background image

11

Model 20

Refrigeration Principle

Section 6

Refrigeration Principle

The insulated evaporator assembly has copper tubing

coiled and soldered around the outer diameter. An

automatic expansion valve sprays liquid refrigerant

through the copper tubing. This refrigerant rapidly

boils, picking up heat from the solution in the

removable basin. As a low pressure gas, the

refrigerant now travels out the copper tubing and down

to the compressor.
The automatic expansion valve is pre--set from the

factory at 9--10 PSI. To make any adjustments to the

automatic expansion valve, place the low side line of

a gauge set to the low side access port near the

compressor. Place the pushbutton control switch in the

ON position. While observing the gauge, turn the

adjustment knob of the automatic expansion valve. A

clockwise adjustment increases the low side pressure.

A counterclockwise adjustment decreases the low

side pressure.

Low Side:

The point between the outlet of the

automatic expansion valve as it enters the insulated

evaporator, all the way to the compressor.

Low Side Pressure:

Automatic expansion valve

setting of 9--10 PSI.

The compressor is a pump which circulates refrigerant

throughout the system. This compressor receives the

low pressure gas from the insulated evaporator. It

compresses the gas and sends it to the condenser as

a high pressure gas. As a safety measure, the

compressor has an internal overload. Should an

overload occur, the compressor will automatically shut

down. Once it has cooled, the compressor will start up

again.

The condenser receives the high pressure gas from

the compressor. A fan motor and blade pull air through

the rear of the unit, and across the condenser. At this

time, heat is removed from the refrigerant gas and is

dissipated out the sides and front of the machine.

Once heat is removed from the gas, the refrigerant

turns into a liquid and drops to the bottom of the

condenser.

The filter dryer receives the liquid refrigerant from the

condenser. It filters impurities from the refrigerant

before it reaches the automatic expansion valve. Any

time the refrigerant is discharged from the system, a

new filter dryer must be installed.

The heat exchanger consists of the liquid line and

suction line soldered together. This is used to sub--cool

the liquid refrigerant in the high side before it reaches

the automatic expansion valve. The colder the

refrigerant is before it reaches the automatic

expansion valve, the more heat it will pick up when it

enters the insulated evaporator. More importantly, the

heat exchanger vaporizes any liquid refrigerant that

might leave the insulated evaporator before it reaches

the compressor.

If the frozen slush in the removable basin was left

unattended for prolonged periods, the liquid refrigerant

entering the insulated evaporator would not be able to

boil off rapidly enough, due to the lack of heat. This

would cause the refrigerant to leave the insulated

evaporator as a liquid. If this occurred, frost would build

up near or on the compressor. Liquid refrigerant

allowed to enter the compressor would boil rapidly

because of the heat in the compressor. This violent

boiling action would allow the refrigerant to pick up

excessive oil in the compressor.

If the machine is subject to this condition, the

excessive oil will separate from the refrigerant as it

enters the insulated evaporator. The oil will occupy

space that the refrigerant must occupy to sufficiently

remove heat from the solution. In addition, oil leaving

a compressor could cause damage to the compressor.

To correct an oil--logged insulated evaporator, open

the automatic expansion valve to approximately 20

PSI. Pour hot water into the insulated evaporator and

place the unit in the ON position. This will cause the

refrigerant to flow into the insulated evaporator very

rapidly. It will then boil violently because of the hot

water. This violent boiling will allow the refrigerant to

pick up the oil and carry it back down to the

compressor. Once the hot water begins to cool, place

the machine in the OFF position. Adjust the automatic

expansion valve to the original setting.

High Side:

The point between the outlet of the

compressor, all the way to the expansion valve.

High Side Pressure:

Should be maintained between

180--200 PSI, depending on room ambient conditions.

Summary of Contents for Saline 20

Page 1: ...Model 20 Saline Slush Freezer Operating Instructions 030990 M 7 23 01...

Page 2: ...umber Serial Number Electrical Specs Voltage Cycle Phase Maximum Fuse Size A Minimum Wire Ampacity A E July 2001 Taylor All rights reserved 030990 M The word Taylor and the Crown design are registered...

Page 3: ...sclaimer 4 Section 3 Safety 5 Section 4 Operator Parts Identification 7 Section 5 Operating Procedures 9 Section 6 Refrigeration Principle 11 Section 7 Refrigeration Schematic 12 Section 8 Electrical...

Page 4: ...Table of Contents Model 20 Notes...

Page 5: ...o the equipment Note All repairs must be performed by an authorized Taylor Service Technician This unit has many sharp edges that can cause severe injuries Site Preparation Review the area the unit is...

Page 6: ...local authorities FOLLOW YOUR LOCAL ELECTRICAL CODES CAUTION THIS EQUIPMENT MUST BE PROPERLY GROUNDED FAILURE TO DO SO CAN RESULT IN SEVERE PERSONAL INJURY FROM ELECTRICAL SHOCK CAUTION Always disconn...

Page 7: ...nt liquid sprayed onto the skin may cause serious damage to tissue Keep eyes and skin protected If refrigerant burns should occur flush immediately with cold water If burns are severe apply ice packs...

Page 8: ...ore it must be collected separately after its use is completed and cannot be disposed as unsorted municipal waste The user is responsible for returning the product to the appropriate collection facili...

Page 9: ...rate this equipment unless it is properly grounded S DO NOT operate this equipment with larger fuses than specified on the equipment data label S DO NOT attempt any repairs unless the main power suppl...

Page 10: ...te or local regulatory agencies and must be followed accordingly Please refer to the cleaning section of this manual for the proper procedure to clean this unit DO NOT obstruct air intake and discharg...

Page 11: ...4 20 x 3 8 PHL 038872 3 Switch Pushbutton Neon Display 030629 12 3a Button Only Black 031073 4 Panel A Side Front X38874 5 Screw 10 32 x 3 8 PHL 038871 Item Description Part No 6 Caster Swivel 3 4 Ste...

Page 12: ...closure Fan 014261 Bracket Fan 025675 Fan 5 Blade 10 Pull 021371 5 Dryer Filter HP62 048901 Item Description Part No 6 Valve Access 1 4 x 3 8 043232 7 Compressor AJA2419ZXA 051787 12 8 Relay 3 Pole 11...

Page 13: ...1300 cc s maximum to the insulated evaporator The heat transfer medium is dictated by the hospital The solution should be a good conductor of heat but should not freeze at a temperature above 37 2_C...

Page 14: ...iver loosen the drain plug in the center of the insulated evaporator until all transfer solution has been drained Tighten the drain plug IMPORTANT It is assumed that all operating rooms are under stri...

Page 15: ...atic expansion valve Any time the refrigerant is discharged from the system a new filter dryer must be installed The heat exchanger consists of the liquid line and suction line soldered together This...

Page 16: ...12 Refrigeration Schematic Model 20 Section 7 Refrigeration Schematic...

Page 17: ...ill stop and the light will go out Under no circumstances should the pushbutton control switch be pressed repeatedly This will cause the compressor start and stop thus causing possible damage to the c...

Page 18: ...idenced by suction pressure not stabilizing at 3 4 PSI 21 28 kPa Pressure fluctuates e Call a service technician f Dirty condenser as evidenced by high head pressure f Clean the condenser regularly g...

Page 19: ...or terminal box for continuity to compressor casing a Call a service technician b Low or high line voltage While the unit is running check voltage supply at the compressor relay b Contact an electrici...

Page 20: ...ACITOR START 270 324UF 110V 030847 12 1 103 115 60 1 RELAY START COMPRESSOR 030846 12 1 103 115 60 1 RELAY START COMPRESSOR 031789 1 103 208 230 60 1 RELAY START COMPRESSOR 051792 1 103 220 240 50 1 C...

Page 21: ...G 424 ID X 103 W 023953 6 1 000 RELAY 3 POLE 012725 1 103 SWITCH PRESSURE 440 PSI SOLDER 048230 1 103 SWITCH PUSHBUTTON NEON DISPLAY 030629 1 103 BUTTON 031073 1 000 COVER POWER SWITCH VALVE ACCESS 1...

Page 22: ...Model 20 051813 12...

Reviews: