background image

527 01 2701 00

Specifications subject to change without notice.

33

        LEGEND

*  Table  9  illustrates  the  complete  hierarchy.  Your  menu  parameters

may  be  different  depending  on  your  configuration.  For  example  if

you do not have a DCV (CO

2

) sensor, then none of the DCV param

-

eters appear.

†  When values are displayed, pressing and holding the   or   button

causes the display to automatically increment.

**  N/A = Not Applicable.

†† ERV Operation: When in cooling mode AND the conditions are NOT

OK  for  economizing  -  the  ERV  terminal  will  be  energized.  In  the

Heating mode, the ERV terminal will be energized when the OA is

below the ERV OAT setpoint in the setpoint menu.

NOTES:

1. STATUS



 OCCUPIED — The factory-standard Occupancy signal

originates with  a thermostat or other controller call for indoor fan

operation at UCB terminal G. This signal passes through the Unit

Control  Board’s  OCCUPANCY  jumper  to  the  ECONO  connector

and to the W7220’s OCC input terminal. An external timeclock or

relay  is  required  to  implement  an  Occupancy  schedule  on  the

economizer damper position.

2. STATUS 

 MA TEMP, SETPOINTS 

 MAT SET — The W7220

menu  parameters  and  labels  include  designations  MA,  MAT  and

Mixed Air for the economizer cooling control sensor. On these roof

-

top units, the economizer control sensor is located downstream of

the evaporator/indoor coil in the supply fan section where this sen

-

sor is designated as Supply Air Temperature (SAT) sensor.

3. SETPOINTS 

 DRYBLB SET  — This  point is  not displayed if a

Return  Air  (differential)  temperature  sensor  or  an  Outdoor  Air

enthalpy sensor is connected.

4. SYSTEM  SETUP  parameters  must  be  configured  as  noted  for

Multi

-

Speed unit operation:

EQUIPMENT = CONV

AUX2 IN = W

FAN SPEED = 2SPEED

ALARMS 

(CONT)

CO2 SENS ERR

N/A

N/A

CO

2

 SENSOR ERROR

CO

2

 sensor has failed, gone out of range or become disconnected - 

check wiring then replace sensor if the alarm continues.

OA SYLK T ERR

N/A

N/A

OUTSIDE AIR S-BUS SENSOR ERROR

Outdoor air enthalpy sensor has failed or become disconnected - 

check wiring then replace sensor if the alarm continues.

OA SYLK H ERR

N/A

N/A

RA SYLK T ERR

N/A

N/A

RETURN AIR S-BUS SENSOR ERROR

Return air enthalpy sensor has failed or become disconnected - check 

wiring then replace sensor if the alarm continues.

RA SYLK H ERR

N/A

N/A

DA SYLK T ERR

N/A

N/A

DISCHARGE AIR S-BUS SENSOR ERROR

Discharge air sensor has failed or become disconnected - check 

wiring then replace sensor if the alarm continues.

OA SENS T ERR

N/A

N/A

OUTSIDE AIR TEMPERATURE SENSOR ERROR

Outdoor air temperature sensor has failed or become disconnected - 

check wiring then replace if the alarm continues.

ACT ERROR

N/A

N/A

ACTUATOR ERROR

Actuator has failed or become disconnected - check for stall, over 

voltage, under voltage and actuator count. Replace actuator if damper 

is movable and supply voltage is between 21.6 V and 26.4 V. Check 

actuator count on STATUS menu.

FREEZE ALARM

N/A

N/A

Check if outdoor temperature is below the LOW Temp Lockout on 

setpoint menu. Check if Mixed air temperature on STATUS menu is 

below the Lo Setpoint on Advanced menu. When conditions are back 

in normal range then the alarm will go away.

SHUTDOWN ACTIVE

N/A

N/A

AUX2 IN is programmed for SHUTDOWN and 24 V has been applied 

to AUX2 IN terminal.

DMP CAL RUNNING

N/A

N/A

DAMPER CALIBRATION ROUTINE RUNNING

If DCV Auto enable has been programmed, when the W7220 is 

completing a calibration on the dampers, this alarm will display. Wait 

until the calibration is completed and the alarm will go away. Must 

have OA, MA and RA sensors for DCV calibration; set up in the 

Advanced setup menu.

DA SENS ALM

N/A

N/A

DISCHARGE AIR TEMPERATURE SENSOR ALARM

Discharge air temperature is out of the range set in the ADVANCED 

SETUP Menu. Check the temperature of the discharge air.

SYS ALARM

N/A

N/A

When AUX1-O is set to SYS and there is any alarm (e.g., failed 

sensors, etc.), the AUX1-O terminal has 24 Vac out.

ACT UNDER V

N/A

N/A

ACTUATOR VOLTAGE LOW

Voltage received by actuator is above expected range.

ACT OVER V

N/A

N/A

ACTUATOR VOLTAGE HIGH

Voltage received by actuator is below expected range.

ACT STALLED

N/A

N/A

ACTUATOR STALLED

Actuator stopped before achieving commanded position.

Table 9 — 

W7220 Menu Structure* (cont)

MENU

PARAMETER

PARAMETER 

DEFAULT 

VALUE

PARAMETER 

RANGE AND 

INCREMENT

NOTES

CLO —

Compressor Lockout

ERV —

Energy Recovery Ventilator

LCD —

Liquid Crystal Display

MA

Mixed Air

MAT —

Mixed Air Temperature

N/A —

Not Applicable

OA

Outdoor Air

OAT —

Outdoor Air Temperature

OCC —

Occupied

RA

Return Air

RAT —

Return Air Temperature

RTU —

Rooftop Unit

SYS —

System

Summary of Contents for RHW036-060

Page 1: ...ors 36 COMPLETING RETURN AIR SMOKE SENSOR INSTALLATION ADDITIONAL APPLICATION DATA Step 12 Adjust Factory Installed Options 37 SMOKE DETECTORS ECONOMI ER IV OCCUPANCY SWITCH Step 13 Install Accessorie...

Page 2: ...ON AND SAFETY HAZARD Failure to follow this warning could cause personal inju ry death and or equipment damage R 410A refrigerant systems operate at higher pressures than standard R 22 systems Do not...

Page 3: ...e K voltage code models the following are not available as factory installed options Coated or copper fin coils Economizers and 2 position damper Powered convenience outlet 1 See Specification Sheet f...

Page 4: ...4 Specifications subject to change without notice 527 01 2701 00 Fig 2 RHW036 060 Unit Dimensional Drawing...

Page 5: ...527 01 2701 00 Specifications subject to change without notice 5 Fig 2 RHW036 060 Unit Dimensional Drawing cont...

Page 6: ...6 Specifications subject to change without notice 527 01 2701 00 Fig 2 RHW036 060 Unit Dimensional Drawing cont...

Page 7: ...ed ductwork at unit duct openings 6 Install outdoor air hood 7 Install condensate line trap and piping 8 Make electrical connections 9 Install other accessories FRAME MOUNTED INSTALLATION Frame mounte...

Page 8: ...BER TITLE 1041738 CURB ASY ROOF ENGINEERING MANUFACTURING ENGINEERING REQUIREMENTS SIZE DRAWING NUMBER REV T 005 Y 002 DRAFTER CHECKER D 48TC400427 B WEIGHT MMC 06 17 11 SHEET 5 OF 5 SURFACE FINISH MF...

Page 9: ...n place The red drain pan can be tightened with a 1 2 in square socket drive extension For further details see Step 10 Install External Condensate Trap and Line on page 12 Before setting the unit onto...

Page 10: ...o the flanges Insulate and weatherproof all external ductwork joints and roof or building openings with counter flashing and mastic in accordance with applicable codes Do not cover or obscure visibili...

Page 11: ...installed on the unit the hood shipped with the unit will not be used and must be discarded Save the aluminum filter for use in the power exhaust hood assembly 1 The indoor coil access panel will be...

Page 12: ...he convenience outlet s transformer primary are not factory connected Installer must connect these leads according to required operation of the conve nience outlet If an always energized convenience o...

Page 13: ...the handle Fig 18 Power Wiring Connections Field Install the NFD Shaft and Handle 1 Remove the control box access panel The NFD enclosure is located below the control box see Fig 19 2 Remove 3 cap he...

Page 14: ...wiring connections Provide a ground fault and short circuit over current protec tion device fuse or breaker per NEC Article 440 or local codes Refer to unit informative data plate for MOCP Max imum O...

Page 15: ...t access is through the unit s control box access panel See Fig 21 The primary leads to the convenience outlet transformer are not factory connected Selection of primary power source is a customer opt...

Page 16: ...does not get into the building or conduit in the interim Check tightness of connector lock nuts before connecting electrical conduits Field supplied and field installed liquid tight conduit connector...

Page 17: ...nal features which might require addi tional conductors in the cable For wire runs up to 50 ft 15 m use no 18 AWG Ameri can Wire Gage insulated wire 35 C 95 F minimum For 50 to 75 ft 15 to 23 m use no...

Page 18: ...delay feature user selectable The DFB also provides an indoor fan off delay feature user selectable See Fig 29 for board arrangement The DFB is located in the main control box of the RHW unit see Fig...

Page 19: ...1 Heating cycle for an Emergency Heating sequence compressors are off and only the elec tric heaters are energized and also during the Defrost cycle to eliminate a cold blow condition in the space De...

Page 20: ...value exceeds 60 A unit mounted supplementary fuses are required for each heater circuit These fuses are included in accessory Single Point Boxes with power distribution and fuse blocks The single poi...

Page 21: ...e left of the Heater module Connect the VIO lead from Heater circuit 1 to terminal TB4 1 For 2 stage heating connect the VIO lead from Heater circuit 2 to terminal TB4 2 See Fig 36 Fig 36 Accessory El...

Page 22: ...22 Specifications subject to change without notice 527 01 2701 00 Fig 37 Typical Control Wiring Diagram Electro Mechanical with W7220 RHW036 060 208 230 3 60 Unit Shown...

Page 23: ...527 01 2701 00 Specifications subject to change without notice 23 Fig 38 Typical Control Wiring Diagram Electro Mechanical with W7220 RHW036 060 460 575 3 60 Unit Shown...

Page 24: ...24 Specifications subject to change without notice 24 Fig 39 Typical RHW036 060 Power Wiring Diagram 208 230 3 60 Unit Shown...

Page 25: ...527 01 2701 00 Specifications subject to change without notice 25 Fig 40 Typical RHW036 060 Power Wiring Diagram 460 575 3 60 Unit Shown...

Page 26: ...vailable with bus sensors User Interface Provides status for normal operation setup parameters checkout tests and alarm and error conditions with a 2 line 16 character LCD display and four button keyp...

Page 27: ...ity Insensitive Connection Bottom Left Terminal Block IAQ 2 10 2 10 vdc Air Quality Sensor Input e g CO2 sensor IAQ COM COM Air Quality Sensor Common IAQ 24V 24 vac Air Quality Sensor 24 vac Source AC...

Page 28: ...Enter button to display the first item in the currently displayed menu Press the Menu Up Exit button to exit a menu s item and return to the list of menus Fig 45 W7220 Controller Navigation Buttons To...

Page 29: ...d stage cooling ON 24 Vac on terminal Y2 I OFF 0 Vac on terminal Y2 I COOL Y2 OUT OFF ON OFF SECOND STAGE COOLING RELAY OUTPUT Cool Stage 2 Relay Output to mechanical cooling Y2 OUT terminal MA TEMP _...

Page 30: ...y sensor option Enthalpy boundary curves for economizing using single enthalpy DCV SET 1100ppm 500 to 2000 ppm increment by 100 DEMAND CONTROLLED VENTILATION SETPOINT Displays only if CO2 sensor is co...

Page 31: ...ivate power exhaust EXH2 H SET 75 0 to 100 EXHAUST FAN 2 SETPOINT AT HIGH SPEED on 2 speed or 3 speed with 1 heat and 2 cool Based on economizer OA damper position to activate power exhaust SYSTEM SET...

Page 32: ...perator to adjust for an out of calibration temperature sensor OA H CAL 0 RH 10 RH OUTSIDE AIR HUMIDITY CALIBRATION Allows for operator to adjust for an out of calibration humidity sensor RA T CAL 0 0...

Page 33: ...onnected check wiring then replace sensor if the alarm continues RA SYLK H ERR N A N A DA SYLK T ERR N A N A DISCHARGE AIR S BUS SENSOR ERROR Discharge air sensor has failed or become disconnected che...

Page 34: ...OA temperature and humidity input from the OA enthalpy sensor When the OA temperature OA humidity and OA dew point are all below the selected boundary the economizer sets the economizing mode to YES e...

Page 35: ...YPE 2SPEED With stage 3 delay STG3 DLY in Advanced setup COOL Y2 OUT will be turned ON after the delay time specified N A Not applicable STATE FAN SPEED OCC Low Y1 Low Y2 High W High INPUTS OUTPUTS DE...

Page 36: ...has been no keypad activity for at least 5 minutes the Alarms menu dis plays and cycles through the active alarms You can also navigate to the Alarms menu at any time Clearing Alarms Once the alarm h...

Page 37: ...utdown terminals on the UCB and then attach the wiring harness from the smoke detector ECONOMI ER IV OCCUPANCY SWITCH See Fig 49 on page 38 for general EconoMi er IV wiring External occupancy control...

Page 38: ...a multimeter to the Vdc terminals on the UCB 4 Set the Range Switch to either A B or C per the Switch Range table 5 Using a straight blade screwdriver turn the Vdc con trol dial to fine tune the Vdc...

Page 39: ...5 2250 2375 2500 0 1 0 4 6 2 6 5 6 8 7 1 7 4 7 7 8 0 8 4 8 7 0 1 0 6 6 9 7 1 7 4 7 7 7 9 8 2 8 5 8 8 0 1 0 8 7 5 7 7 8 0 8 2 8 5 8 7 9 0 0 1 1 0 8 1 8 3 8 5 8 7 9 0 0 1 1 2 8 6 8 8 9 0 9 2 0 1 1 4 9 1...

Page 40: ...tion operation and converging coil circuits during the condenser function operation Fig 52 Typical Piping Schematic Table 14 Cooling Mode each circuit COMPONENT STATUS POSITION Reversing Valve Energiz...

Page 41: ......

Page 42: ...Specifications are subject to change without notice 527 01 2701 00 2020 Carrier Lewisburg TN 37091 USA Replaces New...

Page 43: ...e of obstructions and rotor spins freely Y N _____ Verify that scroll compressors are rotating in the correct direction Y N _____ Verify installation of thermostat Y N _____ III START UP ELECTRICAL Su...

Page 44: ...CUT ALONG D OTTED LINE CUT ALONG DOTTED LINE CL 2 Specifications are subject to change without notice 7 2020 527 01 2701 00 2020 Carrier Lewisburg TN 37091 USA Replaces New...

Reviews: