25
Dirty Sensor Test
The dirty sensor test provides an indication of the sensor’s ability
to compensate for gradual environmental changes. A sensor that
can no longer compensate for environmental changes is consid-
ered 100% dirty and requires cleaning or replacing. You must use
a field provided SD-MAG test magnet to initiate a sensor dirty
test. The sensor’s Dirty LED indicates the results of the dirty test
as shown in Table 6.
Table 6 — Dirty LED Test
Dirty Sensor Test Procedure
1. Hold the test magnet where indicated on the side of the
sensor housing for two seconds.
2. Verify that the sensor’s Dirty LED flashes.
Changing the Dirt Sensor Test
By default, sensor dirty test results are indicated by:
• The sensor’s Dirty LED flashing.
• The controller’s Trouble LED flashing.
• The controller’s supervision relay contacts toggle.
The operation of a sensor’s dirty test can be changed so that the
controller’s supervision relay is not used to indicate test results.
When two detectors are connected to a controller, sensor dirty test
operation on both sensors must be configured to operate in the
same manner.
TO CONFIGURE THE DIRTY SENSOR TEST OPERATION
1. Hold the test magnet where indicated on the side of the
sensor housing until the sensor’s Alarm LED turns on and
its Dirty LED flashes twice (approximately 60 seconds).
2. Reset the sensor by removing the test magnet then holding
it against the sensor housing again until the sensor’s Alarm
LED turns off (approximately 2 seconds).
Remote Station Test
The remote station alarm test checks a test/reset station’s ability to
initiate and indicate an alarm state.
SD-TRK4 Remote Alarm Test Procedure
1. Turn the key switch to the RESET/TEST position for
seven seconds.
2. Verify that the test/reset station’s Alarm LED turns on.
3. Reset the sensor by turning the key switch to the RESET/
TEST position for two seconds.
4. Verify that the test/reset station’s Alarm LED turns off.
Remote Test/Reset Station Dirty Sensor Test
The test/reset station dirty sensor test checks the test/reset station’s
ability to initiate a sensor dirty test and indicate the results. It must
be wired to the controller as shown in Fig. 43 and configured to
operate the controller’s supervision relay. For more information,
see “Changing sensor dirty test operation.”
Fig. 43 — Remote Test/Reset Station Connections
IMPORTANT: OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an unnecessary
evacuation of the facility.
Holding the test magnet against the sensor housing for
more than seven seconds will put the duct detector into the
alarm state and activate all automatic alarm responses.
FLASHES DESCRIPTION
1
0-25% dirty. (Typical of a newly installed detector)
2
25-50% dirty
3
51-75% dirty
4
76-99% dirty
IMPORTANT: OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an unnecessary
evacuation of the facility.
Changing the dirty sensor test operation will put the detec-
tor into the alarm state and activate all automatic alarm
responses. Before changing dirty sensor test operation, dis-
connect all auxiliary equipment from the controller and
notify the proper authorities if connected to a fire alarm
system.
IMPORTANT: OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an unnecessary
evacuation of the facility.
This test places the duct detector into the alarm state.
Unless part of the test, disconnect all auxiliary equipment
from the controller before performing the test. If the duct
detector is connected to a fire alarm system, notify the
proper authorities before performing the test.
IMPORTANT: OPERATIONAL TEST ALERT
Failure to follow this ALERT can result in an unnecessary
evacuation of the facility.
Pressing the controller’s test/reset switch for longer than
seven seconds will put the duct detector into the alarm state
and activate all automatic alarm responses.
1
12
14
13
19
15
2
20
3
RESET/TEST
Trouble
POWER
ALARM
SUPERVISION RELAY
CONTACTS [3]
5
4
1
3
2
SD-TRK4
2
1
TB3
18 VDC (-)
18 VDC (-)
AUXILIARY
EQUIPMENT
+
−
WIRE MUST BE
ADDED BY
INSTALLER
SMOKE DETECTOR
CONTROLLER
Summary of Contents for WeatherMaster 48HC04 Series
Page 37: ...37 Fig 60 Integrated Gas Control IGC Board RED LED STATUS ...
Page 45: ...45 Fig 65 RTU Open Overlay for Economizer Wiring ...
Page 46: ...46 Fig 66 VFD Overlay for W2770 Controller Wiring ...
Page 98: ...98 Fig E 48HC A07 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 100: ...100 Fig G 48HC D11YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 101: ...101 Fig H 48HC D12 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 102: ...102 Fig I 48HC A04 A06 YAC Power Diagram 208 230 1 60 APPENDIX D WIRING DIAGRAMS ...
Page 103: ...103 Fig J 48HC A04 A06 YAC Power Diagram 208 230 3 60 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 104: ...104 Fig K 48HC A04 A06 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 107: ...107 Fig N 48HC A07 A12 YAC Power Diagram 208 230 3 60 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 108: ...108 Fig O 48HC A07 A12 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 109: ...109 Fig P 48HC D08 D09 YAC Power Diagram 230 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 110: ...110 Fig Q 48HC D08 D09 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 111: ...111 Fig R 48HC D11 YAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 112: ...112 Fig S 48HC D11 YAC Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 113: ...113 Fig T 48HC D11 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 114: ...114 Fig U 48HC D12 YAC Power Diagram 230 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 115: ...115 Fig V 48HC D12 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 116: ...116 Fig W 48HC D14 YAC Control Diagram 208 230 3 60 460 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 117: ...117 Fig X 48HC D14 YAC Power Diagram 208 230 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 118: ...118 Fig Y 48HC D14 YAC Power Diagram 460 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 119: ...119 Fig Z 48HC D14 YAC Power Diagram 575 3 60 APPENDIX D WIRING DIAGRAMS ...
Page 142: ...142 Fig AW PremierLink System Control Wiring Diagram System APPENDIX D WIRING DIAGRAMS ...
Page 144: ...144 Fig AY RTU Open Wiring Diagram APPENDIX D WIRING DIAGRAMS ...