Accessory usage guideline

 

* For tubing line sets greater than 50 ft horizontal and/or 20 ft vertical differential, refer to Residential Split System Long-Line Application Guideline 

and Service Manual.

† Only when low-pressure switch is used.
‡ Required for MotorMaster® Control only.

 

ACCESSORY

REQUIRED FOR

LOW-AMBIENT

APPLICATIONS

(Below 55°F)

REQUIRED FOR

LONG-LINE

APPLICATIONS*

(Over 50 Ft)

REQUIRED FOR

SEA COAST

APPLICATIONS
(Within 2 Miles)

Crankcase Heater

 

Yes

Yes

No

 

Evaporator Freeze Thermostat

 

Yes

No

No

 

Winter Start Control

 

Yes†

No

No

 

Accumulator

 

No

No

No

 

Compressor Start Assist

Capacitor and Relay

Yes

Yes

No

MotorMaster® Low-Ambient Controller

or Low-Ambient Pressure Switch

Yes

No

No

Wind Baffle

See Low-Ambient Instructions

No

No

Coastal Filter

No

No

Yes

Support Feet

Recommended

No

Recommended

Liquid-Line Solenoid Valve

or

Hard Shutoff TXV

No

See Long-Line

Application

Guideline

No

Ball Bearing Fan Motor

Yes‡

No

No

ACCESSORY DESCRIPTION AND USAGE (Listed Alphabetically)

1.

Ball-Bearing Fan Motor

A fan motor with ball bearings which permits speed reduction while maintaining bearing lubrication. 

Usage Guideline:

Required on all units when low-ambient controller (full modulation feature) or MotorMaster®—Low-Ambient Controller is installed.

2.

Coastal Filter 

A mesh screen inserted under the top cover and inside the base pan to protect the condenser coil from salt damage without restricting airflow.

3.

Compressor Start Assist – Capacitor and Relay

Start capacitor and relay gives a "hard" boost to compressor motor at each start up.

Usage Guideline:

Required for reciprocating compressors in the following applications: 

Long line
Low ambient
Hard shut off expansion valve on indoor coil
Liquid line solenoid on indoor coil

Required for scroll compressors in the following applications:

Long line
Low ambient

Suggested for all compressors in areas with a history of low voltage problems.

4.

Compressor Start Assist — PTC Type

Solid state electrical device which gives a "soft" boost to the reciprocating compressor at each start-up.

Usage Guideline:

Suggested in installations with marginal power supply.

5.

Crankcase Heater

An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles. Improves compressor lubrication on restart
and minimizes the chance of liquid slugging. 

Usage Guideline:

Required in low ambient applications.
Required in long line applications.
Suggested in all commercial applications.

6.

Evaporator Freeze Thermostat

An SPST temperature-actuated switch that stops unit operation when evaporator reaches freeze-up conditions.

Usage Guideline:

Required when low ambient kit has been added.

7.

Liquid-Line Solenoid Valve (LLS)  

This device serves two purposes. It is an electrically operated shutoff valve which stops and starts refrigerant liquid flow in response to compressor operation.
It maintains a column of refrigerant liquid ready for action at next compressor operation cycle. It also provides system protection against off-cycle refrigerant
migration. 

Note:

 

When LLS is used with reciprocating compressors, Compressor Start Assist — Capacitor and Relay is required.

Usage Guideline:

Required in air conditioner long line applications with a piston indoor metering device to prevent off cycle refrigerant migration. A hard shut 
off TXV can be used instead of an LLS in single flow air conditioner applications. See Long Line Application Guideline.

8.

MotorMaster®—Low-Ambient Controller

A fan-speed control device activated by a temperature sensor, designed to control condenser fan motor speed in response to the saturated, condensing temperature
during operation in cooling mode only. For outdoor temperatures down to –20°F (–28.9°C), it maintains condensing temperature at 100°F ± 10°F (37.8°C ± –
12°C).

Usage Guideline:

A MotorMaster®—Low Ambient Controller or Low-Ambient Pressure Switch must be used when cooling operation is used at outdoor tem-
peratures below 55°F (12.8°C). 
Suggested for all commercial applications.

