34
Fig. 52 — Outdoor-Air Damper Leakage
Differential Dry Bulb Control
For differential dry bulb control, the standard outdoor dry bulb
sensor is used in conjunction with an additional accessory dry
bulb sensor (part number CRTEMPSN002A00). The accessory
sensor must be mounted in the return airstream. (See Fig. 53.)
Wiring is provided in the EconoMi$er IV wiring harness.
Fig. 53 — Return-Air Temperature or Enthalpy
Sensor Mounting Location
In this mode of operation, the outdoor-air temperature is com-
pared to the return-air temperature and the lower temperature
airstream is used for cooling. When using this mode of change-
over control, turn the enthalpy set point potentiometer fully
clockwise to the D setting. (See Fig. 50.)
Outdoor Enthalpy Changeover
For enthalpy control, accessory enthalpy sensor (part number
HH57AC078) is required. Replace the standard outdoor dry
bulb temperature sensor with the accessory enthalpy sensor in
the same mounting location. (See Fig. 53.) When the outdoor
air enthalpy rises above the outdoor enthalpy changeover set
point, the outdoor-air damper moves to its minimum position.
The outdoor enthalpy changeover set point is set with the out-
door enthalpy set point potentiometer on the EconoMi$er IV
controller. The set points are A, B, C, and D. (See Fig. 54.) The
factory-installed 620-ohm jumper must be in place across ter-
minals SR and SR+ on the EconoMi$er IV controller.
Fig. 54 — Enthalpy Changeover Set Points
Fig. 55 — EconoMi$er IV Control
Differential Enthalpy Control
For differential enthalpy control, the EconoMi$er IV controller
uses two enthalpy sensors (HH57AC078 and CRENT-
DIF004A00), one in the outside air and one in the return air
duct. The EconoMi$er IV controller compares the outdoor air
enthalpy to the return air enthalpy to determine EconoMi$er IV
use. The controller selects the lower enthalpy air (return or out-
door) for cooling. For example, when the outdoor air has a
lower enthalpy than the return air, the EconoMi$er IV opens to
bring in outdoor air for free cooling.
Replace the standard outside air dry bulb temperature sensor
with the accessory enthalpy sensor in the same mounting loca-
tion. (See Fig. 42.) Mount the return air enthalpy sensor in the
return air duct. (See Fig. 53.) Wiring is provided in the
EconoMi$er IV wiring harness. (See Fig. 42.) The outdoor en-
thalpy changeover set point is set with the outdoor enthalpy set
point potentiometer on the EconoMi$er IV controller. When
using this mode of changeover control, turn the enthalpy set
point potentiometer fully clockwise to the D setting.
0
5
10
15
20
25
3
0
0.1
3
0.20
0.22
0.25
0.
3
0
0.
3
5
0.40
0.45
0.50
S
TATIC PRE
SS
URE (in. wg)
FLOW
IN
CUBIC
FEET
PER
MINUTE
(cfm)
ECONOMI$ER IV
ECONOMI$ER IV
CONTROLLER
GROMMET
RETURN AIR
S
EN
S
OR
RETURN DUCT
(FIELD-PROVIDED)
CONTROL
CURVE
A
B
C
D
CONTROL POINT
APPROX.
deg. F (deg. C)
AT 50% RH
73 (23)
70 (21)
67 (19)
63 (17)
12
1
4
16
18
2
0
22
24
26
28
30
32
3
4
3
6
38
40
4
2
4
4
46
90
1
0
0
80
7
0
60
50
40
30
20
10
ENTHA
LPY
B
T
U PER POUND DRY
AIR
85
(29)
90
(32)
95
(35)
100
(38)
105
(41)
110
(43)
3
5
(2)
35
(2)
40
(4)
40
(4)
105
(41)
110
(43)
45
(7)
45
(7)
50
(10)
50
(10)
55
(13)
55
(13)
60
(16)
60
(16)
65
(18)
65
(18)
70
(21)
70
(21)
75
(24)
75
(24)
80
(27)
80
(27)
85
(29)
90
(32)
95
(35)
100
(38)
A
A
B
B
C
C
D
D
R
E
LATIVE
HUMID
ITY (
%)
HIGH LIMIT
CURVE
APPROXIMATE DRY BULB TEMPERATURE--degree
s
F (degree
s
C)
TR1
24 V
a
c
COM
TR
24
V
a
c
HOT
1
2
3
4
5
EF
EF1
+
_
P1
T1
P
T
N
EXH
2V
10V
EXH
S
et
S
et
2V
10V
2V
10V
DCV
DCV
Free
Cool
B
C
A
D
S
O+
S
R+
S
R
S
O
AQ1
AQ
DCV
Min
Po
s
Open
M
a
x
N1
Summary of Contents for Puron R-410A
Page 29: ...29 Fig 44 RTU Open Overlay for Economizer Wiring ...
Page 30: ...30 Fig 45 VFD Overlay for W2770 Controller Wiring ...
Page 50: ...50 Fig 63 50KC Typical Unit Wiring Diagram Power 06A 208 230 3 60 ...
Page 51: ...51 Fig 64 50KC Unit Wiring Diagram Control A06 ...
Page 77: ...77 Fig C Unit Wiring Diagram Power for Sizes A04 and A06 208 230 1 60 ...
Page 78: ...78 Fig D Unit Wiring Diagram Power for Size A05 208 230 1 60 ...
Page 79: ...79 Fig E Unit Wiring Diagram Power for Sizes A04 A06 208 230 3 60 460 3 60 575 3 60 ...