background image

2

INSTALLATION

Step 1 — Perform  Jobsite Survey  — 

 Complete

the following checks before installation.

1. Consult local building codes and the NEC (National

Electrical Code) (ANSI/NFPA [American National Stan-

dards Institute/National Fire Protection Association] 70)

for special installation requirements.

2. Determine unit location (from project plans) or select unit

location.

3. Check for possible overhead obstructions which may in-

terfere with unit lifting or rigging.

Step 2 — Place Unit — 

Inspect unit for transportation

damage. File claim with transportation agency.

Provide clearance around and above unit for airflow, safety,

and service access. Do not restrict top (area above condenser

fans) in any way. Allow at least 6 ft on all sides for rated perfor-

mance, code compliance, and service. On units equipped with

power exhaust option, high velocity air is exhausted out the

hood. Unit should be positioned with at least 10 ft clearance be-

tween the exhaust hood and any obstruction.

Check unit dimensional drawings for unit arrangement and

minimum performance and service clearances.

Do not install unit in an indoor location. Do not locate air in-

lets near exhaust vents or other sources of contaminated air.

Although unit is weatherproof, guard against water from

higher level runoff and overhangs.

Level by using unit frame as a reference. Physical data is

shown in Tables 1A-9.

Step 3 — Roof Mount Unit — 

Check building codes

for weight distribution requirements. Unit weight is shown in

Tables 1A-1C and 5. Unit may be mounted on class A, B, or C

roofing material.
ROOF CURB — Assemble and install roof curb as described

in instructions shipped with the accessory. Accessory roof curb

and information required to field fabricate a roof curb is shown

in Fig. 1-5. Install insulation, cant strips, roofing and counter

flashing as required. For unit condensate drain to function

properly, curb must be level or within tolerances shown in

Fig. 1-5.
STEEL BEAMS — If roof curb is not used, support unit with

steel beams along its entire length and then support steel as re-

quired. As a minimum, unit must be supported across its width

at each lifting lug location.

Step 4 — Slab Mount Unit — 

Provide a level con-

crete slab that extends beyond unit cabinet at least 6 inches.

Make a slab 8 in. thick with 4 in. above grade. Use gravel

apron in front of condenser coil air inlet to prevent grass and

foliage from obstructing airflow. Ensure that slab is of

sufficient height to allow for condensate trap of 4 in. on sizes

030-070 or 7 in. on sizes 075-100.

Step 5 — Install Curb Gasketing

SIZE 030-060 UNITS — After ductwork has been connected

to the roof curb, attach adhesive-backed gasketing on all end

rails, cross rails, and duct rails. Be sure all joints and corners of

gasket are square and flush to prevent possible water leaks.

Follow all applicable building codes.
SIZE 070-100 UNITS — After ductwork has been connected

to the roof curb, apply gasket material (

1

/

2

-in. thick x 1

1

/

2

-in.

wide neoprene) where indicated.
Single-Thickness Gasketing (See Fig. 6-8 for Item Num-

bers) — Apply gasketing in the following places:

1. Along both side rails (1) — 2 places, full length
2. Along return air end rail (2) — 1 place
3. Around return air internal duct flange (3) — 1 or 2 places
4. Around supply air internal duct flanges (4) — 3 places

Double-Thickness Gasketing (See Fig. 6 and 8 and Detail

A-A) — Locate a line 9

3

/

4

-in. from the supply air end of the

accessory curb. Apply a double-thickness of gasket material

along line per detail A-A.
NOTE: Do not apply gasket material along the outside edge of

the curb (area “X”). This pan area of the curb extends out

beneath the end of the unit’s air handler section; applying gas-

ket here develops a potential water trap area on top of the curb.
Condenser Section Roof Curb (See Fig. 7) — Apply single-

thickness gasket along both side rails (5).

Step 6 — Install Field-Fabricated Ductwork

The 48P2,P3 units are designed for vertical supply/return

only. Field-fabricated ductwork must be attached to the roof

curb, or to the support steel, prior to the final rigging and instal-

lation of the unit. Supply and return duct dimensions are shown

in Fig. 1-3.

To attach ductwork to roof curb, insert duct approximately 10

to 11 in. up into roof curb. Connect ductwork to 14-gage roof

curb material with sheet metal screws driven from inside the duct.

Secure all ducts to the building structure, using flexible duct

connectors between roof curbs and ducts as required. Ducts

passing through an unconditioned space must be insulated and

covered with a vapor barrier. Outlet grilles must not lie directly

below unit discharge.

Design supply duct strong enough to handle expected static

pressures.

Step 7 — Rig Unit — 

Do not drop unit; keep upright.

Use spreader bars over unit to prevent sling or cable damage.

Sheets of plywood placed along the condenser coils will pro-

vide additional protection. All lifting lugs MUST be used when

lifting unit. Level by using unit frame as a reference. See Fig. 9

and 10 for information. Unit and accessory weights are shown

in Tables 1A-1C and 5. Weight distribution and center of gravi-

ty can be found in Fig. 11.

CAUTION

Disconnect gas piping from units when leak testing at pres-

sures greater than 0.5 psig. Pressures greater than 0.5 psig

will cause gas valve damage resulting in a hazardous

condition. If gas valve is subjected to pressure greater than

0.5 psig, it must be replaced. When pressure testing field-

supplied gas piping at pressures of 0.5 psig or less, the unit

connected to such piping must be isolated by manually

closing the gas valve.

CAUTION

Do not lift unit with forklift truck. Move unit with over-

head rigging only.

WARNING

For vertical supply and return units, tools or parts could

drop into ductwork and cause an injury. Install a 90-degree

elbow in the supply and return ductwork between the unit

and the conditioned space. If a 90-degree elbow cannot be

installed, then a grille of sufficient strength and density

should be installed to prevent objects from falling into the

conditioned space. Failure to follow these instructions

could result in personal injury or property damage due to

falling objects.

Summary of Contents for WEATHER MASTER 48P2

Page 1: ...al economizer and high capacity power exhaust is available on size 075 100 units A factory installed optional return fan is available on size 075 100 units The staged gas control SGC option adds the c...

Page 2: ...rene where indicated Single Thickness Gasketing See Fig 6 8 for Item Num bers Apply gasketing in the following places 1 Along both side rails 1 2 places full length 2 Along return air end rail 2 1 pla...

Page 3: ...00 15 000 Maximum Allowable Rpm 900 900 Shaft Diameter at Pulley in 111 16 111 16 SUPPLY FAN MOTOR AND DRIVE Any motor available on any unit Motor Hp 7 5 10 15 20 25 Motor Frame Size 213T 215T 254T 25...

Page 4: ...00 Maximum Allowable Rpm 900 900 Shaft Diameter at Pulley in 111 16 111 16 SUPPLY FAN MOTOR AND DRIVE Any motor available on any unit Motor Hp 7 5 10 15 20 25 30 Motor Frame Size 213T 215T 254T 256T 2...

Page 5: ...umber of Gas Valves 2 3 2 3 2 3 CONDENSER FANS Propeller Type Quantity Diameter in 4 30 4 30 4 30 Nominal Cfm 36 000 36 600 39 000 Motor Hp Rpm 1 0 1140 1 0 1140 1 0 1140 SUPPLY FAN Centrifugal 30 x 2...

Page 6: ...80 Temperature Rise Range F 10 40 20 50 10 40 20 50 10 40 20 50 Efficiency Vertical Horizontal 81 80 81 80 81 80 81 80 81 80 81 80 Burner Orifice Diameter Quantity in drill no 7 1285 30 7 1285 30 7 12...

Page 7: ...20 x 16 x 1 4 25 x 16 x 1 2 20 x 16 x 1 OPTIONAL ECONOMIZER FILTER Aluminum Frame Permanent Quantity Size in 12 16 x 25 x 1 2 16 x 20 x 1 12 16 x 25 x 1 2 16 x 20 x 1 12 16 x 25 x 1 2 16 x 20 x 1 MBtu...

Page 8: ...ity Evaporator Coil 150 300 300 300 300 300 300 300 Airfoil Fan 350 350 350 Humidi MiZer Adaptive Dehumidification System 72 72 72 72 72 72 92 92 HP SHAFT DIA in SPEED rpm MOTOR SHEAVE MOTOR PITCH DIA...

Page 9: ...s 055 100 10 2 5 11 8 740 2P3V45 4 5 2Q3V106 10 6 2 3VX71 22 71 26 38 2 3VX50 10 91 13 30 15 2 7 5 13 8 820 2P3V50 5 0 2Q3V106 10 6 2 3VX71 22 71 26 38 2 3VX50 10 78 13 20 20 2 10 13 8 920 2P3V56 5 6...

Page 10: ...10 Fig 1 Roof Curb Sizes 030 050...

Page 11: ...11 Fig 2 Roof Curb Sizes 055 060...

Page 12: ...12 Fig 3 Roof Curb Sizes 070 100...