Summary of Contents for Performance 13 38TXA

Page 1: ...t R 22 has been Puron refrigerant is in service in thousands of systems providing highly reliable environmentally sound performance Carrier s Infinity Controls These industry leading controls when installed with Carrier s Ideal Humidity variable speed furnaces or fan coils provide the homeowner with Unparalleled control of temperature humidity indoor air quality and zoning unprecedented ease of us...

Page 2: ...ive laminated plate beneath the compressor to eliminate sound transmission to the rest of the system Application Versatility Carrier s systems utilizing Puron refrigerant have the same application guidelines as other systems Applications which include long line sets 50 to 175 ft or applications which require the system to operate at low outdoor temperatures below 55 F are approved under Carrier s ...

Page 3: ... R 410A Control AccuRater TXV Hard Shutoff Charge Lb 5 50 6 00 6 88 8 75 9 95 11 50 COND FAN Propeller Type Direct Drive Air Discharge Vertical Air Qty CFM 2400 2400 2800 2800 3400 3400 Motor HP 1 8 1 8 1 5 1 5 1 4 1 4 Motor RPM 825 825 825 825 1125 1125 COND COIL Copper Tube Aluminum Plate Fin Face Area Sq ft 12 2 12 2 15 2 18 2 18 2 18 2 Fins per In 25 25 25 25 20 20 Rows 1 1 1 1 2 2 Circuits 2 ...

Page 4: ...KG DESCRIPTION TSTATCCPRH01 B Thermidistat Control Non Programmable Programmable Thermostat with Humidity Control TSTATCCPAC01 B Thermostat Auto Changeover 7 Day Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCNAC01 C Thermostat Auto Changeover Non Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCSAC01 Thermostat Manual Changeover 5 2 Day Programmable F C 1 Stage Heat 1 Stage Cool TSTATCCBAC01 ...

Page 5: ...lems 4 Compressor Start Assist PTC Type Solid state electrical device which gives a soft boost to the reciprocating compressor at each start up Usage Guideline Suggested in installations with marginal power supply 5 Crankcase Heater An electric resistance heater which mounts to the base of the compressor to keep the lubricant warm during off cycles Improves compressor lubrication on restart and mi...

Page 6: ...63 5 67 5 71 5 72 0 67 0 62 0 55 0 ACCESSORY DESCRIPTION AND USAGE continued 9 Outdoor Air Temperature Sensor Designed for use with Carrier Thermostats listed in this publication This device enables the thermostat to display the outdoor temperature This device also is required to enable special thermostat features such as auxiliary heat lock out Usage Guideline Suggested for all Carrier thermostat...

Page 7: ... ambient control is used max 125 F 2 Series designation is the 13th position of the unit model number 3 Center of gravity 4 NOTES A97084 DIMENSIONS IN UNIT SIZE SERIES UNIT DIMENSIONS MINIMUM MOUNTING PAD DIMENSIONS A B C D E F G H J K L M N 024 34 27 13 16 30 34 15 16 4 9 3 4 15 1 2 21 7 8 5 8 8 3 16 17 19 3 4 13 2 15 16 26 x 32 030 33 27 13 16 30 34 15 16 4 9 3 4 15 1 2 21 7 8 3 4 8 3 16 18 1 2 ...

Page 8: ...0 14 00 12 35 CC5A CD5AW024 22 400 TDR 14 00 14 00 12 20 CC5A CD5AW030 22 800 TDR 14 00 14 00 12 35 CE3AA024 22 400 TDR 14 00 14 00 12 25 CE3AA030 22 800 TDR 14 00 14 00 12 45 CK3BA024 22 400 TDR 14 00 14 00 12 50 CK3BA030 22 800 TDR 14 00 14 00 12 55 CK5A CK5BA024 22 400 TDR 14 00 14 00 12 35 CK5A CK5BA030 22 800 TDR 14 00 14 00 12 45 CK5A CK5BW024 22 400 TDR 14 00 14 00 12 35 CK5A CK5BW030 22 80...

