156
Table 99 —
Compressor Expansion Board (CXB) Inputs and Outputs
Table 100 —
Expansion Valve Control Board A (EXV-A) Inputs and Outputs
Table 101 —
Expansion Valve Control Board B (EXV-B) Inputs and Outputs
Table 102 —
Expansion Valve Control Board C (EXV-C) Inputs and Outputs
POINT NAME
POINT DESCRIPTION
TYPE OF I/O
I/O POINT NAME CONTROL BOARD CONNECTOR PIN NO.
INPUTS
CSB_A3
Compressor A3 Feedback
Digital Input
DIG1
CXB
J5, 10-12
CSB_B3
Compressor B3 Feedback
Digital Input
DIG2
CXB
J5, 7-9
CSB_A4
Compressor A4 Feedback
Digital Input
DIG3
CXB
J5, 4-6
CSB_B4
Compressor B4 Feedback
Digital Input
DIG4
CXB
J5, 1-3
OUTPUTS
HS9
Heat Relay 9
Relay
RLY1
CXB
J6, 1-2
HS10
Heat Relay 10
Relay
RLY2
CXB
J6, 3-4
CMPB4
Compressor B4 Relay
Relay
RLY3
CXB
J6, 5-6
CMPB3
Compressor B3 Relay
Relay
RLY4
CXB
J6, 7-8
CMPA4
Compressor A4 Relay
Relay
RLY5
CXB
J6, 9-11
CMPA3
Compressor A3 Relay
Relay
RLY6
CXB
J6, 12-14
POINT NAME
POINT DESCRIPTION
TYPE OF I/O
I/O POINT NAME CONTROL BOARD CONNECTOR PIN NO.
INPUTS
CASTEXV1
Cir A EXV1 Suction Temperature
Thermistor
AN1
EXV-A
J5, 5-6
CASTEXV2
Cir A EXV2 Suction Temperature
Thermistor
AN2
EXV-A
J5, 7-8
LT_A
Circuit A Liquid Temperature
Thermistor
AN3
EXV-A
J5, 9-10
SFBYIN
Supply Fan Bypass Input
Thermistor
AN4
EXV-A
J5, 11-12
Not Used
Not Used
Transducer (4-20mA)
AN5
EXV-A
J5, 1-2
Not Used
Not Used
Transducer (4-20mA)
AN6
EXV-A
J5, 3-4
OUTPUTS
CA_EXV1
Circuit A EXV 1
Stepper Motor
EXV-1
EXVA
J6, 1-5
CA_EXV2
Circuit B EXV 1
Stepper Motor
EXV-2
EXVA
J7, 1-5
POINT NAME
POINT DESCRIPTION
TYPE OF I/O
I/O POINT NAME CONTROL BOARD CONNECTOR PIN NO.
INPUTS
CBSTEXV1
Cir B EXV1 Suction Temperature
Thermistor
AN1
EXV-B
J5, 5-6
CBSTEXV2
Cir B EXV2 Suction Temperature
Thermistor
AN2
EXV-B
J5, 7-8
LT_B
Circuit B Liquid Temperature
Thermistor
AN3
EXV-B
J5, 9-10
PEBYIN
PE/Ret Fan Bypass Input
Thermistor
AN4
EXV-B
J5, 11-12
Not Used
Not Used
Transducer (4-20mA)
AN5
EXV-B
J5, 1-2
Not Used
Not Used
Transducer (4-20mA)
AN6
EXV-B
J5, 3-4
OUTPUTS
CB_EXV1
Circuit A EXV 2
Stepper Motor
EXV-1
EXVB
J6, 1-5
CB_EXV2
Circuit B EXV 2
Stepper Motor
EXV-2
EXVB
J7, 1-5
POINT NAME
POINT DESCRIPTION
TYPE OF I/O
I/O POINT NAME CONTROL BOARD CONNECTOR PIN NO.
INPUTS
Not Used
Not Used
Thermistor
AN1
EXV-C
J5, 5-6
Not Used
Not Used
Thermistor
AN2
EXV-C
J5, 7-8
Not Used
Not Used
Thermistor
AN3
EXV-C
J5, 9-10
Not Used
Not Used
Thermistor
AN4
EXV-C
J5, 11-12
Not Used
Not Used
Transducer (4-20mA)
AN5
EXV-C
J5, 1-2
Not Used
Not Used
Transducer (4-20mA)
AN6
EXV-C
J5, 3-4
OUTPUTS
COND_EXV
Condenser EXV Position
Stepper Motor
EXV-1
EXV
J6, 1-5
BYP_EXV
Bypass EXV Position
Stepper Motor
EXV-2
EXV
J7, 1-5
Summary of Contents for WeatherExpert 48N2
Page 135: ...135 Fig 18 48 50N Typical Power Schematic Nominal 075 Ton Unit Shown ...
Page 136: ...136 Fig 19 48 50N Typical Power Schematic Nominal Ton 90 150 Units Shown ...
Page 137: ...137 Fig 20 48 50N Main Base Board Input Output Connections ...
Page 138: ...138 Fig 21 48 50N RXB EXB CEM Input Output Connections a48 9307 ...
Page 139: ...139 Fig 22 48 50N EXV SCB Input Output Connections a48 9308 ...
Page 140: ...140 Fig 23 48N Typical Modulating Gas Heat Unit Control Wiring ...
Page 141: ...141 Fig 24 50N Typical Electric Heat Unit Control Wiring ...
Page 144: ...144 Fig 27 48N Typical Gas Heat Section Wiring Nominal Ton 120 to 150 Units ...
Page 145: ...145 Fig 28 48 50N Typical Power Component Control Wiring 460 v ...
Page 146: ...146 Fig 29 48 50N Component Control Wiring 575 v Nominal Ton 075 to 150 Units ...
Page 147: ...147 Fig 30 48 50N Component Arrangement Power Box ...
Page 148: ...148 Fig 31 48 50N Component Arrangement Control Box ...
Page 240: ...240 APPENDIX D VFD INFORMATION CONT Fig G VFD Bypass Wiring Diagram WHEN USED ...