50VT

Performance

t

Single---Packaged Heat Pump Units with Puron

R

(R---410A) Refrigerant

Single--- And Three---Phase

2 to 5 Nominal Tons (Sizes 024---060)

Product Data

A99001

Fig. 1 -- Unit 50VT

Single--Packaged Products with Energy--Saving Features and

Puron

R

refrigerant.

S

Up to 14.5 SEER

S

8.0 HSPF

S

12 EER at 95

_

F (35

_

C) OD

S

Factory--Installed TXV

S

Multi--Speed Blower--Standard

FEATURES/BENEFITS

One--piece Heat Pump unit with optional electric heater, low

installation cost, dependable performance and easy maintenance.

Efficient operation High--efficiency design

with SEERs

(Seasonal Energy Efficiency Ratio) of up to 14.5.

Puron Environmentally Sound Refrigerant

is Carrier’s unique

refrigerant designed to help protect the environment. Puron is an

HFC refrigerant which does not contain chlorine that can harm the
ozone layer. Puron refrigerant is in service in millions of systems,

proving highly reliable, environmentally sound performance.

Easy Installation

Factory--assembled package is a compact, fully self--contained,

heat pump unit that is prewired, pre--piped, and pre--charged for
minimum installation expense. These units are available in a

variety of standard capacity ranges with voltage options to meet
residential and light commercial requirements. Units are

lightweight and install easily on a rooftop or at ground level. The

high tech composite base eliminates rust problems associated with
ground level applications.

Durable, dependable components Compressors

are designed

for high efficiency. Each compressor is hermetically sealed against

contamination to help promote longer life and dependable
operation. Each compressor also has vibration isolation to provide

quieter operation. All compressors have internal high pressure and

overcurrent protection.

Direct--drive multi--speed brushless DC blower motor

is

standard on all 50VT models. Direct--drive, PSC condenser--fan
motors are designed to help reduce energy consumption and

provide for cooling operation down to 40

_

F (4.4

_

C) outdoor

temperature. Motormaster

R

II low ambient kit is available as a

field installed accessory.

Thermostat Controls

designed to work as a system with Carrier’s

small packaged product.

Thermostatic Expansion Valve

-- A hard shutoff, balance port

TXV maintains a constant superheat at the evaporator exit (cooling
cycle) resulting in higher overall system efficiency.

Refrigerant system

is designed to provide dependability. Liquid

filter driers are used to promote clean, unrestricted operation. Each

unit leaves the factory with a full refrigerant charge. Refrigerant
service connections make checking operating pressures easier.

High and Low Pressure Switches

provide added reliability for the

compressor.

Indoor and Outdoor coils

are computer--designed for optimum

heat transfer and efficiency. The indoor coil is fabricated from
copper tube and aluminum fins and is located inside the unit for

protection against damage. The outdoor coil is internally mounted

on the top tier of the unit. Copper fin coils and pre--coated fin coils
are available from the factory by special order. These coils are

recommended in applications where aluminum fins are likely to be
damaged due to corrosion. They are ideal for seacoast applications.

Low sound ratings

ensure a quiet indoor and outdoor

environment with sound ratings as low as 72dBA.

Easy to service cabinets

provide easy single--panel accessibility to

serviceable components during maintenance and installation. The
base with integrated drain pan provides easy ground level

installation with or without a mounting pad. Convenient
hand--holds are provided to manipulate the unit on the jobsite. A

nesting feature ensures a positive basepan to roof curb seal when

the unit is roof mounted. A convenient 3/4--in. wide perimeter
flange makes frame mounting on a rooftop easy.

Convertible duct configuration

Unit is designed for easy use in either downflow or horizontal

applications. Each unit is easily converted from horizontal to

downflow with the two duct covers, standard on 3 phase units and
available as an accessory for single phase units. Downflow

operation is easily provided in the field to allow vertical ductwork
connections. The basepan utilizes knockout style seals on the

bottom openings to ensure a positive seal in the horizontal airflow

mode.

Cabinets

are constructed of heavyduty, phosphated, zinc--coated

prepainted steel capable of withstanding 500 hours in salt spray.
Interior surfaces of the evaporator and electric heater compartments

are insulated with cleanable semi--rigid insulation board, which

Summary of Contents for Performance 50VT

Page 1: ...static Expansion Valve A hard shutoff balance port TXV maintains a constant superheat at the evaporator exit cooling cycle resulting in higher overall system efficiency Refrigerant system is designed...

Page 2: ...AND WIRING 20 APPLICATION DATA 21 ELECTRICAL DATA 23 24 TYPICAL WIRING SCHEMATICS 25 27 CONTROLS 28 GUIDE SPECIFICATIONS 29 30 MODEL NUMBER NOMENCLATURE 50VT 1 Type of Unit 50VT Single Packaged Heat P...

Page 3: ...8 0 048 301 501 601 45500 3 3 23800 2 3 8 0 060 301 501 601 60000 3 5 33600 2 3 8 0 LEGEND dB Sound Levels decibels db Dry Bulb SEER Seasonal Energy Efficiency Ratio wb Wet Bulb COP Coefficient of Per...

Page 4: ...TCH psig Cutout Reset Auto 650 15 420 25 LOSS OF CHARGE LOW PRESSURE SWITCH Liquid Line psig Cutout Reset Auto 20 5 45 10 20 5 45 10 RETURN AIR FILTERS throwaway in mm 20x20x1 508x508x25 20x24x1 508x6...

Page 5: ...al heat in the unit when required Each package has a heater module that slides into the controls compartment Heater sizes range from 5 0 to 20 0 kW The electric heater design allows the use of a singl...

Page 6: ...0 HZ CPHEATER055A00 5 0 X X X X X CPHEATER056A00 10 0 X X X CPHEATER068A00 10 0 X X CPHEATER058A00 15 0 X X X X X CPHEATER059A01 20 0 X X X 460 THREE PHASE 60 HZ CPHEATER060A00 5 0 X X X X CPHEATER061...

Page 7: ...ISCHARGE REPLACEMENT PANEL HOLE FOR ECONOMIZER WIRING HARDNESS DOOR LATCH ANGLE HINGED FILTER ACCESS DOOR INSTALL FILTER ACCESS DOOR STICKER ALUMINUM FILTER RAINHOOD 11 13 32 17 13 32 16 1 4 EV APORAT...

Page 8: ...8 UNIT DIMENSIONS 50VT024 030 A08074 50VT...

Page 9: ...060 74 34 59 27 89 40 148 67 98 45 153 70 82 37 66 30 108 49 170 77 82 37 66 30 99 45 165 75 86 39 69 31 104 47 173 78 86 39 69 31 113 51 178 81 92 42 74 34 111 50 185 84 92 42 74 34 120 54 190 86 74...

Page 10: ...d retainer bracket must also be used A BTyp Supply opening B x C Long Support D 445 16 Return opening B X C Insulate d deck pan Short Support CTyp C00076 UNIT SIZE CATALOG NUMBER A IN MM B IN MM C IN...

Page 11: ...will provide a total capacity of 36 000 Btuh and a SHC of 27 400 Btuh Calculate SHC correction if required using Note 4 under Cooling Capacities tables 3 Select heating capacity of unit to provide de...

Page 12: ...18 58 1 93 21 38 17 30 2 16 19 34 15 99 2 40 17 19 14 61 2 66 72 29 85 16 75 1 55 27 72 15 64 1 73 25 55 14 52 1 94 23 35 13 40 2 16 22 34 12 76 2 13 18 67 11 09 2 66 At 75_F 23 9 _C entering dry bulb...

Page 13: ...5 27 32 22 64 2 69 25 06 21 88 2 95 22 58 20 93 3 22 72 36 33 19 07 2 03 34 30 18 58 2 24 32 12 18 01 2 46 29 81 17 37 2 70 27 30 16 63 2 96 24 52 15 74 3 23 At 75_F 23 9 _C entering dry bulb Tennesse...

Page 14: ...26 97 3 31 28 73 24 84 3 61 24 84 22 67 3 93 72 49 01 26 47 2 54 44 48 24 63 2 78 40 03 22 80 3 05 35 68 20 98 3 33 31 39 19 16 3 63 27 12 17 31 3 95 At 75_F 23 9 _C entering dry bulb Tennessee Valley...

Page 15: ...89 3 83 38 06 30 44 3 80 32 50 27 49 4 64 72 50 59 27 89 2 87 47 95 26 72 3 18 45 17 25 51 3 51 42 14 24 18 3 88 41 29 23 80 3 86 35 01 21 00 4 69 At 75_F 23 9 _C entering dry bulb Tennessee Valley A...

Page 16: ...40 4 33 37 39 32 12 4 80 32 61 29 67 5 31 72 60 91 32 02 3 17 55 86 30 17 3 53 50 80 28 29 3 92 45 76 26 38 4 36 40 65 24 40 4 83 35 38 22 30 5 34 At 75_F 23 9 _C entering dry bulb Tennessee Valley A...

Page 17: ...64 5 73 47 60 44 16 6 42 40 92 42 14 7 17 72 79 84 37 74 4 09 72 79 36 91 4 60 65 73 35 91 5 16 58 70 34 70 5 79 51 53 33 23 6 48 44 15 31 39 7 22 At 75_F 23 9 _C entering dry bulb Tennessee Valley A...

Page 18: ...capacity Btuh 1 10 x cfm t ldb t edb Wet bulb temperature corresponding to enthalpy air leaving evaporator coil h lwb t lwb total capacity Btuh 4 5 x cfm h lwb h ewb Where h ewb Enthalpy of air enter...

Page 19: ...F 26 6_C edb temperature of air entering evapo rator coil Below 805 F 26 6_C edb subtract corr factor x cfm from SHC Above 805 F 26 6_C edb add corr factor x cfm to SHC Correction Factor 1 10 x 1 BF...

Page 20: ...1449 1411 1362 1313 1278 1231 1188 High Black CFM 1705 1643 1607 1568 1518 1483 1448 1404 1360 50VT04230 50 60 Low Blue CFM 1295 1234 1182 1126 1075 1016 955 898 857 Med Low Pink CFM 1345 1282 1235 1...

Page 21: ...re duct covers Maximum cooling airflow To minimize the possibility of condensate blow off from the evaporator airflow through the units should not exceed 450 cfm per ton Minimum cooling airflow Minimu...

Page 22: ...LANCE POINT WORKSHEET 0 10 20 30 40 50 60 70 20 10 0 10 20 30 40 50 60 70 OUTDOOR TEMPERATURE F 0 0 2 9 5 9 8 8 11 7 14 6 17 6 20 5 024 0 030 0 036 0 042 0 048 0 060 0 BASED ON INDOOR ENT AIR AT 70 F...

Page 23: ...11 3 15 54 2 62 5 110 2 120 6 125 125 15 20 72 2 83 3 132 8 146 7 150 150 5 4 7 2 25 9 30 74 9 79 9 80 80 50VT 030 501 208 230 3 60 187 253 10 3 58 0 0 9 4 1 17 8 17 8 25 25 3 8 5 10 4 12 30 9 32 9 3...

Page 24: ...size from NEC 3 Unbalanced 3 Phase Supply Voltage Never operate a motor where a phase imbalance in supply volt age is greater than 2 Use the following formula to determine the percentage of voltage i...

Page 25: ...25 TYPICAL WIRING SCHEMATIC 208 230 1 60 A08024 50VT...

Page 26: ...26 TYPICAL WIRING SCHEMATIC 208 230 3 60 A08025 50VT...

Page 27: ...27 TYPICAL WIRING SCHEMATIC 460 3 60 A08026 50VT...

Page 28: ...stage thermostat If optional electric heat package is used a relay is energized bringing on first bank of supplemental electric heat When thermostat is satisfied contacts open deenergizing contactor a...

Page 29: ...l be made from steel and shall be double inlet type with forward curved blades with corrosion resistant finish Fan wheel shall be dynamically balanced 3 Outdoor fan shall be direct drive propeller typ...

Page 30: ...mbient temperature 8 Filter Rack Kit Shall provide filter mounting for downflow applications 9 Square To Round Duct Transitions 024 048 Shall have the ability to convert the supply and return open ing...