Page 9: ...4 00 14 00 12 55 CK5A CK5BW024 22 400 TDR 14 00 14 00 12 40 CK5A CK5BW030 22 800 TDR 14 00 14 00 12 50 CK5PW024 22 400 TDR TXV 14 00 12 30 CK5PW030 22 800 TDR TXV 14 00 12 45 COILS 58MVP100 20 VARIABLE SPEED FURNACE CC5A CD5AW024 22 400 TDR 14 00 14 00 12 25 CC5A CD5AW030 22 800 TDR 14 00 14 00 12 40 CE3AA024 22 400 TDR 14 00 14 00 12 25 CE3AA030 22 800 TDR 14 00 14 00 12 50 CK3BA024 22 400 TDR 14...

Page 10: ... TDR 14 00 14 00 12 20 CK5PA030 28 600 TDR TXV 13 50 11 80 CK5PA036 29 000 TDR TXV 14 00 12 20 CK5PT036 29 000 TDR TXV 14 00 12 20 CK5PW030 28 600 TDR TXV 13 50 11 80 CK5PW036 29 000 TDR TXV 14 00 12 20 COILS 58CV A X 110 20 VARIABLE SPEED FURNACE CC5A CD5AA036 29 000 TDR 14 00 14 00 12 40 CC5A CD5AW030 28 000 TDR 13 50 13 50 12 05 CC5A CD5AW036 29 000 TDR 14 00 14 00 12 45 CE3AA030 28 600 TDR 13 ...

Page 11: ...00 13 00 11 20 CK5A CK5BW036 35 000 NONE 13 00 13 00 11 20 CK5PA036 35 000 TXV 13 00 11 20 CK5PA042 35 000 TXV 13 00 11 20 CK5PT036 35 000 TXV 13 00 11 20 CK5PT042 35 000 TXV 13 00 11 20 CK5PW036 35 000 TXV 13 00 11 20 F A B 4 A B N F B C 042 35 000 TDR 13 00 13 00 11 25 F A B 4 A B N F C 036 35 000 TDR 12 50 12 50 11 15 FE4ANF002 35 000 TDR TXV 13 00 11 75 FE4ANF003 35 000 TDR TXV 13 50 12 05 FE4...

Page 12: ... CK5BW036 35 000 TDR 14 00 14 00 12 10 CK5PA042 35 000 TDR TXV 14 00 12 20 CK5PT042 35 000 TDR TXV 14 00 12 20 CK5PW036 35 000 TDR TXV 14 00 12 10 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AA042 35 000 TDR 14 00 14 00 12 30 CC5A CD5AW036 35 000 TDR 14 00 14 00 12 10 CC5A CD5AW042 35 000 TDR 14 00 14 00 12 25 CE3AA036 35 000 TDR 13 50 13 50 12 00 CE3AA042 35 000 TDR 14 00 14 00 12 30 CK3...

Page 13: ...0 TDR 13 50 13 50 11 90 CC5A CD5AW036 35 000 TDR 13 50 13 50 11 75 CE3AA036 35 000 TDR 13 00 13 00 11 60 CE3AA042 35 000 TDR 13 50 13 50 11 90 CK3BA036 35 000 TDR 13 50 13 50 11 85 CK3BA042 35 000 TDR 13 50 13 50 12 00 CK5A CK5BA042 35 000 TDR 13 50 13 50 12 00 CK5A CK5BT042 35 000 TDR 13 50 13 50 12 00 CK5A CK5BW036 35 000 TDR 13 50 13 50 11 85 CK5PA042 35 000 TDR TXV 13 50 12 00 CK5PT042 35 000 ...

Page 14: ... 12 20 CK5PT036 34 600 TDR TXV 14 00 12 05 CK5PT042 34 600 TDR TXV 14 00 12 15 CK5PW036 34 600 TDR TXV 14 00 12 10 COILS 58CV A X 110 20 VARIABLE SPEED FURNACE CC5A CD5AA036 34 400 TDR 13 50 13 50 12 05 CC5A CD5AA042 34 400 TDR 14 00 14 00 12 10 CC5A CD5AW036 34 400 TDR 14 00 14 00 12 10 CC5A CD5AW042 34 200 TDR 14 00 14 00 12 00 CE3AA036 34 000 TDR 13 50 13 50 11 90 CE3AA042 34 600 TDR 14 00 14 0...

Page 15: ... TDR TXV 13 50 12 05 CK5PW036 34 600 TDR TXV 13 50 12 05 COILS 58MVP080 14 VARIABLE SPEED FURNACE CC5A CD5AA036 34 400 TDR 13 50 13 50 11 75 CC5A CD5AA042 34 400 TDR 13 50 13 50 11 85 CC5A CD5AW036 34 400 TDR 13 50 13 50 11 80 CC5A CD5AW042 33 800 TDR 13 50 13 50 11 75 CE3AA036 34 000 TDR 13 50 13 50 11 60 CE3AA042 34 600 TDR 13 50 13 50 11 90 CK3BA036 34 600 TDR 13 50 13 50 11 80 CK3BA042 34 600 ...

Page 16: ...NONE 13 00 13 00 11 35 CF5AA048 40 500 NONE 12 50 12 50 11 20 CK3BA042 40 500 NONE 13 00 13 00 11 20 CK3BA048 40 500 NONE 13 00 13 00 11 30 CK5A CK5BA042 40 500 NONE 13 00 13 00 11 20 CK5A CK5BA048 40 500 NONE 13 00 13 00 11 30 CK5A CK5BE042 39 500 NONE 12 50 12 50 11 30 CK5A CK5BT042 40 500 NONE 13 00 13 00 11 20 CK5A CK5BT048 40 500 NONE 13 00 13 00 11 30 CK5A CK5BW048 40 500 NONE 13 00 13 00 11...

Page 17: ... 500 TDR 13 50 13 50 12 00 CK5A CK5BT048 40 500 TDR 14 00 14 00 12 15 CK5A CK5BW048 40 500 TDR 14 00 14 00 12 15 CK5PA042 40 500 TDR TXV 13 50 12 00 CK5PA048 40 500 TDR TXV 14 00 12 15 CK5PT042 40 500 TDR TXV 13 50 12 00 CK5PT048 40 500 TDR TXV 14 00 12 15 CK5PW048 40 500 TDR TXV 14 00 12 15 COILS 58CV A X 155 22 VARIABLE SPEED FURNACE CC5A CD5AA042 40 500 TDR 13 50 13 50 12 00 CC5A CD5AC048 40 00...

Page 18: ... 40 500 TDR 13 50 13 50 11 85 CK5A CK5BA042 40 500 TDR 13 00 13 00 11 65 CK5A CK5BT042 40 500 TDR 13 00 13 00 11 65 CK5A CK5BW048 40 500 TDR 13 50 13 50 11 85 CK5PA042 40 500 TDR TXV 13 00 11 65 CK5PT042 40 500 TDR TXV 13 00 11 65 CK5PW048 40 500 TDR TXV 13 50 11 85 048 33 CC5A CD5AA060 46 500 NONE 13 00 13 00 11 50 CC5A CD5AC048 45 000 NONE 12 50 12 50 11 35 CC5A CD5AW048 46 000 NONE 13 00 13 00 ...

Page 19: ...13 50 12 10 CE3AA060 47 000 TDR 14 00 14 00 12 45 CK3BA048 46 000 TDR 13 50 13 50 12 15 CK3BA060 46 500 TDR 13 50 13 50 12 45 CK5A CK5BA048 46 000 TDR 13 50 13 50 12 15 CK5A CK5BA060 46 500 TDR 13 50 13 50 12 45 CK5A CK5BT048 46 000 TDR 13 50 13 50 12 15 CK5A CK5BT060 46 500 TDR 13 50 13 50 12 45 CK5A CK5BW048 46 000 TDR 13 50 13 50 12 15 CK5A CK5BX060 47 500 TDR 14 00 14 00 12 65 CK5PA048 46 000 ...

Page 20: ...0 11 70 CK5PX060 47 500 TDR TXV 13 50 12 05 COILS 58MVP120 20 VARIABLE SPEED FURNACE CC5A CD5AA060 46 500 TDR 13 00 13 00 11 55 CC5A CD5AW048 46 000 TDR 13 00 13 00 11 50 CC5A CD5AW060 47 000 TDR 13 50 13 50 12 00 CE3AA048 46 500 TDR 13 00 13 00 11 55 CE3AA060 47 000 TDR 13 20 13 20 11 95 CK3BA048 46 000 TDR 13 00 13 00 11 60 CK3BA060 46 500 TDR 13 00 13 00 11 80 CK5A CK5BA060 46 500 TDR 13 00 13 ...

Page 21: ...135 22 VARIABLE SPEED FURNACE CC5A CD5AA060 56 000 TDR 12 50 10 90 CD5PX060 58 000 TDR TXV 13 00 11 30 CE3AA060 58 000 TDR 13 00 11 30 CK3BA060 57 500 TDR 13 00 11 25 CK5A CK5BA060 57 500 TDR 13 00 11 25 CK5A CK5BT060 57 500 TDR 13 00 11 25 CK5A CK5BX060 58 500 TDR 13 00 11 40 CK5PA060 57 500 TDR TXV 13 00 11 25 CK5PT060 57 500 TDR TXV 13 00 11 25 CK5PX060 58 500 TDR TXV 13 00 11 40 COILS 58CV A X...

Page 22: ...y Ratio TDR Time Delay Relay TXV Thermostatic Expansion Valve NOTES 1 Ratings are net values reflecting the effects of circulating fan motor heat Supplemental electric heat is not included 2 Tested outdoor indoor combinations have been tested in accordance with DOE test procedures for central air conditioners Ratings for other combinations are determined under DOE computer simulation procedures 3 ...

Page 23: ...87 25 31 13 85 2 11 24 19 13 62 2 37 22 71 13 17 2 64 20 99 12 62 2 95 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 024 0 99 1 00 CK3BA 024 0 97 0 88 030 1 00 1 00 030 0 99 0 89 CC5A CD5AW 024 0 99 1 00 CK5A CK5BA 024 0 97 0 89 030 1 00 1 00 030 0 99 0 90 CE3AA 024 0 99 0 99 C...

Page 24: ... 2 07 19 80 19 80 2 32 18 58 18 58 2 59 17 27 17 27 2 87 67 25 15 17 80 1 64 24 64 18 20 1 85 23 38 18 01 2 09 21 84 17 50 2 35 20 17 16 86 2 63 18 42 16 15 2 91 72 25 90 13 52 1 65 25 81 13 75 1 87 25 31 13 85 2 11 24 19 13 62 2 37 22 71 13 17 2 64 20 99 12 62 2 95 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capaci...

Page 25: ...8 23 8 2 75 21 2 21 2 3 04 57 29 5 29 5 1 85 28 2 28 2 2 04 26 6 26 6 2 25 25 3 25 3 2 49 23 5 23 5 2 75 21 1 21 1 3 04 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 030 0 97 1 00 CK5A CK5BT 036 1 00 0 93 036 1 00 1 00 CK5A CK5BW 030 0 97 0 92 CC5A CD5AW 030 0 97 1 00 CK5PA 030...

Page 26: ...31 7 16 7 2 30 30 1 16 3 2 54 28 5 15 9 2 82 26 5 15 4 3 15 67 32 2 23 3 1 87 30 8 22 9 2 06 29 3 22 4 2 27 27 7 22 0 2 51 25 7 21 3 2 78 22 7 20 2 3 07 63 30 3 23 1 1 86 29 0 22 7 2 05 26 3 21 6 2 25 24 1 20 6 2 47 21 8 19 6 2 73 19 6 18 7 3 01 62 29 9 29 0 1 86 28 1 27 9 2 04 26 6 26 6 2 25 25 1 25 1 2 49 23 8 23 8 2 75 21 2 21 2 3 04 57 29 5 29 5 1 85 28 2 28 2 2 04 26 6 26 6 2 25 25 3 25 3 2 4...

Page 27: ...8 2 22 33 3 33 3 2 45 32 0 32 0 2 72 30 7 30 7 3 01 28 3 28 3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 CK5PT 036 1 00 0 94 042 1 00 1 00 COILS 58CV A X 090 16 VARIABLE SPEED FURNACE CC5A CD5AW 036 1 00 1 00 CC5A CD5AA 036 1 00 0 93 CE3AA 0...

Page 28: ...28 3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CE3AA 036 1 00 0 99 CC5A CD5AA 042 1 00 0 92 042 1 00 0 97 CC5A CD5AW 036 1 00 0 93 CK3BA 036 1 00 0 97 042 1 00 0 92 042 1 00 0 97 CE3AA 036 1 00 0 94 CK5A CK5BA 036 1 00 0...

Page 29: ... 31 1 24 1 2 66 28 3 23 0 2 93 26 0 22 0 3 24 23 3 20 9 3 56 62 34 8 32 4 2 17 32 4 31 2 2 39 30 0 29 7 2 65 27 9 27 9 2 93 26 8 26 8 3 25 24 6 24 6 3 58 57 32 7 32 7 2 15 31 0 31 0 2 38 29 9 29 9 2 64 28 7 28 7 2 94 27 3 27 3 3 25 24 8 24 8 3 58 1350 72 41 4 20 9 2 25 40 2 20 6 2 50 38 2 19 9 2 76 36 4 19 4 3 06 34 2 18 8 3 38 31 7 18 2 3 75 67 39 0 27 8 2 24 37 4 27 3 2 48 35 5 26 7 2 74 33 5 26...

Page 30: ...57 34 8 34 8 2 22 33 3 33 3 2 45 32 0 32 0 2 72 30 7 30 7 3 01 28 3 28 3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 036 1 00 1 00 COILS 58CV A X 070 12 VARIABLE SPEED FURNACE 042 1 00 1 00 CC5A CD5AA 036 0 98 0 93 CC5A CD5AW 036 1 00 1 00 CE3AA 036 0 97 0...

Page 31: ... 8 34 8 2 22 33 3 33 3 2 45 32 0 32 0 2 72 30 7 30 7 3 01 28 3 28 3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK5A CK5BE 042 0 99 0 91 CE3AA 036 0 97 0 94 CK5A CK5BT 036 0 99 0 92 042 0 99 0 93 042 0 99 0 92 CK3BA 042 0 99 0 94 CK5A CK5BW 036 0 99 0 92 CK5A CK5BA 0...

Page 32: ...8 63 36 9 27 8 2 23 34 5 26 8 2 46 31 9 25 7 2 71 29 4 24 6 2 99 26 9 23 6 3 30 24 2 22 4 3 62 62 35 8 34 5 2 22 33 2 32 9 2 45 31 1 31 1 2 70 30 0 30 0 3 00 28 6 28 6 3 32 25 8 25 8 3 65 57 34 8 34 8 2 22 33 3 33 3 2 45 32 0 32 0 2 72 30 7 30 7 3 01 28 3 28 3 3 32 25 9 25 9 3 65 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size ...

Page 33: ...7 38 9 38 5 2 83 36 5 36 5 3 13 35 4 35 4 3 49 32 7 32 7 3 86 30 7 30 7 4 29 57 40 7 40 7 2 56 39 0 39 0 2 83 37 6 37 6 3 15 35 8 35 8 3 49 33 5 33 5 3 87 30 7 30 7 4 29 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 042 1 00 1 01 CC5A CD5AC 048 0 99 0 94 CC5A CD5AC 048 0 99 1 0...

Page 34: ...0 4 24 62 41 6 40 2 2 57 38 9 38 5 2 83 36 5 36 5 3 13 35 4 35 4 3 49 32 7 32 7 3 86 30 7 30 7 4 29 57 40 7 40 7 2 56 39 0 39 0 2 83 37 6 37 6 3 15 35 8 35 8 3 49 33 5 33 5 3 87 30 7 30 7 4 29 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power COILS 58CV A X 135 22 VARIABLE SPEED FURNACE CK5PA...

Page 35: ...0 34 8 3 06 32 7 32 7 3 39 31 2 31 2 3 78 29 5 29 5 4 21 57 38 1 38 1 2 48 36 2 36 2 2 74 35 0 35 0 3 05 33 6 33 6 3 40 32 2 32 2 3 79 29 3 29 3 4 20 1575 72 47 5 23 9 2 61 46 2 23 7 2 90 44 4 23 2 3 22 41 8 22 4 3 56 39 5 21 8 3 95 36 8 21 1 4 40 67 44 9 31 9 2 58 43 0 31 5 2 86 41 1 31 1 3 18 38 8 30 3 3 53 36 3 29 6 3 92 32 0 28 0 4 32 63 42 5 32 0 2 57 40 5 31 4 2 85 37 6 30 1 3 15 35 0 29 1 3...

Page 36: ... 6 46 6 2 97 44 8 44 8 3 28 42 5 42 5 3 63 41 1 41 1 4 02 39 0 39 0 4 45 36 7 36 7 4 92 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CC5A CD5AA 060 1 00 1 00 CK3BA 048 0 99 0 95 CC5A CD5AC 048 0 97 0 98 CK5A CK5BA 048 0 99 0 95 CC5A CD5AW 048 0 99 0 99 CK5A CK5BT 048 0 99 0 95 060 1 01 0...

Page 37: ... 62 47 8 45 0 2 97 45 7 44 1 3 29 43 1 42 6 3 63 40 5 40 5 4 02 39 0 39 0 4 45 36 7 36 7 4 92 57 46 6 46 6 2 97 44 8 44 8 3 28 42 5 42 5 3 63 41 1 41 1 4 02 39 0 39 0 4 45 36 7 36 7 4 92 Multipliers for Determining the Performance With Other Indoor Sections Indoor Section Size Cooling Indoor Section Size Cooling Capacity Power Capacity Power CK5A CK5BT 048 0 99 0 94 CC5A CD5AC 048 0 97 0 99 060 1 ...

Page 38: ...22 36 14 5 52 61 05 34 63 6 06 56 50 32 98 6 63 51 36 31 14 7 25 2250 57 62 16 62 16 4 54 59 57 59 57 5 00 56 86 56 86 5 50 53 93 53 93 6 06 50 56 50 56 6 65 46 69 46 69 7 29 62 62 34 61 20 4 54 59 51 59 51 5 00 56 85 56 85 5 50 53 92 53 92 6 06 50 55 50 55 6 65 46 69 46 69 7 29 67 67 52 50 93 4 60 64 07 49 53 5 06 60 43 48 08 5 55 56 59 46 55 6 09 52 42 44 91 6 67 47 72 43 08 7 31 72 73 65 40 55 ...

Page 39: ...0 2 96 20 4 146 0 3 34 40 TCG SDT KW 36 1 76 7 1 42 34 2 86 5 1 61 32 3 96 3 1 82 30 5 106 0 2 06 28 6 116 0 2 32 26 6 126 0 2 62 24 6 136 0 2 96 22 5 146 0 3 33 45 TCG SDT KW 39 5 77 8 1 43 37 5 87 5 1 61 35 4 97 2 1 82 33 4 107 0 2 06 31 3 117 0 2 33 29 2 127 0 2 62 27 1 137 0 2 96 24 7 147 0 3 33 50 TCG SDT KW 43 1 79 2 1 44 40 9 88 8 1 63 38 7 98 4 1 83 36 5 108 0 2 07 34 3 118 0 2 33 32 0 128...

Page 40: ...2 0 2 10 47 9 82 0 2 39 45 2 92 0 2 71 42 6 102 0 3 08 39 9 112 0 3 49 37 2 122 0 3 96 34 4 132 0 4 48 31 5 142 0 5 06 40 TCG SDT KW 55 7 72 3 2 10 52 8 82 1 2 38 49 9 92 0 2 70 47 0 102 0 3 06 44 1 112 0 3 47 41 1 122 0 3 93 38 1 132 0 4 45 34 9 142 0 5 02 45 TCG SDT KW 60 9 73 6 2 13 57 8 83 2 2 40 54 7 92 7 2 71 51 7 102 0 3 06 48 6 112 0 3 46 45 4 122 0 3 91 42 1 132 0 4 42 38 5 142 0 4 99 50 ...

Page 41: ...er than 50 ft and or 20 ft vertical differential consult Residential Split System Application Guideline and Service Manual available from equipment distributor 7 If any refrigerant tubing is buried provide a 6 in vertical rise to the valve connections at the unit Refrigerant tubing lengths up to 36 in may be buried without further consideration Do not bury refrigerant lines longer than 3 ft 8 Use ...

Page 42: ...42 ...

Page 43: ...43 ...

Page 44: ...nderized and coated with a powder coat paint Fans Condenser fan will be direct drive propeller type discharging air upward Air Cooled Split System Air Conditioner 38TXA 2 to 5 Tons Nominal Condenser fan motors will be totally enclosed 1 phase type with class B insulation and permanently lubricated bearings Shafts will be corrosion resistant Fan blades will be statically and dynamically balanced Co...

Reviews: