Before performing service or maintenance operations on
system, turn off power to unit. Turn off accessory heater
power switch, if applicable. Electrical shock can cause
personal injury.

Recognize safety information. This is the safety-alert symbol

.

When you see this symbol in instructions or manuals, be alert to
the potential for personal injury.
Understand the signal words DANGER, WARNING, CAUTION,
and NOTE. These words are used with the safety-alert symbol.
DANGER identifies the most serious hazards which

will

result in

severe personal injury or death. WARNING signifies a hazard
which

could

result in personal injury or death. CAUTION is used

to identify unsafe practices which

would

result in minor personal

injury or product and property damage. NOTE is used to highlight
suggestions which

will

result in enhanced installation, reliability,

or operation.
These instructions cover minimum requirements and conform to
existing national standards and safety codes. In some instances,
these instructions exceed certain local codes and ordinances,
especially those that may not have kept up with changing residen-
tial construction practices. We require these instructions as a
minimum for a safe installation.

INTRODUCTION

The 50GS and 50GX units (see Fig. 1) are fully self-contained, and
designed for outdoor installation. See Figs. 2 and 3 for unit
dimensions. All unit sizes have discharge openings for both
horizontal and downflow configurations, and are factory shipped
with all downflow duct openings covered . Units may be installed
either on a rooftop, ground-level cement slab, or directly on the
ground if local codes permit. (See Fig. 4A for roof curb dimen-
sions.)

RECEIVING AND INSTALLATION

Step 1—Check Equipment

IDENTIFY UNIT
The unit model number and serial number are stamped on the unit
identification plate. Check this information against shipping pa-
pers.
INSPECT SHIPMENT
Inspect for shipping damage while unit is still on shipping pallet.
If unit appears to be damaged or is torn loose from its anchorage,
have it examined by transportation inspectors before removal.
Forward claim papers directly to transportation company. Manu-
facturer is not responsible for any damage incurred in transit.
Check all items against shipping list. Immediately notify the
nearest Carrier Air Conditioning office if any item is missing. To
prevent loss or damage, leave all parts in original packages until
installation.

Step 2—Provide Unit Support

ROOF CURB
Install accessory roof curb in accordance with instructions shipped
with curb (See Fig. 4A). Install insulation, cant strips, roofing, and
flashing. Ductwork must be attached to curb.

IMPORTANT:

The gasketing of the unit to the roof curb is critical

for a watertight seal. Install gasketing material supplied with the
roof curb. Improperly applied gasketing also can result in air leaks
and poor unit performance.
Curb should be level to within 1/4 in. (See Fig. 5A). This is
necessary for unit drain to function properly. Refer to accessory
roof curb installation instructions for additional information as
required.

SLAB MOUNT
Place the unit on a solid, level concrete pad that is a minimum of
4 in. thick with 2 in. above grade (See Fig. 5B). The slab should
extend approximately 2 in. beyond the casing on all 4 sides of the
unit. Do not secure the unit to the slab

except

when required by

local codes.
GROUND MOUNT
The unit may be installed either on a slab or placed directly on the
ground if local codes permit. Place the unit on level ground
prepared with gravel for condensate discharge.

Step 3—Provide Clearances

The required minimum service clearances are shown in Fig. 2 & 3.
Adequate ventilation and outdoor air must be provided. The
outdoor fan draws air through the outdoor coil and discharges it
through the top fan grille. Be sure that the fan discharge does not
recirculate to the outdoor coil. Do not locate the unit in either a
corner or under an overhead obstruction. The minimum clearance
under a partial overhang (such as a normal house overhang) is 36
in. above the unit top. The maximum horizontal extension of a
partial overhang must not exceed 48 in. For extended overhangs,
provide a minimum clearance of 48 in.

IMPORTANT:

Do not restrict outdoor airflow. An air restriction

at either the outdoor-air inlet or the fan discharge may be
detrimental to compressor life.
Do not place the unit where water, ice, or snow from an overhang
or roof will damage or flood the unit. Do not install the unit on
carpeting or other combustible materials. Slab-mounted units
should be at least 4 in. above the highest expected water and runoff
levels. Do not use unit if it has been under water.

Step 4—Field Fabricate Ductwork

Secure all ducts to roof curb and building structure on vertical
discharge units.

Do not connect ductwork to unit.

