Installation Instructions

PA17NA

SPLIT--SYSTEM, 2--STAGE AIR CONDITIONER

WITH R--410A REFRIGERANT

2 -- 5 TONS

NOTE

: Read the entire instruction manual before starting the

installation.

SAFETY CONSIDERATIONS

Improper installation, adjustment, alteration, service, maintenance,
or use can cause explosion, fire, electrical shock, or other

conditions which may cause death, personal injury, or property
damage. Consult a qualified installer, service agency, or your

distributor or branch for information or assistance. The qualified

installer or agency must use factory--authorized kits or accessories
when modifying this product. Refer to the individual instructions

packaged with the kits or accessories when installing.
Follow all safety codes. Wear safety glasses, protective clothing,

and work gloves. Use quenching cloth for brazing operations.
Have fire extinguisher available. Read these instructions

thoroughly and follow all warnings or cautions included in

literature and attached to the unit. Consult local building codes and
current editions of the National Electrical Code ( NEC ) NFPA 70.

In Canada, refer to current editions of the Canadian electrical code
CSA 22.1.

Recognize safety information. This is the safety--alert symbol

!

!

.

When you see this symbol on the unit and in instructions or
manuals, be alert to the potential for personal injury. Understand

these signal words; DANGER, WARNING, and CAUTION. These

words are used with the safety--alert symbol. DANGER identifies
the most serious hazards which

will

result in severe personal injury

or death. WARNING signifies hazards which

could

result in

personal injury or death. CAUTION is used to identify unsafe

practices which

would

result in minor personal injury or product

and property damage. NOTE is used to highlight suggestions
which

will

result in enhanced installation, reliability, or operation.

!

WARNING

ELECTRICAL SHOCK HAZARD

Failure to follow this warning could result in personal

injury or death.
Before installing, modifying, or servicing system, main

electrical disconnect switch must be in the OFF position.

There may be more than 1 disconnect switch. Lock out and

tag switch with a suitable warning label.

INSTALLATION RECOMMENDATIONS

NOTE

: In some cases noise in the living area has been traced to

gas pulsations from improper installation of equipment.

1. Locate unit away from windows, patios, decks, etc. where

unit operation sound may disturb customer.

2. Ensure that vapor and liquid tube diameters are appropriate

for unit capacity.

3. Run refrigerant tubes as directly as possible by avoiding un-

necessary turns and bends.

4. Leave some slack between structure and unit to absorb vi-

bration.

5. When passing refrigerant tubes through the wall, seal open-

ing with RTV or other pliable silicon--based caulk. (See Fig.
1.)

6. Avoid direct tubing contact with water pipes, duct work,

floor joists, wall studs, floors, and walls.

7. Do not suspend refrigerant tubing from joists and studs with

a rigid wire or strap which comes in direct contact with
tubing.(See Fig. 1.)

8. Ensure that tubing insulation is pliable and completely sur-

rounds vapor tube.

9. When necessary, use hanger straps which are 1 in. (25.4

mm) wide and conform to shape of tubing insulation. (See
Fig. 1.)

10. Isolate hanger straps from insulation by using metal sleeves

bent to conform to shape of insulation.

INSULATION

SUCTION TUBE

LIQUID TUBE

OUTDOOR WALL

INDOOR WALL

LIQUID TUBE

SUCTION TUBE

INSULATION

CAULK

HANGER STRAP

(AROUND SUCTION

TUBE ONLY)

JOIST

1” (25.4 mm)

 MIN

THROUGH THE WALL

SUSPENSION

A07588

Fig. 1 -- Connecting Tubing Installation

The outdoor unit contains system refrigerant charge for operation

with AHRI rated indoor unit when connected by 15 ft. (4.57 m) of
field--supplied or factory accessory tubing. For proper unit

operation, check refrigerant charge using charging information
located on control box cover and/or in the Check Charge section of

this instruction.

IMPORTANT

: Maximum liquid--line size is 3/8--in. OD for all

residential applications including long line.

IMPORTANT

: Always install the factory--supplied liquid--line

filter drier. If replacing the filter drier, refer to Product Data Digest
for appropriate part number. Obtain replacement filter driers from
your distributor or branch.

Summary of Contents for PA17NA

Page 1: ...electrical disconnect switch must be in the OFF position There may be more than 1 disconnect switch Lock out and tag switch with a suitable warning label INSTALLATION RECOMMENDATIONS NOTE In some cases noise in the living area has been traced to gas pulsations from improper installation of equipment 1 Locate unit away from windows patios decks etc where unit operation sound may disturb customer 2 ...

Page 2: ... 12 78_C and the maximum outdoor operating ambient in cooling mode is 125_F 51 67_C when operating voltage is 230v For 208v applications the maximum outdoor ambient is 120_F NOTE Units operating at high stage operation 208v or below line voltage and at an outdoor ambient 120_F or greater may experience compressor trip Make Piping Connections WARNING PERSONAL INJURY AND ENVIRONMENTAL HAZARD Failure...

Page 3: ... Pumps using R 410A refrigerant Install Liquid Line Filter Drier Indoor CAUTION UNIT DAMAGE HAZARD Failure to follow this caution may result in equipment damage or improper operation 1 Installation of filter drier in liquid line is required 2 Filter drier must be wrapped in a heat sinking material such as a wet cloth while brazing Refer to Fig 3 and install filter drier as follows 1 Braze 5 in liq...

Page 4: ...than 100 ft 30 48 m from unit as measured along the control voltage wires use No 16 AWG color coded wire to avoid excessive voltage drop All wiring must be NEC Class 1 and must be separated from incoming power leads Use furnace transformer fan coil transformer or accessory transformer for control power 24v 40va minimum NOTE Use of available 24v accessories may exceed the minimum 40va power require...

Page 5: ...et point is below indoor ambient temperature and is set low enough to energize desired stage In order to start the system in low stage refer to the literature for the installed thermo stat and adjust the set point so that the differential between the room temperature and the set temperature energizes Y1 5 Set room thermostat to COOL and fan control to ON or AUTO mode as desired 6 Operate unit for ...

Page 6: ... periodic maintenance requirements outlined in manual 5 Fill out Dealer Installation Checklist and place in customer file TROUBLESHOOTING If the compressor fails to operate with a cooling call the table below Resistance table can be used to verify if there is any damage to the compressor windings causing system malfunction Table 3 Winding Resistance Winding Winding resistance at 70_F 20_F 21 11_C ...

Page 7: ...as a 24 volt coil and is controlled by Y1 input from the thermostat High and Low Pressure Switches High and low pressure switches are provided in line with the Y1 signal to the contactor for protection The high pressure switch mounted on the liquid tube is set to open at 670 psi and higher and the low pressure switch mounted on the suction tube opens at a pressure of 50 psi and lower CARE AND MAIN...

Page 8: ...Two Stage Air Conditioner Thermidistat Variable Speed Fan Coil TWO STAGE AIR CONDITIONER THERMIDISTAT Thermidistat w Variable Speed Fan Coil 2 Stage Air Conditioner Thermidistat w Variable Speed Furnace 2 Stage Air Conditioner Fig 6 Thermidistat Wiring with 2 Stage R 410A refrigerant Air Conditioner A09278 Single Stage Furnace with 2 Stage Air Conditioner A09279 2 Stage Thermostat with Single Stag...

Page 9: ... filter driers with rated working pressures less than 600 psig S Do not leave R 410A suction line filter driers in line longer than 72 hours S Do not install a suction line filter drier in liquid line S POE oils absorb moisture rapidly Do not expose oil to atmosphere S POE oils may cause damage to certain plastics and roofing materials S Wrap all filter driers and service valves with wet cloth whe...

Page 10: ...ing S 7310 W Morris St S Indianapolis IN 46231 Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations Catalog No IM PA17NA 02 Replaces IM PA17NA 01 Edition Date 09 12 PA17NA ...

Reviews: