background image

2. Push wires back into wall. Align connector block on the

right-hand track in back plate housing, push tab to the right
and slide connector block back to its original location.

3. Align smart sensor circuit board in back plate housing and

snap securely in place.

4. Reinstall thermostat cover pressing firmly until it locks into

place.

5. Install Smart Sensor Power Pack into the Comfort Zone

Center. Attach wires according to Fig. 6.

NOTE:

Four Zone Controller is always zone 1.

Table 1—Rotary Switch Options

POSITION

DESCRIPTION

1

Set Device Address

ie. Zone 2 = Address 3

ie. Zone 3 = Address 2

ie. Zone 4 = Address 1

2

Calibrate Zone Temp

Sensor

3 through D

Not Used

E

Toggle For Alternate

Display On/Off

F

Toggle For Baud Rate

On = 2400
Off = 4800

Note: Rotary switch must be always be left in the

0

zero position after viewing

options. Failure to reset rotary switch to 0 will interupt communication
between Smart Sensor and Four Zone Controller.

Table 2—Smart Sensor Error Codes

ERROR CODE

FAILURE

ROTARY

SWITCH

DEFAULT

SF 01

Device Address

1

64

SF 02

Packed Setpoints*

n/a

74, 74

SF 03

Zone Temp Cal Word

2

1024

SF 04

Baud Rate

F

on

SF 05

Alternate Display

E

off

SF 06

Display Status

n/a

08

SF 07

Packed Set Back Spts

n/a

85, 60

SF 08

Packed Spts Base

Temps

n/a

70, 66

HF 20

Zone Temp Sensor

n/a

Bad board sensor

System should run

HF 21

Controller Comm Fault

n/a

Possible wiring prob-

lem or bad board

HF 22

GPI UART Trans Fault

n/a

Fatal error—system

stopped

HF 23

Non Volatile RAM

Fault

n/a

Fatal error—system

stopped

* Packed setpoints temperatures will depend upon the setpoint base tempera-
tures
SF = Software Failure
HF = Hardware Failure

Fig. 3—Aligning RIbbon Cable

A94315

RIBBON CONNECTOR

TERMINAL BLOCK

SMART SENSOR

Fig. 4—Mounting Back Plate

A94316

Fig. 5—Smart Sensor Wiring

A94317

RED

GREEN

BLACK

YELLOW

WHITE

2