Page 13: ...13 Fig 4 Condenser Section Roof Curb Sizes 070 and 075...

Page 14: ...14 Fig 5 Condenser Section Roof Curb Sizes 090 and 100...

Page 15: ...15 9 3 4 X NO GASKET 4 REF DETAIL A A A A X 4 1 3 2 CONDENSER END SUPPORT 5 5 Fig 6 Gasket Location on Roof Curb Size 070 100 Units Fig 7 Gasket Location Condenser Section Roof Curb Size 070 100 Units...

Page 16: ...he base rail surrounded by four 0 20 in engagement holes Install a drain coupling assem bly using screws provided at each secondary drain hole loca tion See Fig 26 Do not attach any drain coupling ass...

Page 17: ...070 10295 4670 258 4 6564 40 2 1021 250 2 6355 075 11345 5146 268 0 6808 40 2 1021 280 8 7132 090 11945 5418 275 8 7005 41 5 1054 280 8 7132 100 11965 5427 274 7 6978 41 5 1054 280 8 7132 50P 2 3 A B...

Page 18: ...8 7132 Vert Sup Ret Horz Sup Vert Ret 090 13601 6169 245 4 6234 41 5 1054 280 8 7132 w RE Fan w Ext Chassis 100 13621 6178 244 2 6203 41 5 1054 280 8 7132 48P 2 3 4 5 B D H 48 P2 P3 P4 P5 Low Gas Hea...

Page 19: ...4 1112 2220 6 669 187 3 4 45 7 8 040 2148 1460 1458 2145 7 210 214 3 4 45 7 8 050 2244 1471 1469 2241 7 425 217 7 8 45 7 8 055 2558 2331 2328 2554 9 770 242 5 8 45 7 8 060 2567 2349 2346 2563 9 825 24...

Page 20: ...rt up Also check the U traps before each cooling season to ensure the traps are filled and functioning properly 3 2 A B 4 1 NOTE The weight distribution and center of gravity information include the i...

Page 21: ...21 Fig 12 Base Unit Dimensional Drawing 48P2 P3030 035 Standard Chassis Unit Shown a48 8613...

Page 22: ...22 Fig 13 Base Unit Dimensional Drawing 48P4 P5030 035 Standard Chassis Unit Shown a48 8614...

Page 23: ...23 Fig 14 Base Unit Dimensional Drawing 48P2 P3040 050 Standard Chassis Unit Shown a48 8615...

Page 24: ...24 Fig 15 Base Unit Dimensional Drawing 48P4 P5040 050 Standard Chassis Unit Shown a48 8616...

Page 25: ...25 Fig 16 Base Unit Dimensional Drawing 48P2 P3055 060 Standard Chassis Unit Shown a48 8617...

Page 26: ...26 Fig 17 Base Unit Dimensional Drawing 48P4 P5055 060 Standard Chassis Unit Shown a48 8618...

Page 27: ...27 Fig 18 Base Unit Dimensional Drawing 48P2 P3070 Standard Chassis Unit Shown a48 8619...

Page 28: ...28 Fig 19 Base Unit Dimensional Drawing 48P4 P5070 Standard Chassis Unit Shown a48 8620...

Page 29: ...29 Fig 20 Base Unit Dimensional Drawing 48P2 P3075 100 Standard Chassis Unit with Optional High Capacity Power Exhaust Shown a48 8621...

Page 30: ...30 Fig 21 Base Unit Dimensional Drawing 48P4 P5075 100 Standard Chassis Unit with Optional Return Fan Shown a48 8622...

Page 31: ...00 with High Capacity Power Exhaust 279 2 6 6 a48457 A 2 MIN 51 mm Fig 23 Primary Drain Connection A 4 in 102 mm min Sizes 030 070 7 in 178 mm min Sizes 075 100 Fig 24 Slab Mounted Condensate Drain Pi...

Page 32: ...t points to prevent water leaks See Fig 29 UNIT SIZES 055 100 25 Outdoor Air Hoods Fig 32 The outdoor air hoods are factory installed on the 055 100 units Economizer Hoods Units with Economizer Option...

Page 33: ...4 top filter flange Item 5 4 side filter flanges Item 6 bottom support Item 7 front support Item 8 6 filters Item 9 9 filter clips Item 10 seal strip and fasteners 3 Place seal strip on backside of bo...

Page 34: ...ON LEGEND PE VFD Power Exhaust Variable Frequency Drive Fig 36 Economizer Hood Location Units with High Capacity Power Exhaust APPLYRTV INTHE INDICATED AREAS AND BOTH ENDS OF BOTTOM FILTER ROW SEE DET...

Page 35: ...und Maximum wire size is two 2 500 MCM maximum wire size conductors per pole Units with Factory Installed Disconnect The factory installed disconnect is an interlocking door type The discon nect handl...

Page 36: ...UTION Use care when drilling into corner post to avoid damage to con denser coil Fig 40 Disconnect Location Size 070 100 Units CAUTION Use care when drilling into corner post to avoid damage to con de...

Page 37: ...13 DISCONNECT PER NEC EQUIP GND TB1 Fig 43 Field Power Wiring Connections for Factory Installed Disconnect Fig 42 Factory Installed Disconnect Location End of Unit Shown LEGEND Fig 41 Field Power Wiri...

Page 38: ...0 6 9 6 211 3 202 5 250 250 2 5 16 7 15 2 223 5 213 7 250 250 2 7 5 24 2 22 0 238 5 227 3 250 250 2 10 30 8 28 0 251 7 239 3 300 250 25 74 8 68 0 209 3 200 8 250 250 2 3 10 6 9 6 230 5 220 0 300 250 2...

Page 39: ...0 59 0 70 2 3 3 9 66 8 80 2 5 6 1 71 2 90 2 7 5 9 0 77 0 90 2 10 11 0 81 0 100 10 11 0 61 0 80 2 3 3 9 68 8 80 2 5 6 1 73 2 90 2 7 5 9 0 79 0 90 2 10 11 0 83 0 100 15 17 0 67 0 80 2 3 3 9 74 8 90 2 5...

Page 40: ...9 6 220 3 212 0 250 250 2 5 16 7 15 2 232 5 223 2 250 250 2 7 5 24 2 22 0 247 5 236 8 300 250 2 10 30 8 28 0 260 7 248 8 300 300 25 74 8 68 0 218 3 209 8 250 250 2 3 10 6 9 6 239 5 229 0 300 250 2 5 1...

Page 41: ...90 2 3 3 9 75 3 90 2 5 6 1 79 7 100 2 7 5 9 0 85 5 100 2 10 11 0 89 5 110 10 11 0 69 5 90 2 3 3 9 77 3 100 2 5 6 1 81 7 100 2 7 5 9 0 87 5 110 2 10 11 0 91 5 110 15 17 0 75 5 90 2 3 3 9 83 3 100 2 5...

Page 42: ...6 231 3 223 0 250 250 2 5 16 7 15 2 243 5 234 2 300 250 2 7 5 24 2 22 0 258 5 247 8 300 300 2 10 30 8 28 0 271 7 259 8 300 300 25 74 8 68 0 229 3 220 8 300 250 2 3 10 6 9 6 250 5 240 0 300 300 2 5 16...

Page 43: ...2 3 3 9 78 6 100 2 5 6 1 83 0 100 2 7 5 9 0 88 8 110 2 10 11 0 92 8 110 10 11 0 72 8 90 2 3 3 9 80 6 100 2 5 6 1 85 0 100 2 7 5 9 0 90 8 110 2 10 11 0 94 8 110 15 17 0 78 8 100 2 3 3 9 86 6 110 2 5 6...

Page 44: ...284 7 275 9 300 300 2 5 16 7 15 2 296 9 287 1 350 300 2 7 5 24 2 22 0 311 9 300 7 350 350 2 10 30 8 28 0 325 1 312 7 350 350 25 74 8 68 0 282 7 274 2 350 300 2 3 10 6 9 6 303 9 293 4 350 350 2 5 16 7...

Page 45: ...3 3 9 85 9 100 2 5 6 1 90 3 100 2 7 5 9 0 96 1 110 2 10 11 0 100 1 110 10 11 0 80 1 90 2 3 3 9 87 9 100 2 5 6 1 92 3 100 2 7 5 9 0 98 1 110 2 10 11 0 102 1 110 15 17 0 86 7 100 2 3 3 9 94 5 110 2 5 6...

Page 46: ...0 390 4 374 8 450 450 40 114 0 104 0 361 3 348 8 450 450 2 5 0 16 7 15 2 394 7 379 2 500 450 2 7 5 24 2 22 0 409 7 392 8 500 450 2 10 0 30 8 28 0 422 9 404 8 500 500 460 414 508 2 18 6 125 2 18 6 125...

