20
Locate the four 1
1
/
4
-in. drain coupling assemblies and
mounting screws (shipped in a bag taped to the basepan in the
supply fan section, located behind the access panel marked
FAN SECTION). The drain couplings are a 10-gage plate with
a 1
1
/
4
in. half coupling welded to the plate.
After final positioning of the unit, perform the following
procedure:
1. At each of the four secondary drain locations (marked
with labels on the unit base rail), position the drain cou-
pling assembly in the side of the base rail. Mark the
screw holes and the drain hole locations on the base rail.
2. Drill holes for drain outlet (use 1
3
/
8
-in. hole saw) and for
the mounting screws (use
3
/
16
-in. drill bit).
3. Install a drain coupling assembly using screws provided
at each secondary drain hole location.
4. Using field-supplied fittings and pipe sections, assemble
U-traps at each secondary drain fitting. See Fig. 24. Pro-
vide minimum size of ½-in. pipe for secondary drains.
Use a trap at least 4-in. deep for size 030-070 units and
7-in. deep for size 075-100 units.
5. Apply a bead of RTV or similar sealant around the drain
assemblies.
Consult local plumbing codes for direction on joining multi-
ple drain lines. Total size of any combined line does not need to
exceed nominal 2-in. size of primary drain connection.
Fill the U-traps at the secondary drain locations prior to unit
start-up. Also check the U-traps before each cooling season to
ensure the traps are filled and functioning properly.
3
2
A
B
4
1
NOTE: The weight distribution and center of gravity information include the impact of an economizer, the largest indoor fan motor, and a VFD (variable frequency
drive). On units with a return fan or high-capacity power exhaust, the largest motors and VFD are also included. These weights do not include the impact of other
factory-installed options such as barometric relief, power exhaust, high-capacity indoor coil, hot water coil, or indoor fan.
48P2,P3,P4,P5 UNITS
WITH OPTIONAL RETURN FAN
SIZE
CORNER WEIGHTS (lb)
TOTAL
(lb)
A
B
1
2
3
4
in.
in.
Vertical Supply/Return
Horizontal Supply/Return
Low Heat
075
3470
3449
2693
2709
12,321
224
5
/
8
40
1
/
4
090
3327
3745
3097
2751
12,921
232
5
/
8
41
1
/
2
100
3302
3782
3127
2730
12,941
230
3
/
8
41
1
/
2
Vertical Supply/Return
Horizontal Supply/Return
High Heat
075
3543
3449
2693
2766
12,451
226
7
/
8
40
1
/
4
090
3377
3767
3115
2793
13,051
233
3
/
4
41
1
/
2
100
3370
3785
3130
2787
13,071
232
7
/
8
41
1
/
2
Vertical Supply/Return
Horizontal Supply/Return
Low Heat with Extended Chassis
075
3609
3618
2825
2818
12,871
236
1
/
4
40
1
/
4
090
3467
3906
3230
2867
13,471
244
1
/
4
41
1
/
2
100
3437
3948
3264
2842
13,491
241
3
/
4
41
1
/
2
Vertical Supply/Return
Horizontal Supply/Return
High Heat with Extended Chassis
075
3681
3620
2826
2874
13,001
238
1
/
2
40
1
/
4
090
3517
3928
3248
2908
13,601
245
3
/
8
41
1
/
2
100
3505
3951
3267
2898
13,621
244
1
/
4
41
1
/
2
Fig. 11 — Weight Distribution and Center of Gravity (cont)
Summary of Contents for WEATHER MASTER 48P2
Page 10: ...10 Fig 1 Roof Curb Sizes 030 050...
Page 11: ...11 Fig 2 Roof Curb Sizes 055 060...
Page 12: ...12 Fig 3 Roof Curb Sizes 070 100...
Page 13: ...13 Fig 4 Condenser Section Roof Curb Sizes 070 and 075...
Page 14: ...14 Fig 5 Condenser Section Roof Curb Sizes 090 and 100...
Page 21: ...21 Fig 12 Base Unit Dimensional Drawing 48P2 P3030 035 Standard Chassis Unit Shown a48 8613...
Page 22: ...22 Fig 13 Base Unit Dimensional Drawing 48P4 P5030 035 Standard Chassis Unit Shown a48 8614...
Page 23: ...23 Fig 14 Base Unit Dimensional Drawing 48P2 P3040 050 Standard Chassis Unit Shown a48 8615...
Page 24: ...24 Fig 15 Base Unit Dimensional Drawing 48P4 P5040 050 Standard Chassis Unit Shown a48 8616...
Page 25: ...25 Fig 16 Base Unit Dimensional Drawing 48P2 P3055 060 Standard Chassis Unit Shown a48 8617...