Installation 

Install and wire this product in accordance with applicable national and 

local codes, ordinances, and regulations. 
For detailed assembly, setup, and test instructions not provided here 

refer to the printer manufacturer’s documentation. 

WARNING: 

Electrocution hazard. To avoid personal injury or death 

from electrocution, remove all sources of power and allow stored 

energy to discharge before installing or removing equipment. 
 

Cautions

 

•  Do not plug the printer into a power outlet until after all packing 

materials have been removed and the printer has been 

assembled.  

•  Be sure the voltage rating of the power outlet matches the power 

requirements of the printer.  

•  To avoid print-head damage and paper jams, set the head gap as 

instructed in the manufacturer’s documentation. 

Notes 

•  Perform a printer self-test by loading paper and holding down the 

Line Feed button while turning on printer power. 

•  If the printer is required to operate during brownout conditions and 

AC power failures, install a UL Listed (UTRZ) uninterruptible power 

supply that can maintain printer operating voltage for at least 

24 hours. 

•  For ULC applications in which a UPS is used as the emergency 

power supply, install the printer and the UPS in a lockable 

enclosure in accordance with CAN/ULC-S527. 

•  Install the DTK-DL120/240 surge protective device shipped with 

the printer onto the circuit supplying AC power to the printer. 

Follow the SPD manufacturer’s installation instructions. 

•  Use the 25-pin serial connection or the USB connection, but not 

both. 

•  Serial/USB printer connections are power-limited and may or not 

be supervised depending on configuration.  

•  Locate supervised serial/USB printers in the same room as the 

equipment to which they connect.  

•  Locate unsupervised serial/USB printers in the same room and 

within 20 ft. (6.1 m) of the equipment to which they connect. 

Enclose wiring in conduit or equivalent protection against 

mechanical injury.  

•  Connecting a serial/USB printer may cause a ground fault on some 

control units. If this happens, install an IOP3-A isolator module 

between the printer and the control unit. 

To connect using serial cable connections: 

1.  Connect the DB-25 connector end of the cable to the serial port on 

the back of the printer. 

2.  Connect the other end of the cable to the control unit’s serial 

printer port or to the option card printer port as specified in the 

control unit’s technical manual. 

To connect using USB cable connections: 

1.  Connect the USB 2.0, type A host port connector end of the cable 

to the USB port on the printer. 

2.  Connect the other end of the cable to the control unit’s USB 2.0 

type B device port or to the option card USB 2.0 type B device port 

as specified in the control unit’s technical manual. 

Specifications 

 
Voltage 

 

120-volt models 

 

220-volt models 

 

120 V, 50/60 Hz 

220 to 240 V, 50/60 Hz 

Current 

1 A 

Interface 

USB 2.0  

RS-232C Serial 

Wire size 

22 AWG (0.50 mm²) 

Dimensions (W × H × D) 

14.65 × 3.15 × 10.83 in.  

(37.2 × 8.0 × 27.5 cm) 

Weight 

 

120-volt models 

 

220-volt models 

 

8.6 lb. (3.9 kg) 

9.9 lb. (4.5 kg) 

Ribbon cartridge 

Oki 52102001 

Operating environment 

 

Temperature 

 

Relative humidity 

 

32 to 120°F (0 to 49°C) 

0 to 93% noncondensing 

Contact information 

For contact information, see www.edwardsfiresafety.com. 
 
 
 