Table 7 — HH57AC081 Sensor Wiring Terminations
Use Fig. 43 and Table 8 to set the DIP switches for the de
-
sired use of the sensor.
Table 8 — HH57AC081 Sensor DIP Switch
NOTE: When an S-Bus sensor is connected to an existing
network, it will take 60 minutes for the network to recognize
and auto-configure itself to use the new sensor.
During the 60-minute setup period, no alarms for sensor
failures (except SAT) will be issued and no economizing
function will be available.
CO
2
SENSOR WIRING
When using a CO
2
sensor the black and brown common
wires are internally connected and only one is connected to
“IAQ COM” on the W7220. Use the power from the W7220
to power the CO
2
sensor OR make sure the ground for the
power supplies are common. See Fig. 44 for CO
2
sensor
wiring.
Fig. 44 — CO
2
Sensor Wiring
INTERFACE OVERVIEW
This section describes how to use the EconoMi$er
®
X user
interface for:
• Keypad and menu navigation
• Settings and parameter changes
• Menu structure and selection
User Interface
The user interface consists of a 2-line LCD display and a 4-
button keypad on the front of the economizer controller.
Keypad
Use the four navigation buttons (see Fig. 45) to scroll
through the menus and menu items, select menu items,
and to change parameter and configuration settings.
To use the keypad when working with menus:
• Press the ▲ (Up arrow) button to move to the previ
-
ous menu.
• Press the ▼ (Down arrow) button to move to the next
menu.
• Press the
(Enter) button to display the first item in
the currently displayed menu.
• Press the
(Menu Up/Exit) button to exit a menu’s
item and return to the list of menus.
Fig. 45 — W7220 Controller Navigation Buttons
To use the keypad when working with Setpoints, System
and Advanced Settings, Checkout tests and Alarms:
1. Navigate to the desired menu.
2. Press the
(Enter) button to display the first item in
the currently displayed menu.
3. Use the ▲ and ▼ buttons to scroll to the desired
parameter.
4. Press the
(Enter) button to display the value of
the currently displayed item.
5. Press the ▲ button to increase (change) the dis
-
played parameter value.
6. Press the ▼ button to decrease (change) the dis
-
played parameter value.
NOTE: When values are displayed, pressing and holding
the ▲or ▼ button causes the display to automatically in
-
crement or decrement.
1. Press the
(Enter) button to accept the displayed
value and store it in nonvolatile RAM. “CHANGE
STORED” displays.
2. Press the
(Enter) button to return to the current
menu parameter.
3. Press the
(Menu Up/Exit) button to return to the
previous menu.
Menu Structure
Table 9 illustrates the complete hierarchy of menus and pa
-
rameters for the EconoMi$er
®
X system.
The Menus in display order are:
• STATUS
• SETPOINTS
• SYSTEM SETUP
• ADVANCED SETUP
• CHECKOUT
• ALARMS
TERMINAL
TYPE
DESCRIPTION
NUMBER
LABEL
1
S-BUS
S-BUS
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
2
S-BUS
S-BUS
S-BUS
Communications
(Enthalpy Control
Sensor Bus)
USE
DIP SWITCH POSITIONS FOR SWITCHES 1, 2, AND 3
1
2
3
DA
OFF
ON
OFF
RA
ON
OFF
OFF
OA
OFF
OFF
OFF
CO
2
SENSOR
24V
ANALOG
OUT
L1
(HOT)
L2
RED
BLACK
YELLOW
BROWN
ORANGE
GREEN
+
–
POWER SUPPLY. PROVIDE DISCONNECT
MEANS AND OVERLOAD PROTECTION
AS REQUIRED.
1
1