6
EOL termination
Only the EOL termination of the last
subnetwork bus device is set to
ON
.
Setting the Subnet ID
Each device on the subnet is identified with a
subnet address. The Room Temperature
Sensor / Room Control Interface connected
to a controller’s Subnet Port must be set to a
unique subnet ID address. The address is by
default set to 1. Do not modify the
Subnet ID.
The address is set through the DIP switch
located next to the Subnet Port connectors.
Switch position
Subnet ID
address
1
2
3
4 (EOL)
OFF OFF OFF ON or OFF 1
ON
OFF OFF ON or OFF 1
OFF
ON
OFF ON or OFF 2
ON ON
OFF ON or OFF 3
OFF OFF
ON
ON or OFF 4