26
Table 9 – Cooling Charging Chart
Superheat charging table is derived from optimum performance point. (95
_
F [35
_
C] outdoor ambient and (80
_
F [27
_
C] dry bulb; 67
_
F [19
_
C] wet bulb indoor
condition.) Where a dash(--- ---) appears do not attempt to check charge or charge unit under these conditions using the superheat method. (Weigh in method
should be used.)
A150625
To properly check or adjust charge, conditions must be favorable for subcooling charging. Favorable conditions exist when the outdoor temperature is between
75
_
F to 115
_
F (24
_
C and 46
_
C), and the indoor temperature is between 70
_
F and 80
_
F (21
_
C and 27
_
C). Follow the procedure above.
A150626
PY4G
Summary of Contents for PY4G B Series
Page 4: ...4 A190121 Fig 3 24 36 Unit Dimensions PY4G ...
Page 5: ...5 A190122 Fig 4 42 60 Unit Dimensions PY4G ...
Page 16: ...16 A150502 Fig 14 208 230 1 60 Connection Wiring Diagram PY4G ...
Page 17: ...17 A150510 Fig 14 Cont 208 230 1 60 Ladder Wiring Diagram PY4G ...
Page 18: ...18 A150508 Fig 15 208 230 3 60 Connection Wiring Diagram PY4G ...
Page 19: ...19 A150511 Fig 15 Cont 208 230 3 60 Ladder Wiring Diagram PY4G ...
Page 20: ...20 A150509 Fig 16 460 3 60 Connection Wiring Diagram PY4G ...
Page 21: ...21 A150512 Fig 16 Cont 460 3 60 Ladder Wiring Diagram PY4G ...