SAFETY

WARNING: EYE & SKIN BURN HAZARD

Failure to follow this warning could result in personal injury.
This unit contains high energy ultraviolet C-band (UVC) germicidal lamps which can cause serious temporary eye and skin
irritation. Never expose unprotected eyes or skin to the UVC light.

Installation and servicing of air-conditioning equipment can be hazardous due to system pressure and electrical components. Only trained and
qualified service personnel should install, repair or service HVAC equipment.

Untrained personnel can perform basic maintenance functions such as changing lamps. All other operations should be performed by trained service
personnel. When working on air-conditioning equipment, observe precautions in the literature, tag and labels attached to the unit or accessory, and
all other safety precautions that may apply.

Recognize safety information. This is the safety-alert symbol

. When you see this symbol on the unit and in instructions or manuals, be alert

to the potential for personal injury.

Understand the signal words DANGER, WARNING, and CAUTION. These words are used with the safety-alert symbol. DANGER identifies the
most serious hazards which

will

result in severe personal injury or death. WARNING signifies a hazard which

could

result in personal injury or

death. CAUTION is used to identify unsafe practices which

would

result in minor personal injury or product and property damage. NOTE is used

to highlight suggestions which

will

result in enhanced installation, reliability, or operation.

Follow all safety codes. Wear safety glasses and work gloves. Have a fire extinguisher available if needed. Read these instructions thoroughly and
follow all warnings or cautions attached to the unit. Consult local building codes and National Electrical Code (NEC) for special requirements.

Before proceeding with installation, inspect thoroughly for shipping damage. Notify shipper immediately if any damage is found. Check for proper
clearances of moving parts.

The qualified installer or agency must use factory-authorized kits or accessories when modifying this product. Refer to the individual instructions
packaged with the kits or accessories when installing.

Fig. 1–Two Lamp Model UV Lamp

C03009

Installation Instructions

UV Lamp

Accessory Ultraviolet (UV) Germicidal Lamp
1 & 2 Lamp Models—115-v & 208/230-v

Form:

 

    

00001398           

              

Printed in U.S.A.

            FEB

-

2018                                    Catalog No.

  IM-

UVL

CR-01

Summary of Contents for UVLCC1LP

Page 1: ... signal words DANGER WARNING and CAUTION These words are used with the safety alert symbol DANGER identifies the most serious hazards which will result in severe personal injury or death WARNING signifies a hazard which could result in personal injury or death CAUTION is used to identify unsafe practices which would result in minor personal injury or product and property damage NOTE is used to hig...

Page 2: ...e to follow this caution could result in damage to unit or personal injury Perform visual inspection of potential mounting location by removing unit cabinet door prior to cutting or drilling Be careful not to cut drill or drive screws into coil refrigerant lines or other objects inside the HVAC unit NOTE On indoor coils 2 tons or smaller it is recommended that this UV lamp be installed in the conn...

Page 3: ...llow lamp to cool for 1 minute before opening UV lamp casing or HVAC unit cabinet NOTE The recommended life of the lamp assembly in this UV lamp product is 1 year of constant operation or a maximum of 9 000 hours of unit runtime 1 When replacement of lamp is needed order proper lamp assembly See Table 2 from your dealer distributor 2 Disconnect power supply from UV lamp by unplugging the electrica...

Page 4: ...C03004 Fig 2 UV Lamp Assembly Detail View Lamp Base LED Lights Lamp Ballast Assembly Note LED Lights are not lamp change indicators Lamps should be changed annually 4 ...

Page 5: ...2 Fig 3A Typical Furnace Coil Mounting Locations 115 v Application Horizontal N Coil Wide 042 048 060 060A A Coil Side View Standard A Coil Suggested Mounting Locations Front of Coil Casing Standard N Coil 5 ...

Page 6: ...C03021 Fig 3B Alternate Furnace Coil Mounting Locations 115 v Application Small N Coil Small A Coil Alternate Mounting Locations 6 ...

Page 7: ...C04014 Fig 3C Fan Coil Mounting Locations 208 230 v Application Sloped Fan Coil A Coil in Fan Coil Single Lamp Application Sloped Fan Coil Dual Lamp Application 7 ...

Page 8: ... 2018 CAC BDP 7310 W Morris St Indianapolis IN 46231 8 Form No 00001398 Catalog No IM UVLCR 01 ...

Reviews: