Appendix A: Network Points List for RTU Open
RTU Open v5
CARRIER CORPORATION ©2019
Integration Guide
All rights reserved
51
BACnet
Modbus
Point Name
Point
Access
Units
Default
Value
BACnet Point Name
BACnet
Object ID
Modbus Register
Type
Modbus
Register #
Compressor 2 Runtime
R
hr
comp2_rntm
AV:2018
Linkage Max Damper
Position
R
%
link_max_dmpr
AV:2611
Air Source Supply Air
Temp
R
°F
link_sat
AV:2608
Max VFD Output
R/W
%
100
max_vfd_spd
AV:3026
Dehum Min VFD Output R/W
%
100
dehum_min_vfd
AV:3028
Air Source Outdoor Air
Temp
R
°F
link_ahu_oat
AV:2609
Stage 3 SAT Stpt
R/W
°F
56
stg_3_sat
AV:83010
Stage 1 SAT Stpt
R/W
°F
57
stg_1_sat
AV:83008
HP Aux Heat Lockout
Temp
R/W
°F
40
oat_auxht_lockout
AV:3025
input_1
R
ai_1
AI:1001
Factory Test Analog 2
Control
R/W
V
0
ao2_fac_test
AV:91002
Compressor 2 Service
Alarm Timer
R/W
hr
0
comp2_service_hrs
AV:83007
Compressor 1 Service
Alarm Timer
R/W
hr
0
comp1_service_hrs
AV:83006
Compressor 1 Runtime
R
hr
comp1_rntm
AV:2017
Min VFD Output
R/W
%
40
min_vfd_spd
AV:3027
Stage 2 SAT Stpt
R/W
°F
57
stg_2_sat
AV:83009
slidepot voltage reading R
slidepot_volts
AI:1012
Filter Runtime
R
hr
filter_rntm
AV:2015
Fan Off Delay
R/W
seconds
90
fan_delay_off
AV:9024
input_7
R
°F
ai_7
AI:1007
input_11
R
ai_11
AI:1011
input_2
R
ai_2
AI:1002
Minimum Cooling SAT
R/W
°F
50
sat_cl_min
AV:83003
Power Fail Restart Delay R/W
seconds
5
start_delay
AV:9007
Holding Register
(Float)
127
Supply Fan Service
Alarm Timer
R/W
hr
0
sfan_service_hrs
AV:83005
Supply Fan Runtime
R
hr
sfan_rntm
AV:2014
Indoor Air Quality CO2
(ppm)
R
ppm
iaq
AV:1009
Input Register
(Float)
73
Supply Fan VFD
R
%
vfd_output
AV:2027
Indoor Air Quality
R
0=Normal
1=Alarm
iaq_alarm
BV:7005
Discrete Input
33
Supply Air Temperature
R
0=Normal
1=Alarm
sat_alarm
BV:7004
Discrete Input
47
Space Relative Humidity R
0=Normal
1=Alarm
sprh_hi_alarm
BV:7018
Discrete Input
34
Space Temp Sensor
R
0=Normal
1=Alarm
spt_fail
BV:7001
Discrete Input
46
Outdoor Air Quality CO2
(ppm)
R
ppm
oaq
AV:1012
Input Register
(Float)
85
Gas Valve
R
0=Normal
1=Alarm
igc_alarm
BV:7050
Discrete Input
40
Setpoint
R/W
°F
occ_cl_stpt
AV:3001
Holding Register
(Float)
9