4
Configuration
End of Line (EOL) termination
When there are a few devices, such as
sensors, light, blind modules, installed
together with a WTC, only the last device
EOL termination is set to ON. All other
devices must have their EOL terminations
set to OFF.
Figure 4: EOL termination ON
Figure 5: EOL termination OFF
Figure 6: Rotary switch – Subnet ID default position
EOL jumper
EOL termination
+
ON
-
OFF
The EOL termination is defined with the
EOL jumper.
Device addressing
The address is set by default to position “0”.
Do not modify the Subnet ID.
The Subnet ID address must remain “0”
as WTC-ISP/-ISPL is the only sensor
connectable to WTC.
English