background image

20

Monitor Mode

When used only to monitor a system, the Control Mode

is set to Wall T-Stat and the interface operates in a monitor
only mode. All control for the zone is provided by the local
unit control and the wall mounted user interface. The only
additional features supported in this mode are:

1.

A monitored Network FSD (ANI) input so that a fire or 
smoke detector can override the local unit’s control and stop 
the unit’s operation during this alarm condition. This control 
overrides any local control by setting the Local Unit ON/OFF 
Control to Prohibit to prevent the user from operating the 
equipment.

2.

The Zone Temp Sensor Location can be set to appropriately
show the correct position on the graphic.

3.

Provide a zone temperature alarm for annunciating high or low
zone temperature conditions.

4.

Provide the ability to Allow or Prohibit three functions at the
Toshiba User interface; Local Unit ON/OFF Control, Local Op
Mode Control, and Local Setpoint Control.

5.

Provide alarming indication for a dirty filter condition and a
reset function to clear the alarm condition after the filter has
been serviced.

6.

Provide the ability to detect and annunciate communication
errors and failure conditions.

7.

Provide the ability to annunciate alarm conditions present at the
zone control.

Building Automation System (BAS) Control
Mode

When the Control Mode is set to Wall T-Stat, the

interface operates in a control mode. It is used as a BAS
level control and in addition to the features listed above (in
Monitor Mode), it also provides the ability to schedule
occupancy and operate each zone to a setpoint schedule to
adjust the zone’s temperature setpoints based on the
occupancy schedule configured. 

A setpoint and occupancy schedule is provided for each

zone that is used to determine when the zone is occupied or
unoccupied. During the occupied period, the zone uses the
heating and cooling setpoints configured for the occupied
period. When the schedule has determined the zone is
unoccupied, the zone utilizes the unoccupied heating and
cooling setpoints.

To allow for setback recovery and provide a smooth

transition from unoccupied to occupied operation, the
Optimal Start algorithm slowly transitions the setpoints
from the unoccupied values to the occupied values over a
period of time prior to the start of the occupied period. The
amount of time is user adjustable, up to 6 hours.

Manual controls provide the ability to disable any zone 

by setting the Unit Commanded State to OFF. This 
parameter must be set to ON for any operation to occur.

The Mode Control parameter provides the ability to

choose between heating, cooling or allows the unit to
automatically switch modes as required if the Auto mode is
selected. Additionally, the Manual Op Mode Control
provides the ability to lock the unit in a specific mode (must
be set to Inactive for normal operation). Additional manual
overrides are provided for fan speed (Manual Fan Speed
Control) and Louver positioning (Louver Setting) if
applicable.

During the occupied period, the control compares the

current zone temperature to the occupied heating and
cooling setpoints. A cooling mode is required if the zone
temp is above the cooling setpoint while a heat mode is
required if the zone temperature is below the heating
setpoint. It also compares the Mode Control input to any
required mode that may be necessary to determine what
operating modes are permitted. 

The mode control can be set to allow for heating only,

cooling only or both heating and cooling. Finally, if a mode
is required and permitted, then if an Outdoor Air
Temperature sensor value is available (provided from the
Network) then a final check is done to determine if the
mode should be disabled due to an OA temp lockout.

If a mode is required and is allowed, the control sends

the appropriate occupied setpoint (heating or cooling) as
required and sends the AUTO fan control mode to allow the
unit to operate the indoor fan at the appropriate speed
required by the local zone control. The mode continues until
after the zone temperature achieves setpoint plus 1 deg 

F

for heating or minus 1 deg



F for cooling.

If at any time during the occupied period the local user

initiates a manual change of the setpoint, mode or fan speed
from the wall mounted user interface, the BAS level control
will no longer update those functions until the start of the
next unoccupied period.

During the unoccupied period, the control performs the

same checks as was done during the occupied period above
but utilizes the configured unoccupied setpoints to
determine the zone heating or cooling requirements. During
the unoccupied periods, the zone is determined to require
heat if the zone temperature is greater than 1

F below the

unoccupied heating setpoint and is determined to require
cooling if the zone temperature is greater than 1

F above the

unoccupied cooling setpoint. A 1

F hysteresis is still used

so each mode is satisfied when the zone temperature
reaches the appropriate unoccupied setpoint. When the
unoccupied setpoints are reached, the fan operates at a low
speed to maintain air circulation in the zone.

To transition smoothly from the unoccupied setpoints to

the occupied setpoints, optimal start will begin to ramp the
setpoints starting at the user configured time (4 hours
default) prior to the start of the next occupied period. This
allows the zone to reach the occupied temperature setpoints
at the start of the occupied period.

Summary of Contents for OPN-MTCC

Page 1: ...t editions of the National Electrical Code NEC ANSI NFPA American National Standards Institute National Fire Protection Association 70 In Canada refer to the current editions of the Canadian Electrical Code CSA Canadian Standards Association C22 1 Understand the signal words DANGER WARNING and CAUTION DANGER identifies the most serious hazards which will result in severe personal injury or death W...

Page 2: ...onments such as rain snow or extreme temperature theft vandalism and debris on job site Equipment covered in this manual is not suitable for outdoor installations Failure to do so may have serious adverse effects on unit operation and in the case of circuit board assembly may result in immediate or premature failure Failure of any unit caused by deposits of foreign material will not be covered by ...

Page 3: ...condensing unit of the Toshiba Carrier VRF system 2 Feed the communication cables through the pre drilled hole for low voltage wiring 3 Secure the U1U2 communication cable to the cabinet per the local code Fig 3 i Vu Enclosure 1 Use the following wiring materials to connect the field supplied communication cable Line specification A Type 2 core shielded wires B Wire size 16 gage 330 ft max C 14 ga...

Page 4: ...ow Voltage Wiring CLASS 2 Y W GREEN WHITE YELLOW W WHITE STRIPE GRN COLOR IDENTIFICATION RED YEL RED Legend BR BARE Terminal Factory installed Wiring Field installed wiring Wire color See color identification chart for refe BLK BLACK YELLOW 115VAC 60Hz 1Ph Power supply 0 5A Circuit Breaker Main Bus U1 U2 Y W 5VDC 6A Transformer Ground Terminal Block Line Terminal Block Ground Terminal Block BLK WH...

Page 5: ...nect to the Links local access port with the USB L cable from the USB TKIT kit or the cable can be purchases separately p n USB L The connection is on the left side of the Link Connect the other end of the cable to a computer s USB port and install the driver for the USB L if needed 8 Once this cable is connected to the computer check the Device Manager to see what COM port the CP210x is connected...

Page 6: ...nd check for the message No Error in the Error column This program displays the status of the Modbus registers that reside in the TCC Link All Toshiba Carrier Unit X programs have points that reside only in the Controllers and are sent to the TCC Link when requested Use the System Info tab to get the values from the Toshiba Carrier VRF System to verify that the i Vu Open Link is communicating with...

Page 7: ...7 Fig 9 Technician Tool ...

Page 8: ... Alarm Code alarm_code R 1 to 255 1 FSD Alarm 0 255 unit alarms Operation Mode op_mode_stat R Heat 1 Cool 2 Fan 3 Dry 4 Auto Heat 5 Auto Cool 6 Off 7 Zone Temp suc_tmp R deg F Temp Setpoint tmp_mon R deg F Fan Speed fan_spd_mon R Stop 1 Auto 2 High 3 Medium 4 Low 5 Very Low 6 Filter Status filt R Clean 0 Dirty 1 Shutdown Shutdown R W Inactive 0 Active 1 ...

Page 9: ...t 2 Cool 3 Manual Op Mode Control op_mode_cmd R W Heat 1 Cool 2 Fan 3 Dry 4 Auto 5 Inactive 6 Manual Fan Speed Control fan_spd_cmdx R W Auto 1 High 2 Medium 3 Low 4 Louver Setting luvr_set R W Stop 1 Swing 2 Down 3 25 Up 4 50 Up 5 75 Up 6 100 Up 7 Se Min Setpoint Separation min_stpt_sep R W 2 Deg F 10 Deg F 5 Deg F Cooling Lockout Temperature oat_cl_lockout R W 65 deg F 80 deg F 45 Deg F Heating L...

Page 10: ...Occupied Heating Setpoint occ_ht_stpt R W 55 deg F 90 deg F 70 deg F Unoccupied Cooling Setpoint unocc_cl_stpt R W 65 deg F 99 deg F 85 deg F Unoccupied Heating Setpoint unocc_ht_stpt R W 50 deg F 80 deg F 65 deg F Effective Cool Setpoint effective_cl_stpt R deg F Effective Heat Setpoint effective_ht_stpt R deg F Optimal Start optm_star R W 1 hour 4 hours 4 hours ...

Page 11: ...ig 13 Alarm Configuration Screen Table 5 Alarm Configuration Description Point States High Temperature Alarm Limit spt_alrm_hi_lm R W 40 deg F 100 deg F 95 deg F Low Temperature Alarm Limit spt_alrm_lo_lmt 35 deg F 90 deg F 45 deg F ...

Page 12: ... Unit Type unit_type R Air Conditioning 1 Ventilator 2 Local Unit ON OFF Control unit_onoff_ena R W Allow 0 Prohibit 1 Local Op Mode Control op_mode_ena R W Allow 0 Prohibit 1 Local Setpoint Control setpoint_ena R W Allow 0 Prohibit 1 System Outdoor Air Temperature bacnet AV 80001 deg F System Fire Smoke bacnet Off 0 On 1 Fire Smk Shutdown BBV Normal Mode Control Source Normal BAS Controlling Mode...

Page 13: ...in Cool Mod deg F Min Permitted Temp Setting in Cool Mode deg F Max Permitted Temp Setting in Dry Mode deg F Min Permitted Temp Setting in Dry Mode deg F Max Permitted Temp Setting in Auto Mode deg F Min Permitted Temp Setting in Auto Mode deg F Permitted Fan Speed Setting BIT1 Off 0 L 1 Permitted Fan Speed Setting BIT2 Off 0 H 1 Permitted Fan Speed Setting BIT3 Off 0 HH 1 Permitted Fan Speed Sett...

Page 14: ...hen OFF no heating cooling or fan operation is provided Mode must be on for any local or BAS control Alarm Status Indicates if any alarms are currently active Alarm Code If the Alarm Status above is in alarm then this value represents the alarm code received from the zone control Operation Mode Displays the current operational mode used by the zone control Zone Temp Displays the zone temperature o...

Page 15: ...cifies the temperature at which when the OAT falls below cooling will no longer be available to operate Heating Lockout Temperature Specifies the temperature at which when the OAT rises above heating will no longer be available to operate Name Description High Temperature Alarm Limit Use to determine the maximum allowable zone temperature that can occur in this zone at any time If a zone temperatu...

Page 16: ...ol mode Min Permitted Temp Setting in Cool Mode Displays the minimum allowable temperature setting in cool mode Max Permitted Temp Setting in Dry Mode Displays the maximum allowable temperature setting in dry mode Min Permitted Temp Setting in Dry Mode Displays the minimum allowable temperature setting in dry mode Max Permitted Temp Setting in Auto Mode Displays the maximum allowable temperature s...

Page 17: ...ame Description Occupancy Status Displays the current occupancy state Local BACnet Schedule Displays the current state of the occupancy schedule where OFF is unoccupied and ON is occupied Name Description Link Comm Connection Displays whether the TCC Link is communicating to the VRF unit Fire Smoke Shutdown Displays when the operation has been disabled due to an active Fire Smoke condition Unit Al...

Page 18: ...during automatic address 55 E21 Header thermal storage units quantity error 56 E22 Decease of No of thermal storage units 57 E23 Sending error in communication between outdoor units 58 Reserved 59 E25 Duplicated follower outdoor address 5A E26 Decrease of No of connected outdoor units 5C E28 Follower outdoor unit error 5F E31 IPDU communication error 61 F01 Indoor TCJ sensor error 62 F02 Indoor TC...

Page 19: ...torage units DB L27 Thermal storage units quantity error DC L28 Maximum number of outdoor units exceeded DD L29 No of IPDU error DE L30 Auxiliary interlock in indoor unit DF L31 IC error E1 P01 Indoor fan motor error E3 P03 Discharge temp TD1 error E4 P04 High pressure switch detection error E5 P05 Phase missing detection Phase order error E7 P07 Heat sink overheat error EA P10 Indoor overflow err...

Page 20: ...oling or allows the unit to automatically switch modes as required if the Auto mode is selected Additionally the Manual Op Mode Control provides the ability to lock the unit in a specific mode must be set to Inactive for normal operation Additional manual overrides are provided for fan speed Manual Fan Speed Control and Louver positioning Louver Setting if applicable During the occupied period the...

Page 21: ...g mode temperature range air direction and airflow of the indoor units differ according to the unit type 8 When the power to the outdoor units of a multi air conditioning system is interrupted or when the system is being re booted the TCC LINK board cuts TCC LINK communication The response to communication break is Exception Response 0 x 06 9 The register TCC LINK bus error will be Error 1 when al...

Page 22: ...T UP Central Control Address Setting Group Address M M M M M ME E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E E EN N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N NU U U U C C C C C C C C C C C C CA A A A A AN N N N N N N N NC C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C C CE E E E E E E E E E E EL L M M M M M ME E E E E E E E E ...

Page 23: ...button to display the menu screen 2 Push and hold the MENU button and the button at the same time to display the Field setting menu M M M M M ME E E E E E E E E E E E E E E E E E E E E E E E E E E E E E EN N N N N N N N N N N N N N N N N N N N N N N N N N NU U U M ME E E E E E E E E E E E E E E E E E E E EN N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N N NU U U U U U U U U U 2 ...

Page 24: ... T ET SET C C C CL L L CL L C CL L L CL L C CL TIME ME ME E ME E E T TIMER TI IMER TIMER TI IMER R T TIMER TIMER S SET SET SET S S SET T S S SE FAN F FAN FA A A AN FAN N FAN FAN FA A A AN FA A A FA AN FA A AN SWING SWING SWING SWING WING WING SWING FIX FIX FIX FIX UNIT UNIT UNIT UNIT U UN VEN NT MOD DE ST TE E SET S TIME E TEMP TEM EMP EM EMP P P EMP P P P EMP P P P P P P P MP MP CODE No TEM MP P ...

Page 25: ...rietary Information Not for Further Distribution STEP 5 TEST button FINISH Push button to exit DN menu START UP Control Wire Addressing Group Address T T T T T T T T T T T T T T T T T T T T T T T T T T T T T TE ES ES S E E E E E E E T T b b b button MANUAL ADDRESS SETTING 4 ...

Page 26: ...t to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 18 OPNMTCC 001 Printed in U S A Form OPN MTCC 3SI Pg 26 02 18 Replaces OPN MTCC 2SI Carrier Corporation 2018 ...

Reviews: