Advanced Setup
II
INSTALLATION
Press
Press
Press
Press the Fan button
for 10 seconds to enter
these Setup screens.
NOTE:
Each step’s description is
located at
corner of the
easy reference.
the top right
display for
FAN
FAN
FAN
FAN
Adjust the minimum
temperature setpoint
that is used when the
thermostat indicates
OFF
.
Heat will come on when the
temperature falls below this
setpoint.
Select the cycles per
hour limit.
d=cycles per hour
limit defeated.
(d, 2 - 6)
Default = 6 cycles / hour
Default = 2 degrees
Default = 60 degrees
Adjust the deadband
from 1 - 6 degrees F.
Deadband is the difference
between Room temperature
& setpoint before the
equipment will turn on.
This step only appears in compressor equipped systems.
CYCLES/HOUR
DEADBAND
OFF MIN SETPOINT
6
2
60
Note: Set the thermostat to ‘OFF’ mode before adjusting settings.
Continued
Page 6
TO SET PRESS, OR
TO SET PRESS, OR
TO SET PRESS, OR
The purpose of d1 is to allow the installing technician
to override the thermostats 5 minute compressor lockout.
After installation is complete this setting should be set between
d and 6 cycles per hour.
This feature prevents rooms from getting to hot or too cold
when heating or cooling is turned off.