background image

15

Table 5 – Wet Coil Air Delivery*

(Deduct 10 percent for 208 Volt Operation)

UNIT SIZE

SPEED TAP

AIR DELIVERY

2

EXTERNAL STATIC PRESSURE (in. W.C.)

0.1

0.2

0.3

0.4

0.5

0.6

0.7

0.8

0.9

1.0

024

1

SCFM

965

818

777

731

670

617

563

489

451

391

2

SCFM

1003

921

890

850

809

756

700

659

597

539

3

SCFM

1103

1068

1034

996

962

930

892

821

791

742

030

1

SCFM

1052

1018

984

943

914

879

833

795

732

678

2

SCFM

1141

1107

1069

1036

1006

974

932

899

856

784

3

SCFM

1246

1213

1181

1144

1108

1078

1043

1015

973

931

036

1

SCFM

1281

1225

1178

1142

1098

1053

1008

935

878

840

2

SCFM

1359

1321

1278

1236

1201

1160

1109

1068

992

941

3

SCFM

1476

1441

1403

1366

1323

1289

1245

1201

1159

1117

042

1

SCFM

1453

1408

1373

1337

1295

1255

1215

1177

1134

1068

2

SCFM

1544

1507

1475

1436

1397

1359

1326

1290

1246

1201

3

SCFM

1614

1575

1542

1509

1467

1430

1395

1358

1323

1267

048

1

SCFM

1657

1625

1590

1554

1517

1486

1448

1417

1381

1340

2

SCFM

1707

1673

1644

1614

1586

1549

1515

1479

1449

1407

3

SCFM

1931

1900

1870

1840

1809

1778

1749

1714

1683

1646

060

1

SCFM

1837

1798

1753

1716

1677

1637

1590

1549

1497

1445

2

SCFM

1910

1872

1835

1795

1748

1711

1673

1623

1568

1525

3

SCFM

2098

2065

2032

1996

1956

1917

1877

1839

1798

1753

*Air delivery values are based on operating voltage of 230v, wet coil, without filter or electric heater. Deduct filter and electric heater pressure drops to obtain

static pressure available for ducting.

NOTES:

1. Do not operate the unit at a cooling airflow that is less than 350 cfm for each 12,000 Btuh of rated cooling capacity. Evaporator coil frosting may occur at air-

flows below this point.

2. Standard Cubic Feet per Minute.

CONTINUOUS FAN
With the continuous Indoor fan option selected on the thermostat,

G is continuously energized. The continuous fan speed will be the
same as the cooling fan speed.
ELECTRIC RESISTANCE HEATING
If accessory electric heaters are installed, the thermostat energizes
W, which energizes the heater relay and in turn energizes the

electric heaters. The thermostat terminal G must be energized
which starts the indoor--fan motor. If the heaters are staged, W2 is

energized when the second stage of heating is required. When the

need for heating is satisfied, the heater and IFM are de--energized.

MAINTENANCE

To ensure continuing high performance, and to minimize the

possibility of premature equipment failure, periodic maintenance
must be performed on this equipment. This cooling unit should be

inspected at least once each year by a qualified service person. To
troubleshoot unit, refer to Table 9, Troubleshooting Chart.
NOTE TO EQUIPMENT OWNER: Consult your local dealer

about the availability of a maintenance contract.

PERSONAL

INJURY

AND

UNIT

DAMAGE

HAZARD

Failure to follow this warning could result in personal

injury or death and possible unit component damage.
The ability to properly perform maintenance on this

equipment requires certain expertise, mechanical skills,

tools and equipment. If you do not possess these, do not

attempt to perform any maintenance on this equipment,

other than those procedures recommended in the Owner’s

Manual.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
1. Turn off electrical power to the unit and install lockout

tag before performing any maintenance or service on this

unit.
2. Use extreme caution when removing panels and parts.
3. Never place anything combustible either on or in contact

with the unit.

!

WARNING

UNIT OPERATION HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Errors made when reconnecting wires may cause improper

and dangerous operation. Label all wires prior to

disconnecting when servicing.

!

CAUTION

The minimum maintenance requirements for this equipment are as
follows:

1. Inspect air filter(s) each month. Clean or replace when

necessary.

2. Inspect indoor coil, drain pan, and condensate drain each

cooling season for cleanliness. Clean when necessary.

3. Inspect blower motor and wheel for cleanliness each

cooling season. Clean when necessary.

4. Check electrical connections for tightness and controls for

proper operation each cooling season. Service when
necessary.

5. Ensure electric wires are not in contact with refrigerant

tubing or sharp metal edges.

Air Filter

IMPORTANT

: Never operate the unit without a suitable air filter

in the return--air duct system. Always replace the filter with the
same dimensional size and type as originally installed. See Table 1
for recommended filter sizes.

PA

3Z

B

Summary of Contents for PA3Z-B

Page 1: ...round Lead to Unit Ground 8 Routing Control Power Wires 8 Accessory Electric Heat Wiring 8 PRE START UP 8 START UP 9 15 Check for Refrigerant Leaks 9 Start Up Cooling and Make Adjustments 9 Checking Cooling and Heating Control Operation 9 Refrigerant Charge 11 No Charge 11 Low Charge Cooling 11 Indoor Airflow and Airflow Adjustments 11 Sequence of Operation 11 Fan Operation 11 Cooling Operation 11...

Page 2: ...plications with a field supplied plenum RECEIVING AND INSTALLATION Step 1 Check Equipment IDENTIFY UNIT The unit model number and serial number are printed on the unit informative plate Check this information against shipping papers INSPECT SHIPMENT Inspect for shipping damage while unit is still on shipping pallet If unit appears to be damaged or is torn loose from its anchorage have it examined ...

Page 3: ...eater element 3 Size ductwork for cooling air quantity cfm The minimum air quantity for proper electric heater operation is listed in Table 2 Heater limit switches may trip at air quantities below those recommended 4 Seal insulate and weatherproof all external ductwork Seal insulate and cover with a vapor barrier all ductwork passing through conditioned spaces Follow latest Sheet Metal and Air Con...

Page 4: ...DE OF UNIT WITH DUCT OPENINGS 0 0 REQUIRED CLEARNACE FOR SERVICING TOP OF UNIT 36 0 914 SIDE OF UNIT OPPOSITE DUCT OPENINGS 30 0 762 SIDE OF UNIT WITH POWER ENTRY 30 0 762 EXCEPT FOR NEC REQUIREMENTS NOTE CLEARANCES MUST BE MAINTAINED TO PREVENT RECIRCULATION OF AIR FROM OUTDOOR FAN DISCHARGE A REMOVABLE FENCE OR BARRICADE REQUIRES NO CLEARANCE DIMENSIONS IN ARE IN MM A10295 Fig 4 Unit Base Dimens...

Page 5: ... UNIT WITH DUCT OPENINGS 0 0 REQUIRED CLEARANCE FOR SERVICING INCHES MM TOP OF UNIT 36 0 914 SIDE OF UNIT OPPOSITE DUCT OPENINGS 30 0 762 SIDE OF UNIT WITH POWER ENTRY 30 0 762 EXCEPT FOR NEC REQUIREMENTS NOTE CLEARANCES MUST BE MAINTAINED TO PREVENT RECIRCULATION OF AIR FROM OUTDOOR FAN DISCHARGE A REMOVABLE FENCE OR BARRICADE REQUIRES NO CLEARANCE DIMENSIONS IN ARE IN MM A10296 Fig 5 Unit Base D...

Page 6: ...050 2700 20 508 1 4 1050 2700 20 508 1 4 1050 3000 20 508 1 3 1100 INDOOR COIL ROWS FINS in FACE AREA sq ft 2 12 4 3 3 12 4 3 3 12 4 3 3 12 4 9 3 12 4 9 3 12 6 1 INDOOR BLOWER NOMINAL COOLING AIRFLOW cfm SIZE L x D in mm MOTOR HP 800 8 x 11 203 x 279 1 3 1000 8 x 11 203 x 279 1 3 1200 9 5 x 12 241 x 305 1 2 1400 9 5 x 12 241 x 305 1 2 1600 9 5 x 12 241 x 305 3 4 1750 10 5 x 12 267 x 305 1 HIGH PRE...

Page 7: ...y of personal injury if an electrical fault should occur This ground may consist of an electrical wire connected to the unit ground screw in the control compartment or conduit approved for electrical ground when installed in accordance with NEC ANSI NFPA 70 American National Standards Institute National Fire Protection Association latest edition in Canada Canadian Electrical Code CSA C22 1 and loc...

Page 8: ...oad resistor wired across low voltage leads G and C Purpose of resistor is to provide a small electrical load for the indoor thermostat fan circuit to ensure reliable operation ACCESSORY ELECTRIC HEAT WIRING Refer to accessory electric heat installation instructions for information on installing accessory electric heat Accessory electric heat wiring is shown in Fig 14 PRE START UP FIRE EXPLOSION E...

Page 9: ... practices NOTE Install a filter drier whenever the system has been opened for repair 3 Add a small charge of R 410A refrigerant vapor to system and leak test unit 4 Recover refrigerant from system and evacuate to 500 microns if no additional leaks are found 5 Charge unit with R 410A refrigerant using an accurate scale Refer to unit rating plate for required charge Step 2 Start Up Cooling and Make...

Page 10: ...10 Table 3 Superheat Charging A10038 Table 4 Required Subcooling A10039 PA3ZB ...

Page 11: ...efer to the required subcooling in Table 4 to find the required subcooling based on the model type and the outdoor ambient temperature 5 Interpolate if the outdoor temperature lies in between the table values 6 Find the pressure value corresponding to the measured pressure on the compressor discharge line 7 Read across from the pressure reading to obtain the Liquid line temperature for a required ...

Page 12: ...12 ACCESSORY ELECTRIC HEAT 24 VOLT THERMOSTAT CONNECTIONS 24 VOLT THERMOSTAT CONNECTIONS THERMOSTAT WIRES A10024C Fig 13 Typical Single Phase Connection Electrical Diagram PA3ZB ...

Page 13: ...13 24 VOLT THERMOSTAT CONNECTIONS A10024L Fig 13 Cont Typical Single Phase Ladder Electrical Diagram PA3ZB ...

Page 14: ...14 A10025 Fig 14 Single Phase Accessory Electric Heater Wiring PA3ZB ...

Page 15: ...ired When the need for heating is satisfied the heater and IFM are de energized MAINTENANCE To ensure continuing high performance and to minimize the possibility of premature equipment failure periodic maintenance must be performed on this equipment This cooling unit should be inspected at least once each year by a qualified service person To troubleshoot unit refer to Table 9 Troubleshooting Char...

Page 16: ... 1 Remove the blower housing a Remove the screws on the external side of the duct panel that fasten the housing to the duct panel assembly b Remove the side access panel and unscrew the mounting bracket that fastens the blower housing to the internal partition panel of the control box assembly c Make sure that the blower housing is supported by hand before completely removing the mounting bracket ...

Page 17: ...lash water on the insulation motor wiring or air filter s If the drain trough is restricted clear it with a plumbers snake or similar probe device Outdoor Fan Adjustment UNIT OPERATION HAZARD Failure to follow this caution may result in damage to unit components Keep the condenser fan free from all obstructions to ensure proper cooling operation Never place articles on top of unit CAUTION 1 Shut o...

Page 18: ...xtreme caution when working near compressors Power should be shut off if possible for most troubleshooting techniques Refrigerants present additional safety hazards EXPLOSION HAZARD Failure to follow this warning could result in personal injury or death and or property damage Wear safety glasses and gloves when handling refrigerants Keep torches and other ignition sources away from refrigerants an...

Page 19: ...ry cloth shop towel inside unit immediately under component s to be serviced and prevent lubricant run offs through the louvered openings in the unit base 4 Perform required service 5 Remove and dispose of any oil contaminated material per local codes Liquid Line Filter Drier The filter drier is specifically designed to operate with R 410A Use only factory authorized components Filter drier must b...

Page 20: ...imum 700 psig service pressure rating S Leak detectors should be designed to detect HFC refrigerant S R 410A as with other HFCs is only compatible with POE PVE oils S Vacuum pumps will not remove moisture from oil S Only use factory specified liquid line filter driers with rated working pressures no less than 600 psig S Do not install a suction line filter drier in liquid line S POE PVE oils absor...

Page 21: ...use and replace Faulty outdoor fan motor or capacitor Replace Restriction in refrigerant system Locate restriction and remove Compressor operates continuously Dirty air filter Replace filter Unit undersized for load Decrease load or increase unit size Thermostat temperature set too low Reset thermostat setting Low refrigerant charge Locate leak repair and recharge Air in system Recover refrigerant...

Page 22: ...N IN HOUSING ORIFICE AND SETSCREW TIGHTNESS III START UP ELECTRICAL SUPPLY VOLTAGE COMPRESSOR AMPS INDOOR EVAPORATOR FAN AMPS TEMPERATURES OUTDOOR CONDENSER AIR TEMPERATURE DB RETURN AIR TEMPERATURE DB WB COOLING SUPPLY AIR DB WB PRESSURES REFRIGERANT SUCTION PSIG SUCTION LINE TEMP REFRIGERANT DISCHARGE PSIG LIQUID TEMP VERIFY REFRIGERANT CHARGE USING CHARGING CHARTS Measured at suction inlet to c...

Reviews: