Fan Static pressure adjustment
347mm
• Proper Piping
• Improper Piping
gas pipe
hanging bolt
Heat insultor
gradient of 1/1OO or over
air outlet port
avoid lobing
avoid curving
Do not put pipe
into water
1.5m ~ 2m
liquid pipe
120mm
90mm
96mm
drainpipe
4. Drainpipes
The blower can be set for the maximum static pressure and standard static pressure air volume through the controller,
which is set to the standard static pressure at the factory. Based on the duct design and filter selection the static
pressure will need to be adjusted, the static pressure selection is performed as follows:
Remote controller setting mode: remote control selects static pressure in high fan speed , press the health button12
times within 5 seconds, the buzzer will reverberate 4 times, set the maximum static pressure successfully. Press the
health button 12 times within 5 seconds. The buzzer will sound 2 times, the maximum static pressure function will be
cancelled, and the default setting will be restored.
YR-E17WiredController setting mode: keep pressing the key Set and the key minus 5 seconds to enter the
advanced setting, press the key Fan to switch to the function category b(temperature zone display),at this time
function category code flashes(clock zone display),press the key
or to switch the value to 11, then press the key
Set. The existing static pressure display is performed in the time zone and the specific information flashes. While it is
flashing, press the key
or
to change it. After the change is completed, press the key Set to confirm. O1 means
the default standard static pressure, O2 means the maximum static pressure.
Static Pressure Range
unit: Pa
Model
Standard Static Pressure
Max. Static Pressure
40VD005-028S-7S-QEE
20
200
40VD030-054S-7S-QEE
20
180
(a) Keep a gradient (1/5O-1/1OO)of the drain pipes and avoid lobing or curving.
Installation Procedures
8
English
Summary of Contents for XCT 7 40VD005-054S-7S -QEE
Page 8: ...Parts and Function 1 indoor unit air outlet port air inlet port air duct soft connection...
Page 31: ...The manufacturer reserves the right to change any product specifications without notice...
Page 58: ...Il produttore si riserva il diritto di modificare le specifiche del prodotto senza preavviso...
Page 62: ...Pi ces et fonctions Unit int rieure Sortie d air Entr e d air Gaine d air Raccord souple 1...
Page 85: ...Le fabricant se r serve le droit de modifier les sp cifications du produit sans pr avis...
Page 112: ...Der Hersteller beh lt sich das Recht vor Produktspezifikationen ohne Vorank ndigung zu ndern...