background image

11

PRE--START--UP

!

WARNING

ENVIRONMENTAL,

FIRE,

EXPLOSION,

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death and/or property damage.

1. Follow recognized safety practices and wear protective

goggles when checking or servicing refrigerant system.

2. Relieve and recover all refrigerant from system before

touching or disturbing compressor plug if refrigerant
leak is suspected around compressor terminals.

3. Never attempt to repair soldered connection while

refrigerant system is under pressure.

4. Do not use torch to remove any component. System

contains oil and refrigerant under pressure.

5. To remove a component, wear protective goggles and

proceed as follows:

a. Shut off electrical power to unit and install

lockout tag.

b. Relieve and reclaim all refrigerant from system

using both high-- and low--pressure ports.

c. Cut component connecting tubing with tubing

cutter and remove component from unit.

d. Carefully unsweat remaining tubing stubs when

necessary. Oil can ignite when exposed to torch

flame.

Use the Start--Up Checklist supplied at the end of this book and

proceed as follows to inspect and prepare the unit for initial
start--up:

1. Remove all access panels (see Fig. 21).
2. Read and follow instructions on all DANGER, WARNING,

CAUTION, and INFORMATION labels attached to, or
shipped with unit.

3. Make the following inspections:

a. Inspect for shipping and handling damages, such as

broken lines, loose parts, disconnected wires, etc.

b. Inspect for oil at all refrigerant tubing connections and

on unit base. Detecting oil generally indicates a

refrigerant leak. Leak test all refrigerant tubing
connections using electronic leak detector, or

liquid--soap solution. If a refrigerant leak is detected, see
following

Check for Refrigerant Leaks

section.

c. Inspect all field-- and factory--wiring connections. Be

sure that connections are completed and tight. Ensure
wires do not touch refrigerant tubing or sharp sheet

metal edges.

d. Inspect coil fins. If damaged during shipping and

handling, carefully straighten fins with a fin comb.

4. Verify the following conditions:

a. Make sure that outdoor--fan blade is correctly positioned

in fan orifice.

b. Make sure that air filter(s) is in place.

c. Make sure that condensate drain pan and trap are filled

with water to ensure proper drainage.

d. Make sure that all tools and miscellaneous loose parts

have been removed

5. Each unit system has two (2) Schrader--type ports, one low--

side Schrader fitting located on the suction line, and one
high--side Schrader fitting located on the compressor
discharge line. Be sure that caps on the ports are tight.

START--UP

Step 1 — Check Cooling and Heating Control

Operation

Start and check the unit for proper control operation as follows:

1. Place room thermostat SYSTEM switch or MODE control

in OFF position. Observe that blower motor starts when

FAN mode is placed in FAN ON position and shuts down
when FAN MODE switch is placed in AUTO position.

2. Thermostat:

On a typical two stage thermostat, when the room temper-
ature rises 1 or 2 degrees above the cooling control setting

of the thermostat, the thermostat completes the circuit
between thermostat terminal R and terminals Y1, and G.
These completed circuits through the thermostat connect the

contactor coil (C) (through unit wire Y1) and indoor fan
board (through unit wire G) across the 24--v. secondary of

transformer (TRAN).
On a typical two stage thermostat, when the room temperat-

ure is several degrees above the cooling control setting of
the thermostat, the thermostat completes the circuit between
terminal R and terminals Y1, Y2 , and G.

3. If your unit contains accessory electric heat, place system

switch or MODE control in HEAT position. Set control

above room temperature. Observe that the indoor blower is
operating and warm air is flowing through the supply air
vents inside your home. Observe that the heating cycle

shuts down when the control setting is satisfied.
If your unit does not contain accessory electric heat and you

would like to obtain it, please contact your local dealer for
more information.

4. When using an automatic changeover room thermostat

place both SYSTEM or MODE control and FAN mode
stitches in AUTO positions. Observe that unit operates in

Cooling mode when temperature control is set to “call for
Cooling” (below room temperature).

NOTE

: Once the compressor has started and then has stopped, it

should not be started again until 5 minutes have elapsed.

Step 2 — Check for Refrigerant Leaks

EXPLOSION HAZARD

Failure to follow this warning could

result in death, serious personal injury,

and/or property damage.
Never use air or gases containing

oxygen for leak testing or operating

refrigerant compressors. Pressurized

mixtures of air or gases containing

oxygen can lead to an explosion.

!

WARNING

Proceed as follows to locate and repair a refrigerant leak and to

charge the unit:

1. Locate leak and make sure that refrigerant system pressure

has been relieved and reclaimed from both high--and low--
pressure ports.

2. Repair leak following Refrigerant Service procedures.

NOTE

: Install a filter drier whenever the system has been opened

for repair.

3. Add a small charge of R--410A refrigerant vapor to system

and leak--test unit.

4. Recover refrigerant from refrigerant system and evacuate to

500 microns if no additional leaks are found.

5. Charge unit with R--410A refrigerant, using an electronic

scale. Refer to unit rating plate for required charge.

50V

R

Summary of Contents for Performance 50VR-A

Page 1: ...3 A09033 Fig 1 Unit 50VR Electrical Controls and Wiring 33 Refrigerant Circuit 34 Evaporator Airflow 34 Metering Device 34 System Information 35 Loss of Charge Switch 35 Check Defrost Thermostat 35 TR...

Page 2: ...the downflow panels before rigging and lifting into place The panel removal process may require the unit to be on the ground Step 2 Provide Unit Support IMPORTANT The unit must be secured to the curb...

Page 3: ...3 A180108 Fig 2 50VR C24 30 Unit Dimensions 50VR...

Page 4: ...4 A180107 Fig 3 50VR A36 60 Unit Dimensions 50VR...

Page 5: ...30 6 778 46 1 1170 Large CPRFCURB013B00 14 356 14 356 43 9 1116 42 2 1072 Part Number CPRCURB011B00 can be used on both small and large basepan units The cross supports must be located based on whethe...

Page 6: ...install the unit on carpeting or other combustible materials Slab mounted units should be at least 2 in 51 mm above the highest expected water and runoff levels Do not use unit if it has been under w...

Page 7: ...ing condensate drain connection be sure to comply with local codes and restrictions This unit disposes of condensate water through a 3 4 in NPT fitting which exits through the base on the evaporator c...

Page 8: ...f nonresidence type air conditioning and ventilating systems NFPA 90A or residence type NFPA 90B and or local codes and ordinances Adhere to the following criteria when selecting sizing and installing...

Page 9: ...ellow wires connected to the line side of the contactor 4 Connect field L1 to black wire from connection 11 of the compressor contactor 5 Connect field wire L3 to yellow wire from connection 13 of the...

Page 10: ...ominal High Stage Cooling Airflow Cfm Size in Size mm Motor HP RPM 675 775 900 1050 1200 1400 675 855 10x10 254x254 1 2 1050 775 1000 10x10 254x254 1 2 1050 900 1200 11x10 279 4x254 3 4 1000 1050 1400...

Page 11: ...TART UP Step 1 Check Cooling and Heating Control Operation Start and check the unit for proper control operation as follows 1 Place room thermostat SYSTEM switch or MODE control in OFF position Observ...

Page 12: ...es stabilize 4 Measure and record the following a Outdoor ambient air temperature F C db b Liquid line temperature F C at TXV c Discharge high side pressure psig d Suction low side pressure psig for r...

Page 13: ...nect one speed tap wire to two or more speed connections on the Interface Fan Board IFB Jumper wires must use 18 AWG wire with at least 2 64 insulation Cooling Heat Pump Continuous Fan with Advanced D...

Page 14: ...674 K3 K2 K4 K1 QC2 QC5 QC6 QC4 QC9 QC3 US HSCI DH DH DH DH Shunt in no dehumidification position Shunt in dehumidification position A12571 208 230 VAC Models HIGH LOW COM QC5 QC4 QC3 KZ KL 07 09 08...

Page 15: ...irection of flow Position HPS TXV in Bypass Metering Position C03012 Fig 13 Typical Heat Pump Operation Heating Mode COMPRESSOR ACCUMULATOR OUTDOOR COIL INDOOR COIL LCS LEGEND HPS High Pressure Switch...

Page 16: ...65 670 586 466 299 BHP 0 11 0 12 0 12 0 13 0 13 0 14 Medium Red CFM 1139 1069 1012 937 870 786 724 626 512 381 BHP 0 22 0 23 0 24 0 24 0 25 0 26 0 26 0 27 0 27 0 28 Med High Orange CFM 1229 1171 1105...

Page 17: ...1356 BHP 0 42 0 44 0 45 0 46 0 48 0 49 0 51 0 52 0 53 0 55 Med High Orange CFM 1854 1837 1781 1784 1720 1698 1655 1625 1578 1532 BHP 0 56 0 57 0 60 0 59 0 62 0 63 0 64 0 66 0 67 0 67 High Black CFM 1...

Page 18: ...75 970 1035 1075 1065 LOW STAGE COOLING 835 850 845 930 945 940 1025 1040 1035 COOLING WITH DEHUMIDIFY 675 685 670 750 760 745 825 835 820 A42 HIGH STAGE COOLING 1240 1265 1275 1375 1405 1414 1515 154...

Page 19: ...17 0 18 0 18 0 20 0 21 0 22 Med Low Pink CFM 1213 1169 1110 1065 1016 964 923 878 820 777 BHP 0 16 0 17 0 17 0 19 0 20 0 21 0 22 0 23 0 24 0 25 Medium Red CFM 1251 1198 1149 1104 1066 1017 970 932 89...

Page 20: ...dium 2 Red CFM 1818 1770 1731 1693 1657 1621 1579 1546 1505 1436 BHP 0 56 0 57 0 59 0 60 0 62 0 63 0 64 0 66 0 67 0 66 Med High Orange CFM 1881 1849 1818 1793 1763 1729 1679 1610 1523 1479 BHP 0 67 0...

Page 21: ...1400CFM 12x20x1 12x20x1 305x508x25 305x508x25 2 0 2 5 0 09 0 14 0 16 0 18 0 25 0 28 0 3 1200 1800 CFM 16x24x1 14x24x1 406x610x25 356x610x25 3 0 3 5 0 10 0 11 0 12 0 13 0 14 0 16 0 16 1500 2200 CFM 16x...

Page 22: ...12 0 14 0 16 0 18 20 kW 0 00 0 00 0 02 0 04 0 06 0 08 0 09 0 11 0 13 0 15 0 17 0 19 Large Cabinet 36 60 STATIC STANDARD CFM SCFM 1100 1200 1300 1400 1500 1600 1700 1800 1900 2000 2100 2200 2300 2400...

Page 23: ...23 A13144 Fig 15 Connection Wiring Diagram without Advanced Dehumidification AD FIOP 208 230 1 60 50VR...

Page 24: ...24 A13145 Fig 15 Cont Ladder Wiring Diagram without Advanced Dehumidification AD FIOP 208 230 1 60 50VR...

Page 25: ...D 7 THIS FUSE IS MANUFACTURED BY LITTLE FUSE P N 287003 8 N E C CLASS 2 24V 9 TO USE THE ADVANCED DEHUMIDIFICATION FEATURE CUT JUMPER 1 SCHEMATIC 208 230V 1 60 BLK OF2 OF1 BLK BLK DR ON DB FIELD SPLIC...

Page 26: ...JUMPERED TEST PINS USE METAL OBJECT FIELD SPEED UP CYCLE 1 MOMENTARILY SHORT PINS AND RELEASE TO BYPASS COMPRESSOR OFF DELAY 2 SHORT FOR 5 SEC AND RELEASE FOR FORCED DEFROST 3 PERMANENT SHORT WILL BE...

Page 27: ...27 A13146 Fig 17 Connection Wiring Diagram 208 230 3 60 50VR...

Page 28: ...28 A13147 Fig 17 Cont Ladder Wiring Diagram 208 230 3 60 50VR...

Page 29: ...29 A13148 Fig 18 Connection Wiring Diagram 460 3 60 50VR...

Page 30: ...30 A13149 Fig 18 Cont Ladder Wiring Diagram 460 3 60 50VR...

Page 31: ...31 A170012 Fig 19 Cooling Charging Chart 50VR...

Page 32: ...ace the filter with the same dimensional size and type as originally installed See Table 1 for recommended filter sizes Inspect air filter s at least once each month and replace throwaway type or clea...

Page 33: ...n and condensate drain line when inspecting the coils Clean the drain pan and condensate drain by removing all foreign matter from the pan Flush the pan and drain trough with clear water Do not splash...

Page 34: ...tch NOTE Because these switches are attached to refrigeration system under pressure it is not advisable to remove this device for troubleshooting unless you are reasonably certain that a problem exist...

Page 35: ...tem Do not unsweat a filter drier from the system Heat from unsweating will release moisture and contaminants from drier into system Puron R 410A Refrigerant Charging Refer to unit information plate a...

Page 36: ...capacitor overload or start relay Determine cause and replace Defective thermostat Replace thermostat Faulty condenser fan motor or capacitor Replace Restriction in refrigerant system Locate restrict...

Page 37: ...VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB HEAT PUMP SUPPLY AIR ELECTRIC HEAT SUPPLY AIR...

Page 38: ...p S 7310 W Morris St S Indianapolis IN 46231 Edition Date 09 19 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No 50VR...

Reviews: