Point Name/Description
Default/Range
Supply Air Temperature
– Displays the current supply air temperature.
R: -56 to 245°F
(-48.9 to 118.3°C)
Supply Air Temp Calibration
– A calibration offset value to allow the supply air
temperature sensor to be adjusted to match a calibrated standard measuring the
temperature in the same location.
D:
R:
0 °F/ °C
-9.9 to 10 °F
(-5.5 to 5.5 °C)
Space Relative Humidity –
Displays the current value of relative humidity sensor, if
present.
R: 0 to 100%
Relative Humidity Calibration
– You can enter a calibration offset for the relative
humidity. The offset is added to or subtracted from the controller's RH input value, and
the calculated value is shown in the
Status
>
Space Relative Humidity
.
D:
R:
0%
-15 to 15%rh
Setpoints
Navigation:
i-Vu® / Field Assistant:
Properties
>
Control Program
>
Configuration
>
Setpoints
Select a color band on the setpoint graph to see the current setpoints in the
Heating
and
Cooling
fields. The values in this
graphic are Fahrenheit. See setpoint descriptions below.
NOTE
This graphic is an example only. Your setpoints may differ.