66
Staged Air Volume (SAV™) with Variable Fre
-
quency Drive
The Staged Air Volume (SAV) system utilizes a Variable Frequen
-
cy Drive (VFD) to automatically adjust the indoor fan motor
speed in sequence with the unit’s ventilation, cooling and heating
operation. Per ASHRAE 90.1-2016 standard, during the first stage
of cooling operation the SAV system will adjust the fan motor to
provide 66% of the design airflow rate for the unit. When the call
for the second stage of cooling is required, the SAV system will al
-
low the design airflow rate for the unit established (100%). During
the heating mode, the SAV system will allow total design airflow
rate (100%) operation. During ventilation mode, the SAV system
will operate the fan motor at 66% speed. Figure 78 shows the Vari
-
able Frequency Drive. See Fig. 79 for the VFD location.
Fig. 78 —
Variable Frequency Drive (VFD)
Fig. 79 —
VFD Location
MULTI-SPEED VFD DISPLAY KIT (FIELD-INSTALLED
ACCESSORY)
NOTE: The Remote VFD Keypad is part of the Multi-Speed VFD
display kit (P/N: CRDISKIT002A00), which is a field-installed
accessory. It is not included with the 50LC size 14-26 base units.
The VFD keypad as shown in Fig. 80 consists of the following
sections:
Alphanumeric Display
The LCD display is backlit with 2 alphanumeric lines. All data is
displayed on the LCD (see Fig. 81).
Menu Key
Use the Menu key to select between Status, Quick Menu or Main
Menu. The triangle icon at the bottom of the LCD display indi
-
cates the currently selected mode (see number 5 in Fig. 81).
Navigation Keys and Status LEDs
The Navigation keys and Status LEDs are detailed in Fig. 82.
Operation Keys and LEDs
Figure 83 details the functions of the Operating keys. An illumi
-
nated yellow LED above the key indicates the active key.
230V/460V
575V ONLY
Summary of Contents for WeatherExpert 50LC14
Page 4: ...4 Fig 2 50LC Vertical Airflow Size 14...
Page 5: ...5 Fig 3 50LC Horizontal Airflow Size 14...
Page 6: ...6 Fig 4 50LC Back View and Condensate Drain Location Size 14...
Page 7: ...7 Fig 5 50LC Corner Weights and Clearances Size 14...
Page 8: ...8 Fig 6 50LC Bottom View Size 14...
Page 9: ...9 Fig 7 50LC Vertical Airflow Sizes 17 20...
Page 10: ...10 Fig 8 50LC Horizontal Airflow Sizes 17 20...
Page 11: ...11 Fig 9 50LC Back View and Condensate Drain Location Sizes 17 20...
Page 12: ...12 Fig 10 50LC Corner Weights and Clearances Sizes 17 20...
Page 13: ...13 Fig 11 50LC Bottom View Sizes 17 20...
Page 14: ...14 Fig 12 50LC Vertical Airflow Sizes 24 26...
Page 15: ...15 Fig 13 50LC Horizontal Airflow Sizes 24 26...
Page 16: ...16 Fig 14 50LC Back View and Condensate Drain Location Sizes 24 26...
Page 17: ...17 Fig 15 50LC Corner Weights and Clearances Sizes 24 26...
Page 18: ...18 Fig 16 50LC Bottom View Sizes 24 26...
Page 21: ...21 Fig 19 Roof Curb Details 14 Size Unit...
Page 22: ...22 Fig 20 Roof Curb Details 17 and 20 Size Units...
Page 23: ...23 Fig 21 Roof Curb Details 24 and 26 Size Units...
Page 30: ...30 Fig 42 50LC 14 26 Electro Mechanical Control Wiring Diagram...
Page 31: ...31 Fig 43 50LC 14 26 RTU Open Control Wiring Diagram...
Page 32: ...32 Fig 44 50LC 14 26 SystemVu Control Wiring Diagram...
Page 35: ...35 Fig 47 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 208 230V Shown...
Page 36: ...36 Fig 48 Typical Power Wiring Diagram SystemVu Controls 50LC Unit 460V 575V Shown...
Page 80: ......
Page 81: ......