Table 9 — Open System Wiring Specifications and Recommended Vendors
LEGEND
WIRING SPECIFICATIONS
RECOMMENDED VENDORS AND PART NUMBERS
WIRE
TYPE
DESCRIPTION
CONNECT AIR
INTERNATIONAL
BELDEN RMCORP
CONTRACTORS
WIRE AND
CABLE
MS/TP
NETWORK
(RS-485)
22 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide for
specifications.
W221P-22227
—
25160PV
CLP0520LC
24 AWG, single twisted shielded pair, low capacitance, CL2P,
TC foam FEP, plenum rated. See MS/TP Installation Guide
for specifications.
W241P-2000F
82841
25120-OR
—
RNET
4 conductor, unshielded, CMP, 18 AWG, plenum rated.
W184C-2099BLB
6302UE
21450
CLP0442
Fig. 43 — Side Return Duct Dimensions
a48-8245
3
1.25
”
IN
S
IDE
RA
97.7
8”
(020-050), 150.47
”
(051 AND 060)
IN
S
IDE DIMEN
S
ION
AWG
—
American Wire Gage
CL2P
—
Class 2 Plenum Cable
CMP
—
Communications Plenum Rated
FEP
—
Fluorinated Ethylene Polymer
TC
—