![Carrier WeatherMaker 50A020-060 Installation Instructions Manual Download Page 19](http://html.mh-extra.com/html/carrier/weathermaker-50a020-060/weathermaker-50a020-060_installation-instructions-manual_2560320019.webp)
19
Table 2 — 50A Base Unit Operating Weights (lb)
Table 3 — 50A Option and Accessory Weights (lb)
Table 4 — Constant Volume Fan
Motor Weights (lb)
Table 5 — Variable Air Volume / Staged Air Volume
Fan Motor Weights (lb)
LEGEND AND NOTES FOR TABLES 2-5
LEGEND NOTES:
1. Base unit weight includes outdoor-air hoods. Base unit weight
does NOT include indoor-fan motor. ADD indoor-fan motor,
FIOPs, and accessories for TOTAL operating weight.
2. VAV/SAV™ motor weights include the indoor motor and the VFD,
optional VFD bypass, VFD transducer and associated wiring.
UNIT SIZE
020
025
027
030
035
040
050
060
50A2,A3,A6,A7
3625
3761
3761
3792
4025
4455
4599
6826
50A4,A5,A8,A9
3703
3839
3839
3870
4218
4648
4792
7041
UNIT SIZE
020
025
027
030
035
040
050
060
Barometric Relief
300
300
300
300
300
300
300
450
Non-Modulating Power Exhaust
450
450
450
450
450
450
450
675
Modulating Power Exhaust
500
500
500
500
500
500
500
725
Electric Heat
110
110
110
110
110
110
110
165
Cu Tube/Alum Fin Cond. Coil
100
100
100
150
150
187
317
26
Cu Tube/Cu Fin Cond. Coil
263
263
263
370
370
512
751
677
OA Hood Crate/Packaging
(Less Hoods’ Weight)
45
45
45
45
45
45
45
45
(Packaging Only)
Outdoor Air Hoods/Filters (included with unit)
170
170
170
170
170
170
170
255
Hail Guards
73
73
73
73
73
146
146
219
Roof Curb (14-in.)
365
365
365
365
365
410
410
540
Double Wall
275
275
275
275
275
275
275
375
Humidi-MiZer Coil
150
150
150
150
150
180
180
195
MOTOR HP
UNIT VOLTAGE
PREMIUM
EFFICIENCY
IFM
5 HP
230/460
80
380
75
575
80
10 HP
230/460
126
380
120
575
126
15 HP
230/460
217
380
155
575
217
20 HP
230/460
250
380
185
575
250
25 HP
230/460
309
380
225
575
309
30 HP
230/460
303
380
283
575
303
40 HP
230/460
551
380
601
575
551
MOTOR HP
UNIT VOLTAGE
PREMIUM
EFFICIENCY
IFM
5 HP
230/460
138
380
133
575
149
10 HP
230/460
195
380
198
575
195
15 HP
230/460
316
380
254
575
319
20 HP
230/460
385
380
320
575
357
25 HP
230/460
444
380
360
575
454
30 HP
230/460
338
380
318
575
342
40 HP
230/460
686
380
736
575
686
Cu
—
Copper
FIOP —
Factory-Installed Option
HP
—
Horsepower
IFM
—
Indoor Fan Motor
OA
—
Outdoor Air
SAV
—
Staged Air Volume
VAV
—
Variable Air Volume
VFD
—
Variable Frequency Drive