background image

22

Normal Operation

An LED (light--emitting diode) indicator is provided on the

integrated gas unit controller (IGC) to monitor operation. The IGC
is located by removing the control access panel (see Fig. 20).

During normal operation, the LED is continuously on (See Table 7
for error codes).

Airflow and Temperature Rise

The heating section for each size unit is designed and approved for

heating operation within the temperature--rise range stamped on the
unit rating plate.
Table 10, 11 and 12 show the approved temperature rise range for
each heating input, and the air delivery cfm at various temperature

rises for a given external static pressure. The heating operation

airflow must produce a temperature rise that falls within the
approved range. For single phase units only, “High” blower speed

is for high static cooling only and must not be used for gas heating
speed.
Refer to Indoor Airflow and Airflow Adjustments section to adjust

heating airflow when required.

Heating Sequence of Operation (Single Phase Models)

(See Fig. 14 and unit wiring label)

On a call for heating, terminal W of the thermostat is energized,
starting the induced-draft motor for a 5 second pre-purge. When

the pressure switch senses that the induced-draft motor is moving

sufficient combustion air, the burner sequence begins.

This

function is controlled by the integrated gas unit controller (IGC).

The indoor (evaporator) –fan motor is energized 30 seconds after
flame is established. When the thermostat is satisfied and W is

de-energized, the burners stop firing and the indoor (evaporator)

fan motor shuts off after a 90 second time-off delay. Please note
that the IGC has the capability to automatically reduce the indoor

fan motor on delay and increase the indoor fan motor off delay in
the event of high duct static and/or a partially-clogged filter.

Heating Sequence of Operation (3 Phase Models)

(See Fig. 15 and 16 and unit wiring label.)
On a call for heating, terminal W of the thermostat is energized,
starting the induced--draft motor. When the pressure switch senses

that the induced--draft motor is moving sufficient combustion air,
the burner sequence begins. This function is performed by the

integrated gas unit controller (IGC). The indoor (evaporator)--fan

motor is energized 45 sec after flame is established. When the
thermostat is satisfied and W is de--energized, the burners stop

firing and the indoor (evaporator) fan motor shuts off after a
45--sec time--off delay. Please note that the IGC has the capability

to automatically reduce the indoor fan motor on delay and increase

the indoor fan motor off delay in the event of high duct static
and/or partially--clogged filter.

Limit Switches

Normally closed limit switch (LS) completes the control circuit.

Should the leaving--air temperature rise above the maximum
allowable temperature, the limit switch opens and the control

circuit “breaks.” Any interruption in the control circuit instantly
closes the gas valve and stops gas flow to the burners. The blower

motor continues to run until LS resets.
When the air temperature at the limit switch drops to the

low--temperature setting of the limit switch, the switch closes and

completes the control circuit. The direct--spark ignition system
cycles and the unit returns to normal heating operation.

Table 7 – LED Indications

STATUS CODE

LED INDICATION

Normal Operation

2

On

No Power or Hardware Failure

Off

Check fuse, low voltage circuit

1 Flash

Limit Switch Fault

2 Flashes

Flame Sense Fault

3 Flashes

Four Consecutive Limit Switch Faults

4 Flashes

Ignition Lockout Fault

5 Flashes

Pressure Switch Fault

6 Flashes

Rollout Switch Fault

7 Flashes

Internal Control Fault

8 Flashes

Temporary 1 hr auto reset

1

9 Flashes

NOTES:

1.This code indicates an internal processor fault that will reset itself in one

hr. Fault can be caused by stray RF signals in the structure or nearby. This

is a UL requirement.

2. LED indicates acceptable operation. Do not change ignition control

board.

3. When W is energized the burners will remain on for a minimum of 60 sec.

4. If more than one error code exists they will be displayed on the LED in

sequence.

Rollout Switch

The function of the rollout switch is to close the main gas valve in

the event of flame rollout. The switch is located above the main
burners. When the temperature at the rollout switch reaches the

maximum allowable temperature, the control circuit trips, closing
the gas valve and stopping gas flow to the burners. The indoor

(evaporator) fan motor (IFM) and induced draft motor continue to
run until switch is reset. The IGC LED will display FAULT CODE

7.

Step 3 — Start--up Cooling and Make Adjust-

ments

Complete the required procedures given in the Pre--Start--Up
section before starting the unit. Do not jumper any safety devices

when operating the unit. Do not operate the compressor when the
outdoor temperature is below 40

F (4.4

C) (unless accessory

low--ambient kit is installed). Do not rapid--cycle the compressor.

Allow 5 minutes between on cycles to prevent compressor damage.

Checking Cooling Control Operation

Start and check the unit for proper cooling control operation as

follows:

1. Place room thermostat SYSTEM switch in OFF position.

Observe that blower motor starts when FAN switch is
placed in ON position and shuts down when FAN switch is

placed in AUTO position.

2. Place SYSTEM switch in COOL position and FAN switch

in AUTO position. Set cooling control below room
temperature. Observe that compressor, condenser fan, and
evaporator blower motors start. Observe that cooling cycle

shuts down when control setting is satisfied. The evaporator
fan will continue to run for 90 sec.

3. When using an auto--changeover room thermostat, place

both SYSTEM and FAN switches in AUTO positions.

Observe that unit operates in Heating mode when
temperature control is set to call for heating (above room
temperature) and operates in Cooling mode when

temperature control is set to call for cooling (below room
temperature).

IMPORTANT

: Three--phase, scroll compressors are direction

oriented. Unit must be checked to ensure proper compressor
3--phase power lead orientation. If not corrected within 5 minutes,
the internal protector will shut off the compressor. The 3--phase
power leads to the unit must be reversed to correct rotation. When
turning backwards, the difference between compressor suction and
discharge pressures will be minimal.

PY4G

Summary of Contents for PY4G B Series

Page 1: ...nput 13 Adjust Gas Input 14 Check Burner Flame 15 Normal Operation 22 Airflow and Temperature Rise 22 Heating Sequence of Operation 22 Limit Switches 22 Rollout Switch 22 Start Up Cooling Make Adjustments 22 Checking Cooling Control Operation 22 Checking Adjusting Refrigerant Charge 23 Indoor Airflow and Airflow Adjustments 23 Cooling Sequence of Operation 24 A09183 Fig 1 Unit PY4G Low NOx Model A...

Page 2: ...NG AND INSTALLATION Step 1 Check Equipment Identify Unit The unit model number and serial number are stamped on the unit information plate Check this information against shipping papers Inspect Shipment Inspect for shipping damage before removing packaging materials If unit appears to be damaged or is torn loose from its anchorage have it examined by transportation inspectors before removal Forwar...

Page 3: ... unit if it has been under water Step 5 Rig and Place Unit Rigging and handling of this equipment can be hazardous for many reasons due to the installation location roofs elevated structures etc Only trained qualified crane operators and ground support staff should handle and install this equipment When working with this equipment observe precautions in the literature on tags stickers and labels a...

Page 4: ...4 A190121 Fig 3 24 36 Unit Dimensions PY4G ...

Page 5: ...5 A190122 Fig 4 42 60 Unit Dimensions PY4G ...

Page 6: ... 30 6 778 46 1 1170 Large CPRFCURB013B00 14 356 14 356 43 9 1116 42 2 1072 Part Number CPRCURB011B00 can be used on both small and large basepan units The cross supports must be located based on whether the unit is a small basepan or a large basepan NOTES 1 Roof curb must be set up for unit being installed 2 Seal strip must be applied as required to unit being installed 3 Roof curb is made of 16 g...

Page 7: ...p Rpm 2500 24 609 6 1 10 810 2500 24 609 6 1 10 810 2700 24 609 6 1 10 810 2700 24 609 6 1 10 810 3200 24 609 6 1 5 810 3200 24 609 6 1 5 810 3600 26 660 4 1 5 810 3600 26 660 4 1 5 810 INDOOR COIL Rows Fins in Face Area sq ft 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 3 7 3 17 4 7 3 17 4 7 INDOOR BLOWER Nominal Cooling Airflow Cfm Size in Size mm Motor HP RPM 800 800 1000 1000 1150 1150 13...

Page 8: ...ns for correct filter sizes and quantity Table 2 Maximum Gas Flow Capacity NOMINAL IRON PIPE SIZE IN INTERNAL DIAMETER IN LENGTH OF PIPE FT m 10 3 20 6 30 9 40 12 50 15 60 18 70 21 80 24 90 27 100 30 125 38 150 46 175 53 200 61 1 2 622 175 120 97 82 73 66 61 57 53 50 44 40 3 4 824 360 250 200 170 151 138 125 118 110 103 93 84 77 72 1 1 049 680 465 375 320 285 260 240 220 205 195 175 160 145 135 1 ...

Page 9: ...m of the gas supply connection to the gas valve When installing the gas supply line observe local codes pertaining to gas pipe installations Refer to the NFPA 54 ANSI Z223 1 latest edition in Canada CAN CGA B149 1 NOTE In the state of Massachusetts 1 Gas supply connections MUST be performed by a licensed plumber or gas fitter 2 When flexible connectors are used the maximum length shall not exceed ...

Page 10: ...ult in property damage Collect ALL screws that were removed Do not leave screws on rooftop as permanent damage to the roof may occur CAUTION 3 For single phase models only on the discharge side only remove the insulation covering the downshot plastic knockout Insulation is held in place with aluminum tape Please note that large chassis units have 2 pieces of insula tion and only the piece over the...

Page 11: ...ate electrical service with a field supplied waterproof disconnect switch mounted at or within sight from the unit Refer to the unit rating plate NEC and local codes for maximum fuse circuit breaker size and minimum circuit amps ampacity for wire sizing The field supplied disconnect switch box may be mounted on the unit over the high voltage inlet hole when the standard power and low voltage entry...

Page 12: ...ilure to follow this warning could result in personal injury or death 1 Follow recognized safety practices and wear protective goggles when checking or servicing refrigerant system 2 Do not operate compressor or provide any electric power to unit unless compressor plug is in place and secured 3 Do not remove compressor plug until all electrical sources are disconnected and tagged 4 Relieve and rec...

Page 13: ...ny safety devices when operating the unit Make sure that burner orifices are properly aligned Unstable operation my occur when the burner orifices in the manifold are misaligned Follow the lighting instructions on the heating section operation label located on the inside of the control access panel to start the heating section NOTE Make sure that gas supply has been purged and that all gas piping ...

Page 14: ... determined by measuring the gas flow at the meter or by measuring the manifold pressure Measuring the gas flow at the meter is recommended for natural gas units The manifold pressure must be measured to determine the input of propane gas units Measure Gas Flow Natural Gas Units Minor adjustment to the gas flow can be made by changing the manifold pressure The manifold pressure must be maintained ...

Page 15: ...udes from 2001 to 4500 ft 611 to 1372 m above sea level must be derated by 10 by an authorized gas conversion station or dealer For Canadian Installations from 2000 to 4500 ft 610 1372 m use U S A column 2001 to 3000 ft 611 to 914 m Table 5 High Altitude Compensation Natural Gas Three Phase Nameplate Input Btu hr Rated Heating Input Btu hr Natural Gas at Installation Altitude Above Sea Level U S A...

Page 16: ...16 A150502 Fig 14 208 230 1 60 Connection Wiring Diagram PY4G ...

Page 17: ...17 A150510 Fig 14 Cont 208 230 1 60 Ladder Wiring Diagram PY4G ...

Page 18: ...18 A150508 Fig 15 208 230 3 60 Connection Wiring Diagram PY4G ...

Page 19: ...19 A150511 Fig 15 Cont 208 230 3 60 Ladder Wiring Diagram PY4G ...

Page 20: ...20 A150509 Fig 16 460 3 60 Connection Wiring Diagram PY4G ...

Page 21: ...21 A150512 Fig 16 Cont 460 3 60 Ladder Wiring Diagram PY4G ...

Page 22: ...to the low temperature setting of the limit switch the switch closes and completes the control circuit The direct spark ignition system cycles and the unit returns to normal heating operation Table 7 LED Indications STATUS CODE LED INDICATION Normal Operation2 On No Power or Hardware Failure Off Check fuse low voltage circuit 1 Flash Limit Switch Fault 2 Flashes Flame Sense Fault 3 Flashes Four Co...

Page 23: ...id line temperature See Table 9 6 Compare actual liquid line temperature with desired liquid line temperature Using a tolerance of 2 F 1 1 C add refrigerant if actual temperature is more than 2 F 1 1 C higher than proper liquid line temperature or remove refrigerant if actual temperature is more than 2 F 1 1 C lower than required liquid line temperature NOTE If the problem causing the inaccurate r...

Page 24: ... LOW terminal on the interface fan board IFB See Fig 18 2 Determine correct normal cooling fan speed for unit and application Add the wet coil pressure drop in Table 14 to the system static to determine the correct cooling airflow speed in Table 11 or 12 that will deliver the nominal cooling airflow as listed in Table 1 for each size 3 Remove the vinyl cap off of the desired speed tap wire Refer t...

Page 25: ...GC Board COM LOW HIGH GAS HEAT Q1 R1L C8 RL3 Q3 DCR QCR QC1 G1 G2 A7 D4 D6 C2 OILL R9 AB A15 C4 C9 C0 R4 RL4 C7 R2 R3 R5 R6 QCB Y Y R U C 24VAC JW1 P2 P1 W2 Y2 Y1 Y DH G C R SSTZ 8 P3 SDL 24VAC R CDM C F1 QC6 QC7 QC4 QC3 K2 K1 D2 RI0 RI2 JM6 RI DL JM5 U1 C3 D3 D5 JW3 JW2 JW4 JW7 3 AMP C A09058 Fig 18 Interface Fan Board IFB PY4G ...

Page 26: ...attempt to check charge or charge unit under these conditions using the superheat method Weigh in method should be used A150625 To properly check or adjust charge conditions must be favorable for subcooling charging Favorable conditions exist when the outdoor temperature is between 75_F to 115_F 24_C and 46_C and the indoor temperature is between 70_F and 80_F 21_C and 27_C Follow the procedure ab...

Page 27: ...x BHP 0 09 0 10 0 10 0 11 x x x x x x Gas Heat Rise o F NA NA NA NA NA NA NA NA NA NA Gas Heat Rise o C NA NA NA NA NA NA NA NA NA NA Med Low Pink Alternate Cooling Alternate Heating CFM 840 759 677 600 505 411 293 x x x BHP 0 14 0 15 0 16 0 16 0 17 0 17 0 18 x x x Gas Heat Rise o F 53 NA NA NA NA NA NA NA NA NA Gas Heat Rise o C 30 NA NA NA NA NA NA NA NA NA Medium 2 Red Cooling Alternate Heating...

Page 28: ...54 338 x x x x x x BHP 0 09 0 10 0 10 0 11 x x x x x x Gas Heat Rise o F NA NA NA NA NA NA NA NA NA NA Gas Heat Rise o C NA NA NA NA NA NA NA NA NA NA Med Low Pink Alternate Cooling Alternate Heating CFM 840 759 677 600 505 411 293 x x x BHP 0 14 0 15 0 16 0 16 0 17 0 17 0 18 x x x Gas Heat Rise o F 53 NA NA NA NA NA NA NA NA NA Gas Heat Rise o C 30 NA NA NA NA NA NA NA NA NA Medium 2 Red Cooling ...

Page 29: ...8 0 08 0 09 0 09 0 10 0 10 0 11 x x x Gas Heat Rise o F NA NA NA NA NA NA NA NA NA NA Gas Heat Rise o C NA NA NA NA NA NA NA NA NA NA Med Low Pink Alternate Cooling Alternate Heating CFM 1144 1105 1066 1026 984 941 895 850 806 763 BHP 0 28 0 28 0 29 0 30 0 31 0 31 0 32 0 33 0 34 0 34 Gas Heat Rise o F 58 61 63 65 NA NA NA NA NA NA Gas Heat Rise o C 32 34 35 36 NA NA NA NA NA NA Medium 2 Red Coolin...

Page 30: ...77 717 650 575 527 466 419 BHP 0 13 0 13 0 14 0 14 0 15 0 16 0 17 0 18 0 19 0 20 Gas Heat Rise o F NA NA NA NA NA NA NA NA NA NA Gas Heat Rise o C NA NA NA NA NA NA NA NA NA NA Med Low Pink CFM 1016 950 902 842 783 721 655 590 541 480 BHP 0 13 0 14 0 15 0 16 0 17 0 18 0 19 0 20 0 21 0 22 Gas Heat Rise o F NA NA NA NA NA NA NA NA NA NA Gas Heat Rise o C NA NA NA NA NA NA NA NA NA NA Medium 2 Red Co...

Page 31: ...0 07 0 07 0 08 0 08 0 09 x x x x Gas Heat Rise o F NA NA NA NA NA NA NA NA NA NA Gas Heat Rise o C NA NA NA NA NA NA NA NA NA NA Med Low Pink Alternate Cooling Alternate Heating CFM 1430 1386 1347 1302 1258 1208 1160 1114 1065 1014 BHP 0 26 0 27 0 28 0 29 0 30 0 30 0 32 0 33 0 34 0 35 Gas Heat Rise o F 60 NA NA NA NA NA NA NA NA NA Gas Heat Rise o C 34 NA NA NA NA NA NA NA NA NA Medium 2 Red Cooli...

Page 32: ... 306 x BHP 0 09 0 10 0 10 0 11 0 12 0 12 0 13 0 14 0 14 x Gas Heat Rise o F NA NA NA NA NA NA NA NA NA NA Gas Heat Rise o C NA NA NA NA NA NA NA NA NA NA Med Low 1 Pink Heating CFM 1403 1361 1320 1276 1236 1192 1145 1099 1054 1012 BHP 0 28 0 29 0 30 0 31 0 31 0 33 0 34 0 35 0 36 0 37 Gas Heat Rise o F 48 50 51 53 55 57 59 62 64 NA Gas Heat Rise o C 27 28 28 29 30 32 33 34 36 NA Medium 2 Red Coolin...

Page 33: ... 360 2 305 8 x BHP 0 09 0 10 0 10 0 11 0 12 0 12 0 13 0 14 0 14 x Gas Heat Rise o F NA NA NA NA NA NA NA NA NA NA Gas Heat Rise o C NA NA NA NA NA NA NA NA NA NA Med Low Pink CFM 1403 1361 1320 1276 1236 1192 1145 1099 1054 1012 BHP 0 28 0 29 0 30 0 31 0 31 0 33 0 34 0 35 0 36 0 37 Rise o F NA NA NA NA NA NA NA NA NA NA Rise o C NA NA NA NA NA NA NA NA NA NA Medium 2 Red Cooling Alternate Heating ...

Page 34: ...6 39 42 45 Heating Rise o C 16 17 18 19 20 20 22 23 25 High Black CFM 1560 1491 1416 1337 1255 1233 1160 1082 998 Heating Rise o F 28 30 31 33 35 36 38 41 44 Heating Rise o C 16 16 17 18 19 20 21 23 24 36090 35 65 o F 19 36 o C Low Blue CFM 979 912 859 789 731 654 556 454 374 Heating Rise o F NA NA NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA Med Low Pink CFM 1136 1080 1015 957...

Page 35: ... 44 47 50 Heating Rise o C 18 19 19 20 22 23 24 26 28 High Black CFM 1472 1401 1326 1251 1275 1198 1139 1085 1023 Heating Rise o F 29 31 33 35 34 36 38 40 42 Heating Rise o C 16 17 18 19 19 20 21 22 24 42090 35 65 o F 19 36 o C Low Blue CFM 952 882 806 746 671 605 530 551 486 Heating Rise o F NA NA NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA Med Low Pink CFM 1002 936 875 821 7...

Page 36: ... 35 36 37 Heating Rise o C NA NA NA NA NA NA 20 20 21 High Black CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803 Heating Rise o F NA NA NA NA NA NA NA 35 37 Heating Rise o C NA NA NA NA NA NA NA 20 21 48115 30 60 o F 17 33 o C Low Blue CFM 1402 1351 1311 1263 1224 1172 1136 1080 1041 Heating Rise o F NA NA NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA Med Low Pink CFM 1457 1404...

Page 37: ... 50 51 53 Heating Rise o C 25 25 26 26 27 27 28 28 29 High Black CFM 2344 2306 2259 2203 2141 2070 1991 1902 1803 Heating Rise o F 41 41 42 43 44 46 48 50 53 Heating Rise o C 23 23 23 24 25 26 27 28 29 60090 35 65 o F 19 36 o C Low 1 Blue CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027 Heating Rise o F 46 48 50 52 54 56 59 62 65 Heating Rise o C 26 27 28 29 30 31 33 35 36 Med Low Pink CFM 1678 16...

Page 38: ...o F 19 36 o C Low Blue CFM 1445 1389 1341 1281 1236 1189 1139 1072 1027 Heating Rise o F NA NA NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA Med Low Pink CFM 1678 1635 1602 1558 1513 1474 1438 1404 1349 Heating Rise o F 57 58 59 61 63 65 NA NA NA Heating Rise o C 32 32 33 34 35 36 NA NA NA Medium 2 Red CFM 1962 1915 1880 1843 1794 1753 1711 1675 1628 Heating Rise o F 49 50 51 52...

Page 39: ... 39 41 43 46 48 51 54 NA NA NA Heating Rise o C 22 23 24 26 27 28 30 NA NA NA Medium 2 Red CFM 1208 1144 1091 1025 964 902 886 830 746 663 WATTS 345 350 358 366 373 377 390 396 407 410 BHP 0 37 0 38 0 38 0 39 0 40 0 40 0 42 0 42 0 44 0 44 Heating Rise o F 36 38 40 43 46 49 50 53 NA NA Heating Rise o C 20 21 22 24 25 27 28 29 NA NA Med High Orange CFM 1495 1439 1376 1303 1221 1207 1137 1052 981 894...

Page 40: ... 61 NA NA NA NA NA NA NA NA Heating Rise o C 32 34 NA NA NA NA NA NA NA NA Medium 2 Red CFM 1208 1144 1091 1025 964 902 886 830 746 663 WATTS 345 350 358 366 373 377 390 396 407 410 BHP 0 37 0 38 0 38 0 39 0 40 0 40 0 42 0 42 0 44 0 44 Heating Rise o F 54 58 60 64 NA NA NA NA NA NA Heating Rise o C 30 32 34 36 NA NA NA NA NA NA Med High 1 Orange CFM 1495 1439 1376 1303 1221 1207 1137 1052 981 894 ...

Page 41: ... F 43 46 49 53 NA NA NA NA NA NA Heating Rise o C 24 26 27 29 NA NA NA NA NA NA Medium Red CFM 1255 1210 1145 1074 1008 940 878 895 838 785 WATTS 249 272 284 292 305 319 320 329 336 347 BHP 0 27 0 29 0 30 0 31 0 33 0 34 0 34 0 35 0 36 0 37 Heating Rise o F 35 36 38 40 43 46 49 48 52 55 Heating Rise o C 19 20 21 22 24 26 27 27 29 31 Med High 2 Orange CFM 1335 1267 1246 1176 1109 1049 988 926 872 89...

Page 42: ... NA NA NA NA NA NA NA NA NA NA Heating Rise o C NA NA NA NA NA NA NA NA NA NA Medium 1 Red CFM 1255 1210 1145 1074 1008 940 878 895 838 785 WATTS 249 272 284 292 305 319 320 329 336 347 BHP 0 27 0 29 0 30 0 31 0 33 0 34 0 34 0 35 0 36 0 37 Heating Rise o F 53 55 58 62 NA NA NA NA NA NA Heating Rise o C 30 31 32 35 NA NA NA NA NA NA Med High 2 Orange CFM 1335 1267 1246 1176 1109 1049 988 926 872 89...

Page 43: ...e o F 43 44 46 47 48 50 51 53 55 57 Heating Rise o C 24 25 25 26 27 28 29 30 30 32 Medium 2 Red CFM 1861 1822 1786 1758 1716 1688 1660 1619 1583 1539 WATTS 400 417 426 441 452 467 482 492 507 519 BHP 0 43 0 45 0 46 0 47 0 48 0 50 0 52 0 53 0 54 0 56 Heating Rise o F 36 37 37 38 39 40 40 41 42 43 Heating Rise o C 20 20 21 21 22 22 22 23 23 24 Med High Orange CFM 2319 2291 2255 2230 2193 2166 2118 2...

Page 44: ...o F 55 56 58 59 NA NA NA NA NA NA Heating Rise o C 30 31 32 33 NA NA NA NA NA NA Medium 2 Red CFM 1861 1822 1786 1758 1716 1688 1660 1619 1583 1539 WATTS 400 417 426 441 452 467 482 492 507 519 BHP 0 43 0 45 0 46 0 47 0 48 0 50 0 52 0 53 0 54 0 56 Heating Rise o F 46 47 48 48 50 50 51 53 54 55 Heating Rise o C 25 26 26 27 28 28 29 29 30 31 Med High 1 Orange CFM 2319 2291 2255 2230 2193 2166 2118 2...

Page 45: ...o F 61 63 65 NA NA NA NA NA NA NA Heating Rise o C 34 35 36 NA NA NA NA NA NA NA Medium 2 Red CFM 1861 1822 1786 1758 1716 1688 1660 1619 1583 1539 WATTS 400 417 426 441 452 467 482 492 507 519 BHP 0 43 0 45 0 46 0 47 0 48 0 50 0 52 0 53 0 54 0 56 Heating Rise o F 51 52 53 54 55 56 57 59 60 62 Heating Rise o C 28 29 30 30 31 31 32 33 33 34 Med High 1 Orange CFM 2319 2291 2255 2230 2193 2166 2118 2...

Page 46: ...e o F 36 37 38 39 40 41 41 42 44 45 Heating Rise o C 20 21 21 22 22 23 23 24 24 25 Medium 2 Red CFM 1944 1913 1872 1838 1801 1771 1731 1698 1655 1613 WATTS 486 501 511 529 537 554 565 578 595 603 BHP 0 52 0 54 0 55 0 57 0 58 0 59 0 61 0 62 0 64 0 65 Heating Rise o F 34 35 36 36 37 38 39 39 40 41 Heating Rise o C 19 19 20 20 21 21 21 22 22 23 Med High Orange CFM 2178 2148 2105 2073 2036 2002 1967 1...

Page 47: ...o F 46 47 48 49 50 52 53 54 56 58 Heating Rise o C 26 26 27 27 28 29 29 30 31 32 Medium 2 Red CFM 1944 1913 1872 1838 1801 1771 1731 1698 1655 1613 WATTS 486 501 511 529 537 554 565 578 595 603 BHP 0 52 0 54 0 55 0 57 0 58 0 59 0 61 0 62 0 64 0 65 Heating Rise o F 44 45 46 46 47 48 49 50 51 53 Heating Rise o C 24 25 25 26 26 27 27 28 29 29 Med High 1 Orange CFM 2178 2148 2105 2073 2036 2002 1967 1...

Page 48: ... 57 0 58 0 59 0 61 0 62 0 64 0 65 Heating Rise o F 49 50 51 52 53 54 55 56 58 59 Heating Rise o C 27 28 28 29 29 30 31 31 32 33 Med High 1 Orange CFM 2178 2148 2105 2073 2036 2002 1967 1919 1845 1751 WATTS 674 691 703 717 733 743 758 754 734 701 BHP 0 72 0 74 0 75 0 77 0 79 0 80 0 81 0 81 0 79 0 75 Heating Rise o F 44 44 45 46 47 48 48 50 52 54 Heating Rise o C 24 25 25 26 26 26 27 28 29 30 High B...

Page 49: ...0 600 1400 CFM 12x20x1 12x20x1 305x508x25 305x508x25 2 0 2 5 3 0 0 09 0 14 0 16 0 18 0 25 0 28 0 30 1200 1800 CFM 16x24x1 14x24x1 406x610x25 356x610x25 3 5 4 0 0 10 0 11 0 12 0 13 0 14 0 16 0 16 1500 2200 CFM 16x24x1 18x24x1 406x610x25 457x610x25 5 0 0 15 0 17 0 18 0 20 0 21 0 22 0 23 0 23 Table 16 Filter Pressure Drop Table IN W C FILTER SIZE IN MM COOLING TONS STANDARD CFM SCFM 600 700 800 900 1...

Page 50: ... electric wires are not in contact with refrigerant tubing or sharp metal edges 6 Check and inspect heating section before each heating season Clean and adjust when necessary 7 Check flue hood and remove any obstructions if necessary Air Filter IMPORTANT Never operate the unit without a suitable air filter in the return air duct system Always replace the filter with the same dimensional size and t...

Page 51: ... See Fig 20 4 Disconnect gas piping at unit gas valve 5 Remove fan partition mounting bracket 2 screws located on the left side of control compartment on the fan partition panel Slide bracket forward bottom first to remove See Fig 19 6 Remove wires connected to gas valve Mark each wire 7 Remove the mounting screw that attaches the burner rack to the unit base See Fig 19 8 Partially slide the burne...

Page 52: ...Fig 23 6 Ensure that setscrew engages the flat area on the motor shaft when tightening 7 Replace grille Electrical Controls and Wiring Inspect and check the electrical controls and wiring annually Be sure to turn off the electrical power to the unit Remove access panels see Fig 20 to locate all the electrical controls and wiring Check all electrical connections for tightness Tighten all screw conn...

Page 53: ...ice depending on size Pressure Switches Pressure switches are protective devices wired into control circuit low voltage They shut off compressor if abnormally high or low pressures are present in the refrigeration circuit These pressure switches are specifically designed to operate with R 410A systems R 22 pressure switches must not be used as replacements for the R 410A system Low Pressure Switch...

Page 54: ... into the surrounding area It is also known as a high side design since high pressure gas surrounds the motor and compression chamber The majority of the shell will be hot to the touch The rotary compressor also utilizes an external built in accumulator to reduce the likelihood of refrigerant liquid from entering the compressor Servicing Systems on Roofs with Synthetic Materials POE polyolester co...

Page 55: ...only compatible with POE synthetic oils S Vacuum pumps will not remove moisture from oil S Do not use liquid line filter driers with rated working pressures less than 600 psig S Do not leave R 410A suction line filter driers in line longer than 72 hrs S Do not install a suction line filter drier in liquid line S POE synthetic oils absorb moisture rapidly Do not expose oil to atmosphere S POE synth...

Page 56: ...shown on rating plate Defective compressor Replace and determine cause Insufficient line voltage Determine cause and correct Blocked outdoor coil Determine cause and correct Defective run start capacitor Determine cause and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace ...

Page 57: ...ng Limit switch faults LED 2 flashes High temperature limit switch is open Check the operation of the indoor evaporator fan motor Ensure that the supply air temperature rise is in accordance with the range on the unit nameplate Clean or replace filters Flame sense fault LED 3 flashes The IGC sensed flame that should not be present Reset unit If problem persists replace control board 4 consecutive ...

Page 58: ... ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB GAS HEAT SUPPLY AIR PRESSURES GAS INLET PRESSURE IN W C GAS MANIFOLD PRESSURE IN W C REFRIGERANT SUCTION PSIG SUCTION LINE TEMP REFRIGERANT DISCHARGE PSIG LIQUID TEMP VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS GAS HEAT TE...

Reviews: