Table 11 — VFD Unit Parameters – 48LC*B Size 17 (cont)
RAMP UP
TIME (sec)
RAMP DOWN
TIME (sec)
CURRENT
LIMIT
TERMINAL 18
DIGITAL INPUT
TERMINAL 19
DIGITAL INPUT
TERMINAL 27
DIGITAL INPUT
TERMINAL 29
DIGITAL INPUT
Motor
Option
Voltage
3–41
3–42
4–18
5–10
5–11
5–12
5–13
STD
208/230
10.00
10.00
100%
[8]
[16]
[17]
[18]
460
10.00
10.00
100%
[8]
[16]
[17]
[18]
575
10.00
10.00
100%
[8]
[16]
[17]
[18]
MID
208/230
10.00
10.00
100%
[8]
[16]
[17]
[18]
460
10.00
10.00
100%
[8]
[16]
[17]
[18]
575
10.00
10.00
100%
[8]
[16]
[17]
[18]
HIGH
208/230
10.00
10.00
100%
[8]
[16]
[17]
[18]
460
10.00
10.00
100%
[8]
[16]
[17]
[18]
575
10.00
10.00
100%
[8]
[16]
[17]
[18]
ULTRA
208/230
10.00
10.00
100%
[8]
[16]
[17]
[18]
460
10.00
10.00
100%
[8]
[16]
[17]
[18]
575
10.00
10.00
100%
[8]
[16]
[17]
[18]
TERMINAL 53
LOW VOLTAGE
TERMINAL 53
HIGH VOLTAGE
TERMINAL 53
LOW REFERENCE
TERMINAL 53
HIGH REFERENCE
RESET
MODE
AUTO. RESTART
TIME (s)
RFI
FILTER
Motor
Option Voltage
6–10
6–11
6–14
6–15
14–20
14–21
14–50
STD
208/230
2
[10]
0
[60]
[3]
600
[0]
460
2
[10]
0
[60]
[3]
600
[0]
575
2
[10]
0
[60]
[3]
600
[0]
MID
208/230
2
[10]
0
[60]
[3]
600
[0]
460
2
[10]
0
[60]
[3]
600
[0]
575
2
[10]
0
[60]
[3]
600
[0]
HIGH
208/230
2
[10]
0
[60]
[3]
600
[0]
460
2
[10]
0
[60]
[3]
600
[0]
575
2
[10]
0
[60]
[3]
600
[0]
ULTRA
208/230
2
[10]
0
[60]
[3]
600
[0]
460
2
[10]
0
[60]
[3]
600
[0]
575
2
[10]
0
[60]
[3]
600
[0]
Table 12 — VFD Unit Parameters – 48LC*B Size 20
REGIONAL
SETTINGS
GRID
TYPE
MOTOR
POWER
MOTOR
VOLTAGE
MOTOR
FREQUENCY
(Hz)
MOTOR
CURRENT
(MUST-HOLD
AMPS)
MOTOR
NOMINAL
SPEED (RPM)
Motor
Option Voltage
Motor
P/N
VFD
Carrier P/N
VFD
Mfr P/N
0–03
0–06
1–20
1–22
1–23
1–24
1–25
STD
208/230 HD60FE656 HK30WA372 131L9797
[1]
[102]
[11]
230
60
11.7
1750
460
HD60FE656 HK30WA378 131L9865
[1]
[122]
[11]
460
60
5.4
1750
575
HD58FE577 HK30WA383 131N0227
[1]
[132]
[11]
575
60
4.9
1710
MID
208/230 HD60FK657 HK30WA373 131L9798
[1]
[102]
[14]
230
60
21.2
1760
460
HD60FK657 HK30WA380 131L9867
[1]
[122]
[14]
460
60
9.7
1760
575
HD60FL576 HK30WA384 131N0229
[1]
[132]
[14]
575
60
7.2
1745
HIGH
208/230 HD62FK654 HK30WA374 131L9799
[1]
[102]
[15]
230
60
28.0
1760
460
HD62FK654 HK30WA381 131L9868
[1]
[122]
[15]
460
60
13.7
1760
575
HD62FL576 HK30WA384 131N0229
[1]
[132]
[15]
575
60
8.9
1750
ULTRA
208/230 HD64FK654 HK30WA375 131L9800
[1]
[102]
[16]
230
60
37.3
1755
460
HD64FK654 HK30WA386 131L9869
[1]
[122]
[16]
460
60
16.9
1755
575
HD64FL576 HK30WA388 131N0233
[1]
[132]
[16]
575
60
12.6
1755
Summary of Contents for WeatherExpert 48LC B14 Series
Page 4: ...4 Fig 2 48LC B14 Vertical Airflow ...
Page 5: ...5 Fig 3 48LC B14 Horizontal Airflow ...
Page 6: ...6 Fig 4 48LC B14 Back View and Condensate Drain Location ...
Page 7: ...7 Fig 5 48LC B14 Corner Weights and Clearances ...
Page 8: ...8 Fig 6 48LC B14 Bottom View ...
Page 9: ...9 Fig 7 48LC B17 20 Vertical Airflow ...
Page 10: ...10 Fig 8 48LC B17 20 Horizontal Airflow ...
Page 11: ...11 Fig 9 48LC B17 20 Back View and Condensate Drain Location ...
Page 12: ...12 Fig 10 48LC B17 20 Corner Weights and Clearances ...
Page 13: ...13 Fig 11 48LC B17 20 Bottom View ...
Page 14: ...14 Fig 12 48LC B24 26 Vertical Airflow ...
Page 15: ...15 Fig 13 48LC B24 26 Horizontal Airflow ...
Page 16: ...16 Fig 14 48LC B24 26 Back View and Condensate Drain Location ...
Page 17: ...17 Fig 15 48LC B24 26 Corner Weights and Clearances ...
Page 18: ...18 Fig 16 48LC B24 26 Bottom View ...
Page 21: ...21 Fig 20 48LC B14 Roof Curb Details ...
Page 22: ...22 Fig 21 48LC B17 20 Roof Curb Details ...
Page 23: ...23 Fig 22 48LC B24 26 Roof Curb Details ...
Page 30: ...30 Fig 40 48LC B14 26 VAV RTU Open Control Wiring Diagram ...
Page 31: ...31 Fig 41 48LC B14 26 Power Wiring Diagram ...
Page 53: ......