication PORTUGU S...
Page 160: ...O fabricante reserva se o direito de alterar as especifica es do produto sem aviso pr vio...