For horizontal

applications, unit is provided with flanges on the horizontal
openings. All ductwork should be secured to the flanges. Insulate
and weatherproof all external ductwork, joints, and roof openings
with counter flashing and mastic in accordance with applicable
codes.
Ducts passing through an unconditioned space must be insulated
and covered with a vapor barrier. If a plenum return is used on a
vertical unit, the return should be ducted through the roof deck to
comply with applicable fire codes. A minimum clearance is not
required around ductwork. Cabinet return-air static shall not
exceed -.25 in. wg.

Step 5—Rig and Place Unit

Rigging and handling of this equipment can be hazardous for many
reasons due to the installation location (roofs, elevated structures,
etc.)
Only trained, qualified crane operators and ground support staff
should handle and install this equipment.
When working with this equipment, observe precautions in the
literature, on tags, stickers, and labels attached to the equipment,
and any other safety precautions that might apply.
Follow all applicable safety codes. Wear safety shoes and work
gloves.

Never stand beneath rigged units or lift over people.

Never exceed 200 lbs. per bracket lifting force.

2

Summary of Contents for SINGLE PACKAGED ELECTRIC COOLING UNITS 50GS

Page 1: ...IT 24 EVAPORATOR AIRFLOW 25 METERING DEVICE ACUTROL DEVICE 25 LIQUID LINE STRAINER 25 Troubleshooting 25 Start Up Checklist 25 NOTE TO INSTALLER Before the installation READ THESE INSTRUCTIONS CAREFULLY AND COMPLETELY Also make sure the User s Manual and Replacement Guide are left with the unit after installation SAFETY CONSIDERATIONS Installation and servicing of air conditioning equipment can be...

Page 2: ...5A This is necessary for unit drain to function properly Refer to accessory roof curb installation instructions for additional information as required SLAB MOUNT Place the unit on a solid level concrete pad that is a minimum of 4 in thick with 2 in above grade See Fig 5B The slab should extend approximately 2 in beyond the casing on all 4 sides of the unit Do not secure the unit to the slab except...

Page 3: ...82 6 14 0 355 6 15 0 381 0 50GS036 208 230 1 60 208 230 3 60 460 3 60 268 121 6 37 02 940 3 20 0 508 0 14 0 355 6 13 0 330 2 50GS042 208 230 1 60 208 230 3 60 460 3 60 294 133 3 35 02 889 5 19 0 482 6 14 0 355 6 13 0 330 2 50GX024 208 230 1 60 270 122 5 37 02 940 3 18 5 469 9 14 5 368 3 16 0 406 4 50GX030 208 230 1 60 208 230 3 60 291 132 0 39 02 991 1 19 5 495 3 15 5 393 7 17 6 447 0 50GX036 208 ...

Page 4: ... 176 38 98 990 2 19 0 482 6 16 0 406 0 17 0 432 0 50GX042 208 230 1 60 208 230 3 60 460 3 60 321 146 38 98 990 2 20 5 520 7 16 75 425 5 16 6 421 6 50GX048 208 230 1 60 208 230 3 60 460 3 60 326 148 38 98 990 2 19 5 495 3 17 6 447 6 18 0 457 2 50GX060 208 230 1 60 208 230 3 60 460 3 60 399 181 42 98 1091 1 20 5 520 7 16 2 412 8 17 6 447 0 C99006 REQUIRED CLEARANCE FOR OPERATION AND SERVICING INCHES...

Page 5: ...ACunit base Gasketing outer flange Flashing field supplied Roofing mater ial field supplied Cant strip field supplied Provided with roofcurb Roof Duct wo rk field supplied Insulation field supplied Roofcurb Wood nailer Gasketing inner flange Screw NOTE A Roof Curb for Small Cabinet Note A When unit mounting screw is used retainer bracke t must also be used HVAC unit base Gasketing outer flange Fla...

Page 6: ...66 3 55 56 56 58 71 88 106 57 61 64 85 80 108 4 94 94 95 98 97 122 145 88 86 90 110 112 140 TOTAL WEIGHT 254 260 258 268 294 324 389 270 291 299 321 326 399 C00071 1 2 4 3 x y Fig 5A Unit Leveling Tolerances C99065 A B C MAXIMUM ALLOWABLE DIFFERENCE in A B B C A C 1 4 1 4 1 4 Fig 5B Slab Mounting Detail C99096 OPTIONAL RETURN AIR OPENING OPTIONAL SUPPLY AIR OPENING EVAP COIL COND COIL 2 6 ...

Page 7: ...de and bottom of the unit For downshot applications the ductwork can be connected to the roof curb See Fig 2 3 for connection sizes and locations IMPORTANT Use flexible connectors between ductwork and unit to prevent transmission of vibration Use suitable gaskets to ensure weathertight and airtight seal When electric heat is installed use fire proof canvas or similar heat resistant material connec...

Page 8: ...BLOWER Nominal Airflow Cfm Size in Motor HP RPM 600 10x10 1 4 825 800 10x10 1 4 1075 1000 10x10 1 4 1075 1200 11x10 1 2 1075 1400 11x10 3 4 1075 1600 11x10 3 4 1075 2000 11x10 1 0 1100 RETURN AIR FILTERS in Throwaway 20x20 20x20 20x20 20x24 20x24 24x30 24x30 Required filter sizes shown are based on the larger of the ARI Air Conditioning and Refrigeration Institute rated cooling airflow or the heat...

Page 9: ...or maximum required airflow either heating or cooling for unit being installed Avoid abrupt duct size increases or decreases or performance may be affected 13 Adequately insulate and weatherproof all ductwork located outdoors Insulate ducts passing through unconditioned space and use vapor barrier in accordance with latest issue of Sheet Metal and Air Conditioning Contractors National Association ...

Page 10: ...sure lug connection 11 of the compressor contactor 4 Connect L2 to pressure lug connection 23 of the compressor contactor Three phase units 1 Run the high voltage L1 L2 L3 and ground leads into the control box 2 Connect ground lead to chassis ground connection 3 Locate the black and yellow wires connected to the lines side of the contactor 4 Connect field L1 to black wire on connection 11 of the c...

Page 11: ...5 0 20 0 18 1 20 8 26 0 30 0 36 1 41 7 54 2 62 5 72 2 83 3 28 7 28 7 28 7 31 0 37 5 42 5 50 1 57 1 72 7 83 1 95 3 109 2 35 35 35 35 40 45 60 60 80 90 100 110 208 230 3 60 187 254 10 7 85 1 4 4 3 8 5 0 7 5 10 0 11 3 15 0 15 0 19 9 10 4 12 0 20 8 24 1 31 3 36 1 41 6 48 0 18 8 18 8 18 8 20 0 31 1 35 1 44 1 50 1 57 0 65 0 25 25 25 25 35 40 45 60 60 70 460 3 60 414 508 5 3 42 0 8 2 5 10 15 20 6 12 18 2...

Page 12: ... 6 42 6 50 3 57 2 72 8 83 3 95 4 109 3 35 35 35 35 40 45 60 60 80 90 100 110 208 230 3 60 187 253 12 4 88 0 1 6 4 1 3 8 5 0 7 5 10 0 11 3 15 0 15 0 20 0 10 4 12 0 20 8 24 1 31 3 36 1 41 7 48 1 21 2 21 2 21 2 21 2 31 2 35 2 44 2 50 2 57 2 65 3 25 25 25 25 35 40 45 60 60 70 460 3 60 414 506 6 1 44 0 0 9 2 0 5 10 15 20 6 0 12 0 18 0 24 1 10 5 10 5 17 5 25 1 32 6 15 15 20 30 35 048 208 230 1 60 187 25...

Page 13: ...ng cutter and remove component from unit d Carefully unsweat remaining tubing stubs when neces sary Oil can ignite when exposed to torch flame Proceed as follows to inspect and prepare the unit for initial startup 1 Remove access panel 2 Read and follow instructions on all WARNING CAUTION and INFORMATION labels attached to or shipped with unit 3 Make the following inspections a Inspect for shippin...

Page 14: ...mostat SYSTEM switch in OFF position Observe that blower motor starts when FAN switch is placed in ON position and shuts down after 30 second fan time delay expires when FAN switch is placed in AUTO position 2 Place SYSTEM switch in COOL position and FAN switch in AUTO position Set cooling control below room temperature Observe that compressor condenser fan and evaporator blower motors start Obser...

Page 15: ...Fig 12 Wiring Diagram 208 230 60 1 C99003 15 ...

Page 16: ...Fig 13 Wiring Diagram 208 230 60 3 C99004 16 ...

Page 17: ...Fig 14 Wiring Diagram 460 60 3 C99005 17 ...

Page 18: ...speed remove and replace with lead for desired blower motor speed Insulate the removed lead to avoid contact with chassis parts FOR 460 V GE MOTORS For color coding on the 460 v GE motor leads see Table 7 To change the speed of the indoor fan motor IFM remove fan motor speed lead from the time delay relay TDR and replace with the lead for the desired blower motor speed The motor speed lead is atta...

Page 19: ...455 438 422 Cfm 1338 1295 1288 1181 1111 968 813 High Watts 646 636 626 614 602 589 Cfm 1385 1268 1196 1159 1032 948 042 Low Watts 675 660 650 640 630 620 610 595 580 Cfm 1387 1326 1275 1204 1142 1081 995 918 850 Med Watts 886 855 825 795 778 765 750 735 718 700 Cfm 1458 1406 1350 1285 1224 1163 1091 1013 932 870 High Watts 1000 950 925 910 890 875 855 833 Cfm 1488 1424 1360 1296 1233 1148 1071 10...

Page 20: ...96 783 529 036 Low Watts 470 458 445 430 415 399 384 Cfm 1352 1257 1240 1199 1107 1015 924 Med Watts 514 501 487 471 455 438 422 Cfm 1338 1295 1288 1181 1111 968 813 High Watts 646 636 626 614 602 589 Cfm 1385 1268 1196 1159 1032 948 042 Low Watts 625 614 605 593 574 549 518 485 454 Cfm 1540 1510 1473 1396 1348 1288 1192 1124 1037 Med Watts 726 695 661 625 591 561 540 Cfm 1648 1593 1530 1446 1352 ...

Page 21: ...lean when necessary 3 Inspect blower motor and wheel for cleanliness and check lubrication each heating and cooling season Clean when necessary 4 Check electrical connections for tightness and controls for proper operation each heating and cooling season Service when necessary 5 Ensure electric wires are not in contact with refrigerant tubing or sharp metal edges C99037 Fig 15 Cooling Charging Cha...

Page 22: ...he blower wheel and motor annually Disconnect and tag electrical power to the unit before cleaning the blower motor and wheel Failure to adhere to this warning could cause personal injury or death To clean the blower motor and wheel 1 Remove and disassemble blower assembly as follows a Remove unit access panel b Disconnect motor lead from time delay relay TDR Disconnect yellow lead from terminal L...

Page 23: ...wheel and housing with vacuum cleaner using soft brush attach ment Remove grease and oil with mild solvent d Reassemble wheel into housing e Reassemble motor into housing Be sure setscrews are tightened on motor shaft flats and not on round part of shaft f Reinstall unit access panel 3 Restore electrical power to unit Start unit and check for proper blower rotation and motor speeds during heating ...

Page 24: ...r to top cover 2 Turn motor grille assembly upside down on top cover to expose the fan blade 3 Inspect the fan blades for cracks or bends 4 If fan needs to be removed loosen the setscrew and slide the fan off the motor shaft 5 When replacing fan blade position blade so that the hub is 1 8 in away from the motor end 1 8 in of motor shaft will be visible 6 Ensure that setscrew engages the flat area ...

Page 25: ...The heating and or cooling air flow does not require checking unless improper performance is suspected If a problem exists be sure that all supply and return air grilles are open and free from obstructions and that the air filter is clean When necessary refer to Indoor Airflow and Airflow Adjustments section to check the system airflow METERING DEVICE ACUTROL DEVICE This metering device is a fixed...

Page 26: ...use and correct Defective run start capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat set too low R...

Page 27: ...ghtness III START UP Supply Voltage L1 L2 C S __________ L2 L3 S R __________ L3 L1 R C __________ Compressor Amps L1 C __________ L2 S __________ L3 R __________ Indoor Evaporator Fan Amps __________ TEMPERATURE Outdoor Condenser Air Temperature __________ DB Return Air Temperature __________ DB __________ WB Cooling Supply Air __________ DB __________ WB PRESSURES Refrigerant Suction __________ ...

Page 28: ...1 50gsgx4si Manufacturer reserves the right to discontinue or change at any time specifications or designs without notice and without incurring obligations Book 1 6 Tab 6 8 PC 101 Catalog No 535 00130 Printed in U S A Form 50GS GX 4SI Pg 28 9 03 Replaces 50GS GX 3SI ...