Carrier PA17NA Installation Instructions Manual Download Page 4

4

Table 2 – Accessory Usage

ACCESSORY

REQUIRED FOR LONG LINE

APPLICATIONS*

REQUIRED FOR

SEA COAST

APPLICATIONS

(Within 2 miles/3.22 km)

Compressor Start Assist Capacitor and Relay

Yes

No

Crankcase Heater

Yes

(standard on some units)

No

Hard Shut---Off TXV

Yes

(Standard with factory---approved indoor unit)

Yes

Support Feet

No

Recommended

* For tubing line sets between 80 and 200 ft. (24.38 and 60.96 m) and/or 35 ft. (10.7 m) vertical differential, refer to Residential Split---System Longline

Application Guideline.

Make Electrical Connections

Be sure field wiring complies with local and national fire, safety,
and electrical codes, and voltage to system is within limits shown

on unit rating plate. Contact local power company for correction of

improper voltage. See unit rating plate for recommended circuit
protection device.

NOTE

: Operation of unit on improper line voltage constitutes

abuse and could affect unit reliability. See unit rating plate. Do not
install unit in system where voltage may fluctuate above or below
permissible limits.

NOTE

: Use copper wire only between disconnect switch and unit.

NOTE

: Install branch circuit disconnect of adequate size per NEC

to handle unit starting current. Locate disconnect within sight from
and readily accessible from unit, per Section 440--14 of NEC.

Route Ground and Power Wires

Remove access panel to gain access to unit wiring. Extend wires
from disconnect through power wiring hole provided and into unit

control box.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal injury or

death.
The unit cabinet must have an uninterrupted or unbroken

ground to minimize personal injury if an electrical fault should

occur. The ground may consist of electrical wire or metal

conduit when installed in accordance with existing electrical

codes.

Connect Ground and Power Wires

Connect ground wire to ground connection in control box for

safety. Connect power wiring to contactor as shown in Fig. 5.

DISCONNECT
PER N.E.C. AND/OR
LOCAL CODES

CONTACTOR

GROUND
LUG

FIELD GROUND

WIRING

FIELD POWER

WIRING

BLUE

3 PHASE ONLY

A91056

Fig. 5 -- Line Power Connections

Connect Control Wiring

Route 24--v control wires through control wiring grommet and

connect leads to control wiring (See Fig. 7). Refer to Installation

Instructions packaged with thermostat.
Use No. 18 AWG color--coded, insulated (35

_

C minimum) wire. If

thermostat is located more than 100 ft. (30.48 m) from unit, as
measured along the control voltage wires, use No. 16 AWG

color--coded wire to avoid excessive voltage drop.

All wiring must be NEC Class 1 and must be separated from
incoming power leads.
Use furnace transformer, fan coil transformer, or accessory
transformer for control power, 24v/40va minimum.

NOTE

:

Use of available 24v accessories may exceed the

minimum 40va power requirement. Determine total transformer
loading and increase the transformer capacity or split the load with
an accessory transformer as required.

Final Wiring Check

IMPORTANT

: Check factory wiring and field wire connections

to ensure terminations are secured properly. Check wire routing to
ensure wires are not in contact with tubing, sheet metal, etc.

Compressor Crankcase Heater

When equipped with a crankcase heater, furnish power to heater a
minimum of 24 hr before starting unit. To furnish power to heater

only, set thermostat to OFF and close electrical disconnect to
outdoor unit.
A crankcase heater is required if refrigerant tubing is longer than

80 ft. (24.38 m). Refer to the Application Guideline and Service
Manual

Longline

Section--Residential

Split--System

Air

Conditioners and Heat Pumps.

Airflow Selections (ECM Furnaces)

The ECM Furnaces provide blower operation to match the

capacities of the compressor during high and low stage cooling

operation. Tap selections on the furnace control board enable the
installing technician to select the proper airflows for each stage of

cooling. Below is a brief summary of the furnace airflow
configurations

1. The Y2 call for high stage cooling energizes the “Cool” tap

on the control board. The grey wire from cool tap is connec-

ted to tap 5 on the motor. Refer to the furnace Product Data
to find the corresponding airflow. If the airflow setting for

high cooling needs to be switched from tap 5 to a different
tap, jumper a connection from the cool tap to the desired tap
so that the Y2 signal is communicated via the cool tap to the

desired speed tap.

2. The Y1 call for low stage cooling energizes the “Fan” tap

on the control board. The red wire from the fan tap is con-
nected to tap 1 on the motor. Refer to the furnace Product
Data to find the corresponding airflow. If the airflow setting

for low cooling needs to be switched from tap 1 to a differ-
ent tap, jumper a connection from the Fan tap to the desired

tap so that the Y1 signal is communicated via the Fan tap to
the desired speed tap. The Y1 setting will also govern the

continuous fan airflow for the furnace.

Refer to the literature for the furnace for further details.

PA

17N

A

Summary of Contents for PA17NA

Page 1: ...electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 ...

Page 2: ... 12 78_C and the maximum outdoor operating ambient in cooling mode is 125_F 51 67_C when operating voltage is 230v For 208v applications the maximum outdoor ambient is 120_F NOTE Units operating at high stage operation 208v or below line voltage and at an outdoor ambient 120_F or greater may experience compressor trip Make Piping Connections WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure...

Page 3: ... Pumps using R 410A refrigerant Install Liquid Line Filter Drier Indoor CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation 1 Installation of filter drier in liquid line is required 2 Filter drier must be wrapped in a heat sinking material such as a wet cloth while brazing Refer to Fig 3 and install filter drier as follows 1 Braze 5 in liq...

Page 4: ...than 100 ft 30 48 m from unit as measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power require...

Page 5: ...et point is below indoor ambient temperature and is set low enough to energize desired stage In order to start the system in low stage refer to the literature for the installed thermo stat and adjust the set point so that the differential between the room temperature and the set temperature energizes Y1 5 Set room thermostat to COOL and fan control to ON or AUTO mode as desired 6 Operate unit for ...

Page 6: ... periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file TROUBLESHOOTING If the compressor fails to operate with a cooling call the table below Resistance table can be used to verify if there is any damage to the compressor windings causing system malfunction Table 3 Winding Resistance Winding Winding resistance at 70_F 20_F 21 11_C ...

Page 7: ...as a 24 volt coil and is controlled by Y1 input from the thermostat High and Low Pressure Switches High and low pressure switches are provided in line with the Y1 signal to the contactor for protection The high pressure switch mounted on the liquid tube is set to open at 670 psi and higher and the low pressure switch mounted on the suction tube opens at a pressure of 50 psi and lower CARE AND MAIN...

Page 8: ...Two Stage Air Conditioner Thermidistat Variable Speed Fan Coil TWO STAGE AIR CONDITIONER THERMIDISTAT Thermidistat w Variable Speed Fan Coil 2 Stage Air Conditioner Thermidistat w Variable Speed Furnace 2 Stage Air Conditioner Fig 6 Thermidistat Wiring with 2 Stage R 410A refrigerant Air Conditioner A09278 Single Stage Furnace with 2 Stage Air Conditioner A09279 2 Stage Thermostat with Single Stag...

Page 9: ... filter driers with rated working pressures less than 600 psig S Do not leave R 410A suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth whe...

Page 10: ...ing S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM PA17NA 02 Replaces IM PA17NA 01 Edition Date 09 12 PA17NA ...

Reviews: