15
Fig. 23 — Cooling Charging Chart — 50TCQ-D24 Circuit A
OVERCHARGING UNIT INCREASES THE RISK OF
NUISANCE HIGH PRESSURE SWITCH TRIPS
CAUTION DO NOT OVERCHARGE UNIT
20 TON HEAT PUMP CHARGING CHART - R410A REFRIGERANT
(COOLING MODE) - CIRCUIT A
20
40
60
80
100
120
140
150
200
250
300
350
400
450
500
550
600
650
Compressor Discharge Pressure, (psig)
Outdoor Coil Leaving Temperature, (Degrees F)
Add Charge if Above the Curve
Remove Charge if Below the Curve
IN HEATING MODE,
RECLAIM CHARGE AND RECHARGE UNIT PER NAMEPLATE
50HE501616 - A