Page 47: ...0 403 2 387 6 450 450 40 114 0 104 0 374 1 361 6 450 450 2 5 0 16 7 15 2 407 5 392 0 500 450 2 7 5 24 2 22 0 422 5 405 6 500 500 2 10 0 30 8 28 0 435 7 417 6 500 500 460 414 508 2 23 1 150 2 23 1 150...

Page 48: ...0 412 2 396 6 500 450 40 114 0 104 0 383 1 370 6 450 450 2 5 0 16 7 15 2 416 5 401 0 500 500 2 7 5 24 2 22 0 431 5 414 6 500 500 2 10 0 30 8 28 0 444 7 426 6 500 500 460 414 508 2 23 1 150 2 26 9 179...

Page 49: ...0 65 0 202 1 250 2 5 0 7 6 217 3 250 2 7 5 11 0 224 1 250 2 10 0 14 0 230 1 250 60 77 0 217 1 250 2 5 0 7 6 232 3 300 2 7 5 11 0 239 1 300 2 10 0 14 0 245 1 300 75 96 0 240 8 300 2 5 0 7 6 256 0 350 2...

Page 50: ...2 25 34 0 270 1 300 2 30 40 0 282 1 300 60 77 0 2 10 14 0 245 1 300 2 15 21 0 259 1 300 2 20 27 0 271 1 300 2 25 34 0 285 1 350 2 30 40 0 297 1 350 75 96 0 2 10 14 0 268 8 350 2 15 21 0 282 8 350 2 20...

Page 51: ...9 1 250 1 25 34 0 236 1 300 1 30 40 0 242 1 300 1 40 52 0 254 1 300 60 77 0 1 20 27 0 244 1 300 1 25 34 0 251 1 300 1 30 40 0 257 1 300 1 40 52 0 269 1 300 75 96 0 1 20 27 0 267 8 350 1 25 34 0 274 8...

Page 52: ...1 4 300 50 65 0 239 7 300 2 5 7 6 254 9 300 2 7 5 11 0 261 7 300 2 10 14 0 267 7 300 60 77 0 254 7 300 2 5 7 6 269 9 300 2 7 5 11 0 276 7 350 2 10 14 0 282 7 350 75 96 0 278 4 350 2 5 7 6 293 6 350 2...

Page 53: ...5 34 0 307 7 350 2 30 40 0 319 7 350 60 77 0 2 10 14 0 282 7 350 2 15 21 0 296 7 350 2 20 27 0 308 7 350 2 25 34 0 322 7 350 2 30 40 0 334 7 400 75 96 0 2 10 14 0 306 4 400 2 15 21 0 320 4 400 2 20 27...

Page 54: ...6 7 300 1 25 34 0 273 7 300 1 30 40 0 279 7 300 1 40 52 0 291 7 350 60 77 0 1 20 27 0 281 7 350 1 25 34 0 288 7 350 1 30 40 0 294 7 350 1 40 52 0 306 7 350 75 96 0 1 20 27 0 305 4 400 1 25 34 0 312 4...

Page 55: ...5 0 251 1 300 2 5 0 7 6 266 3 300 2 7 5 11 0 273 1 300 2 10 0 14 0 279 1 300 60 77 0 266 1 300 2 5 0 7 6 281 3 350 2 7 5 11 0 288 1 350 2 10 0 14 0 294 1 350 75 96 0 289 8 350 2 5 0 7 6 305 0 400 2 7...

Page 56: ...5 34 0 319 1 350 2 30 40 0 331 1 350 60 77 0 2 10 14 0 294 1 350 2 15 21 0 308 1 350 2 20 27 0 320 1 350 2 25 34 0 334 1 400 2 30 40 0 346 1 400 75 96 0 2 10 14 0 317 8 400 2 15 21 0 331 8 400 2 20 27...

Page 57: ...8 1 300 1 25 34 0 285 1 350 1 30 40 0 291 1 350 1 40 52 0 303 1 350 60 77 0 1 20 27 0 293 1 350 1 25 34 0 300 1 350 1 30 40 0 306 1 350 1 40 52 0 318 1 350 75 96 0 1 20 27 0 316 8 400 1 25 34 0 323 8...

Page 58: ...ing for the building pressure BP control achieved via the modulating power exhaust option should sample building pressure in the area near the entrance lobby or other appropriate and sensitive locatio...

Page 59: ...Control Box Details Sizes 030 050 BP Building Pressure Transducer DP Duct Pressure Transducer FS Filter Switch OACFM Outdoor Air Cfm Sensor Transducer LEGEND Fig 47 Auxiliary Control Box Details Sizes...

Page 60: ...rom cross rail to fan sled should be as shown in Fig 50 UNIT SIZES 075 100 To remove shipping brackets re move the 6 screws holding each bracket to the cross rail There are 4 brackets per unit See Fig...

Page 61: ...s supply piping for 0 5 in wg maximum pressure drop Do not use supply pipe smaller than unit gas connection Step 17 Configure Optional Staged Gas or Modulating Gas Control The 48P Series large rooftop...

Page 62: ...screws provided The sides should be placed on the inside of top hoods for all hood assemblies 6 in 14 in and 30 in Attach speed clips to screen Insert screen into bottom opening of 6 in and 14 in hoo...

Page 63: ...IN INLET HOOD 30 IN INLET HOOD 30 IN INLET HOOD Fig 56 Flue Inlet Hood Locations Sizes 055 100 Low Heat Horizontal Supply Units Fig 57 Flue Inlet Hood Locations Sizes 055 100 High Heat Vertical and H...

Page 64: ...n Speed Clips Screws 67 1 Horizontal Supply Only 2 1 Horizontal Supply Only 2 Flue Outlet Hood Pre assembled 61 1 2 2 3 2 3 Flue Deflector V Type Hood Deflector Baffle Screws 62 1 2 2 Horizontal Suppl...

Page 65: ...FLECTOR HOOD MAKE SCREW HOLES ALIGN ACCESS PANEL OPENING HOOD SIDE TYP BOTH SIDES SPEED CLIP TYP 3 COVER 14 IN HOOD ONLY SCREEN Fig 63 Flue Deflector Baffle Curve Type Fig 64 Mounting Deflector Hoods...

Page 66: ...size 030 035 and 070 100 units See Fig 70 for baffle details Use 20 gage galva nized sheet metal or similar corrosion resistant material for the baffles Use field supplied screws to attach baffles to...

Page 67: ...ails NOTE 48 50P030 035 and 070 100 units do not require baffles UNIT SIZE QUANTITY DIMENSION A in mm 030 035 Not Used 040 060 2 78 125 0 125 1984 3 070 100 Not Used BAFFLE INSTALLATION LOCATION SIZES...

Page 68: ...should be wired using single twisted pairs of 20 AWG American Wire Gage conductor cable rated for the application except for the T 56 accessory sensor which requires 3 conductor cable HUMIDITY CONTROL...

Page 69: ...71 Field Control Thermostat Wiring a48 8474 1 2 4 3 5 6 7 8 9 10 12 13 14 15 16 T56 SPT T55 SPT UNIT TB201 11 SEN SEN SET JUMPER TERMINALS Fig 72 T55 or T56 Wiring a48 8475 RED BLK SENSOR 1 SENSOR 2...

Page 70: ...USED RCB J4 6 5 13 14 15 10 9 RCB J8 RELAY 5 MBB J8 7 8 TB201 FILTER STATUS MBB J8 Fig 74 Heat Interlock Relay Wiring Fig 75 Outdoor Air Enthalpy Switch Wiring Fig 76 CO2 Space Sensor Wiring Fig 77 F...

Page 71: ...71 RCB J4 CEM J6 4 3 RED BRN Fig 78 Fan Status Switch Wiring Fig 79 Space and Return Air Humidity Sensor Wiring Fig 80 Return Air CO2 Sensor Wiring a48 8482 a48 8483...

Page 72: ...2 BLU WHT FIRE SHUTDOWN RCB J4 TB 202 14 15 16 17 18 19 TB201 TB201 1 2 Fig 81 Return Air Smoke Detector Wiring Fig 82 Fire Shutdown Wiring Fig 83 Purge Evacuation and Pressurization Wiring a48 8483...

Page 73: ...28 CCN Connection Approved Shielded Cables The following color code is recommended NOTE If a cable with a different color scheme is selected a similar color code should be adopted for the entire netw...

Page 74: ...ontrol in the event of a building fire The available functions include Fire Shutdown Pressuriza tion Evacuation and Smoke Purge These functions are enhanced when multiple rooftop units are used to zon...

Page 75: ...TIONS RECOMMENDED VENDORS AND PART NUMBERS Wire Type Description Connect Air International Belden RMCORP Contractors Wire and Cable MS TP Network RS 485 22 AWG single twisted shielded pair low capacit...

Page 76: ...st dampers See Fig 82 for wiring SMOKE CONTROL INSTALLATION Implementation of the various smoke control modes on these units requires the in staller to modify the unit wiring to add contacts via eithe...

Reviews: