FN1AAF: Operation and Maintenance Manual

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

4

5. Locate  the  three  blower  speed  tap  wires  (red,  blue,  and  gray)

attached to the blower motor (

Fig. 6

).

6. Identify the correct Motor Tap for desired airflows and connect the

wires according to 

Table 1

.

– The Red motor lead is energized when switch is set to LOW, the

Blue motor lead is energized when switch is set to MED.

NOTE: 

The Blue and Gray motor leads are energized when switch is set

to HIGH. The 

Gray lead should remain on Motor Tap 5 

in order to

assure  that  red  filter/obstruction  indicator  is  properly  detecting  filter

condition.

A200258

Fig. 6 – Motor Taps

7. Replace the top door screws.
8. Tighten the bottom door screws.

Table 1 – Blower Configuration

Altitude Adjustments

Depending  on  your  location,  you  may  see  up  to  10%  increase  of

measured  airflow  at  higher  altitudes. To  compensate,  you  can  change

motor taps for alternate airflows 

(Airflow Adjustments on p3)

.

Troubleshooting

Before  you  request  dealer  service,  check  for  these  easily  solved

problems: 

• Check your main electrical panel circuit breakers or fuses if the unit

will not turn on.

• Make sure the unit is plugged in to a working 115V electrical outlet.

• Check for sufficient airflow. Filters should be clean and unobstructed.
If you need to contact your authorized dealer for troubleshooting and/or

repairs, be sure to have the model and serial numbers of your equipment

available.

Specifications

A200223

Fig. 7 – 005 Model Wiring Diagram

A200258

Fig. 8 – 015 Model Wiring Diagram

Switch Setting

Motor Lead

Motor Tap Options

LOW

Red

1
2
3

Switch Setting

Motor Lead

Motor Tap Options

MED

Blue

2
3
4

Switch Setting

Motor Lead

Motor Tap Options

HIGH

Gray

5

Table 2 – Electrical Specifications

005 Model

015 Model

Voltage

115

Hertz

60

Amps

5.0

12.0

Speeds

*

*.

005 model

 has a green lighted power switch only; wired to tap 5 from 

the factory.

015 model

 has the green lighted power switch, plus 3-speed rotary 

switch; wired to taps 1, 3, and 5 from the factory. Taps 2 and 4 can be 

field-wired for alternative CFMs. See 

(Airflow Adjustments on p3)

1

3

Nominal CFM

500

500 / 1000 / 1500

BRN 

BLK - L

YEL

 - N

GRN/YEL

 - GND

BLU - 3

FM

TRAN

115V

FILTER

LIGHT

DIFFERENTIAL

PRESSURE

SWITCH

C

R

2

1

2a

1a

N

L1

POWER PLUG

LIGHTED

POWER SWITCH

24V

BRN - C 
BLK - L

YEL - N

GRN/YEL - GND

BLU - Medium

FM

GRY - High

RED - Low

C L G N

1

2

3 4 5

MOTOR CONNECTOR

TRAN

115V

FILTER

LIGHT

DIFFERENTIAL

PRESSURE

SWITCH

C

R

2

1

2a

1a

N

L1

POWER PLUG

LIGHTED

POWER SWITCH

24V

LEGEND

WIRING
COMMON
FUSE
GROUND
TRANSFORMER

C

TRAN

FM

FAN MOTOR

CONNECTION POINT

NORMALLY OPEN

NORMALLY CLOSED

DOUBLE POLE DOUBLE THROW

NO

NC

DPDT

C

L

G

N

1

2

3

4

5

MEDIUM

LOW

HIGH

SPEED TAPS

POWER

CONNECTION

MOT

OR

CONNECT

OR

Æ

NO1

NC1

NO2

NC2

C1

C2

SWITCH 

POSITION

DPDT

3 SPEED SWITCH 

NO1

NC1

NO2

NC2

C1

C2

LEFT

Æ

LOW

SPEED

NO1

NC1

NO2

NC2

C1

C2

CENTRE

Æ

MEDIUM

SPEED

NO1

NC1

NO2

NC2

C1

C2

RIGHT

Æ

HIGH

SPEED

RED

BLU

GRY

RED

BLU

GRY

BLK

YEL

GRN/YEL

BLK

BRN 24V

BLK

11

12

14

24

21

G

Summary of Contents for OptiClean FN1AAF 005

Page 1: ...rd MERV 7 or higher pre filter Minimum 500 CFM and Maximum 1500 CFM Meets or exceeds ASHRAE Standard 170 Ventilation of Health Care Facilities Vertical design for smaller footprint compared to many competitors and can be mounted and operated horizontally when necessary Portable and adaptable to nearly any location Heavy duty locking casters for easy and smooth transport HEPA filter rack and sealin...

Page 2: ... Remove the bottom front door then the top door over the blower section Inspect the HEPA filter and make sure it has not been dislodged or damaged during shipping that the side bolts and nuts near each corner are tight and the HEPA filter is held securely in place and the seal around the top edge of the filter is in place 9 Make sure the first stage pre filter is in place and not damaged 10 Replac...

Page 3: ...se a 1 2 inch open end or adjustable wrench to remove the bottom nuts from the all thread bars on both sides four nuts total 7 Slide the bottom HEPA filter supports down along with the filter and out of the unit 8 Remove the HEPA filter and immediately put it inside an approved containment bag Dispose per facility guidelines for hazardous materials 9 Position the new HEPA filter into the unit with...

Page 4: ...ting and or repairs be sure to have the model and serial numbers of your equipment available Specifications A200223 Fig 7 005 Model Wiring Diagram A200258 Fig 8 015 Model Wiring Diagram Switch Setting Motor Lead Motor Tap Options LOW Red 1 2 3 Switch Setting Motor Lead Motor Tap Options MED Blue 2 3 4 Switch Setting Motor Lead Motor Tap Options HIGH Gray 5 Table 2 Electrical Specifications 005 Mod...

Page 5: ...103 342890 75105 6 2 Gasket 6 152 mm 346295 402 7 2 Gasket 16 408 mm or 20 506 mm 346295 401 346295 403 8 2 Caster Assembly 346285 701 346285 702 9 1 HEPA Filter 346345 75101 346345 75102 10 1 Pre filter MERV 7 KH01AZ500 KH01AZ501 11 1 Lower Door Assembly 346279 701 346279 702 12 1 Upper Door Assembly 346277 701 346277 702 13 1 Indicator red 346299 401 14 1 Power Switch green lighted 346300 401 15...

Page 6: ...dition Date 06 20 Catalog No OM FN1AAF 02 Replaces OM FN1AAF 01 FN1AAF Operation and Maintenance Manual Manufacturer reserves the right to change at any time specifications and designs without notice and without obligations 6 Notes Page ...

Reviews: