Outdoor Unit Connected to Factory Approved Indoor

Unit

Outdoor unit contains correct system refrigerant charge for

operation with factory approved AHRI rated indoor unit when
connected by 15 ft. (4.57 m) of field--supplied or factory--accessory

tubing, and factory supplied filter drier. Check refrigerant charge
for maximum efficiency.

Refrigerant Tubing Connection Outdoor

Connect vapor and liquid tubes to fittings on vapor and liquid

service valves (see Table 1.) Use refrigerant grade tubing

Sweat Connection

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Service valves must be wrapped in a heat--sinking material

such as a wet cloth while brazing.

Use refrigeration grade tubing. Service valves are closed from
factory and ready for brazing. After wrapping service valve with a

wet cloth, braze sweat connections using industry accepted

methods and materials. Consult local code requirements.
Refrigerant tubing and indoor coil are now ready for leak testing.

This check should include all field and factory joints.

Table 1 – Refrigerant Connections and Recommended Liquid

and Vapor Tube Diameters (In.)

UNIT SIZE

(SERIES)

LIQUID

RATED VAPOR*

Connection

& Max. Tube

Diameter

Connection

Diameter

Tube

Diameter

24

3/8

3/4

3/4

36

3/8

7/8

7/8

48

3/8

7/8

1---1/8

60

3/8

7/8

1---1/8

* Units are rated with 25 ft. (7.6 m) of lineset. See Product Data sheet for

performance data when using different size and length linesets.

Notes

:

1. Do not apply capillary tube or fixed orifice indoor coils to these units.
2. For Tubing Set lengths between 80 and 200 ft. (24.38 and 60.96 m)

horizontal or 35 ft. (10.7 m) vertical differential 250 ft. (76.2 m) Total

Equivalent Length), refer to the Residential Piping and Longline Guide

line--- Air Conditioners and Heat Pumps using R---410A refrigerant.

Install Liquid--Line Filter Drier Indoor

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
1. Installation of filter drier in liquid line is required.
2. Filter drier must be wrapped in a heat--sinking material

such as a wet cloth while brazing.

Refer to Fig. 3 and install filter drier as follows:

1. Braze 5--in. liquid tube to the indoor coil.
2. Wrap filter drier with damp cloth.
3. Braze filter drier to above 5--in. (127 mm) liquid tube.

Flow arrow must point towards indoor coil.

4. Connect and braze liquid refrigerant tube to the filter drier.

A05178

Fig. 3 -- Liquid Line Filter Drier

Evacuate Refrigerant Tubing and Indoor Coil

CAUTION

!

UNIT DAMAGE HAZARD

Failure to follow this caution may result in equipment

damage or improper operation.
Never use the system compressor as a vacuum pump.

Refrigerant tubes and indoor coil should be evacuated using the

recommended deep vacuum method of 500 microns. The alternate
triple evacuation method may be used (see triple evacuation

procedure in service manual). Always break a vacuum with dry
nitrogen.

Deep Vacuum Method

The deep vacuum method requires a vacuum pump capable of

pulling a vacuum of 500 microns and a vacuum gage capable of
accurately measuring this vacuum depth. The deep vacuum method

is the most positive way of assuring a system is free of air and
liquid water. A tight dry system will hold a vacuum of 1000

microns after approximately 7 minutes. See Fig. 4.

500

MINUTES

0

1

2

3

4

5

6

7

1000

1500

LEAK IN

SYSTEM

VACUUM TIGHT

TOO WET
TIGHT

DRY SYSTEM

2000

MI

CRONS

2500

3000

3500

4000

4500

5000

A95424

A95424

Fig. 4 -- Deep Vacuum Graph

Final Tubing Check

IMPORTANT

: Check to be certain factory tubing on both indoor

and outdoor unit has not shifted during shipment. Ensure tubes are
not rubbing against each other or any sheet metal or wires. Pay
close attention to feeder tubes, making sure wire ties on feeder
tubes are secure and tight.

PA

17N

A

Summary of Contents for PA17NA

Page 1: ...electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 ...

Page 2: ... 12 78_C and the maximum outdoor operating ambient in cooling mode is 125_F 51 67_C when operating voltage is 230v For 208v applications the maximum outdoor ambient is 120_F NOTE Units operating at high stage operation 208v or below line voltage and at an outdoor ambient 120_F or greater may experience compressor trip Make Piping Connections WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure...

Page 3: ... Pumps using R 410A refrigerant Install Liquid Line Filter Drier Indoor CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation 1 Installation of filter drier in liquid line is required 2 Filter drier must be wrapped in a heat sinking material such as a wet cloth while brazing Refer to Fig 3 and install filter drier as follows 1 Braze 5 in liq...

Page 4: ...than 100 ft 30 48 m from unit as measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power require...

Page 5: ...et point is below indoor ambient temperature and is set low enough to energize desired stage In order to start the system in low stage refer to the literature for the installed thermo stat and adjust the set point so that the differential between the room temperature and the set temperature energizes Y1 5 Set room thermostat to COOL and fan control to ON or AUTO mode as desired 6 Operate unit for ...

Page 6: ... periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file TROUBLESHOOTING If the compressor fails to operate with a cooling call the table below Resistance table can be used to verify if there is any damage to the compressor windings causing system malfunction Table 3 Winding Resistance Winding Winding resistance at 70_F 20_F 21 11_C ...

Page 7: ...as a 24 volt coil and is controlled by Y1 input from the thermostat High and Low Pressure Switches High and low pressure switches are provided in line with the Y1 signal to the contactor for protection The high pressure switch mounted on the liquid tube is set to open at 670 psi and higher and the low pressure switch mounted on the suction tube opens at a pressure of 50 psi and lower CARE AND MAIN...

Page 8: ...Two Stage Air Conditioner Thermidistat Variable Speed Fan Coil TWO STAGE AIR CONDITIONER THERMIDISTAT Thermidistat w Variable Speed Fan Coil 2 Stage Air Conditioner Thermidistat w Variable Speed Furnace 2 Stage Air Conditioner Fig 6 Thermidistat Wiring with 2 Stage R 410A refrigerant Air Conditioner A09278 Single Stage Furnace with 2 Stage Air Conditioner A09279 2 Stage Thermostat with Single Stag...

Page 9: ... filter driers with rated working pressures less than 600 psig S Do not leave R 410A suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth whe...

Page 10: ...ing S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM PA17NA 02 Replaces IM PA17NA 01 Edition Date 09 12 PA17NA ...

Reviews: