GENERAL
Economizer minimum vent and changeover settings to job requirements (if equipped) (Y/N) _____
Verify smoke detector unit shutdown by utilizing magnet test (Y/N) _____
IV. HUMIDI-MIZER
®
SYSTEM START-UP
STEPS
1. Check UCB (Unit Control Board) for jumper 1, 2, 3 (Jumper 1, 2, 3 must be cut and open) (Y/N) _____
2. Open humidistat contacts (Y/N) _____
3. Start unit In cooling (Close Y1) (Y/N) _____
OBSERVE AND RECORD
A. Suction pressure
_______________ PSIG
B. Discharge pressure
_______________ PSIG
C. Entering air temperature
_______________ ° F
D. Liquid line temperature at outlet or reheat coil
_______________ ° F
E. Confirm correct rotation for compressor (Y/N) _____
F. Check for correct ramp-up of outdoor fan motor as condenser coil warms (Y/N) _____
4. Switch unit to high-latent mode (sub-cooler) by closing humidistat with Y1 closed (Y/N) _____
5. Check unit charge per charging chart (Y/N) _____
OBSERVE
A. Reduction in suction pressure (5 to 7 psi expected) (Y/N) _____
B. Discharge pressure unchanged (Y/N) _____
C. Liquid temperature drops to 50°F to 55°F range (Y/N) _____
D. LSV solenoid energized (valve closes) (Y/N) _____
6. Switch unit to dehumid (reheat) by opening Y1 (Y/N) _____
OBSERVE
A. Suction pressure increases to normal cooling level (Y/N) _____
B. Discharge pressure decreases (35 to 50 psi) (Limited by head pressure control) (Y/N) _____
C. Liquid temperature returns to normal cooling level (Y/N) _____
D. LSV solenoid energized (valve closes) (Y/N) _____
E. DSV solenoid energized, valve opens (Y/N) _____
7. With unit in dehumid mode close W1 compressor and outdoor fan stop; LSV and DSV solenoids de-energized
(Y/N) _____
8. Open W1 restore unit to dehumid mode (Y/N) _____
9. Open humidistat input compressor and outdoor fan stop; LSV and DSV solenoids de-energized (Y/N) _____
10. Restore setpoints for thermostat and humidistat (Y/N) _____
Summary of Contents for WeatherMaker 50FC-16 Series
Page 4: ...4 Fig 2 50FC 16 Unit Dimensional Drawing ...
Page 5: ...5 Fig 2 50FC 16 Unit Dimensional Drawing cont ...
Page 8: ...8 Fig 5 50FC 16 Roof Curb Details ...
Page 21: ...21 Fig 42 Typical Control Wiring Diagram Electro Mechanical with W7220 Controller ...
Page 22: ...22 Fig 43 Typical Control Wiring Diagram SystemVu Controller ...
Page 23: ...23 Fig 44 Typical Power Wiring Diagram 208 230 460 3 60 Unit Shown ...
Page 24: ...24 Fig 45 Typical Power Wiring Diagram 575 3 60 Unit Shown ...
Page 41: ......