background image

18

Compressor Rotation — 

To determine whether or not

compressor is rotating in the proper direction:

1. Connect service gages to suction and discharge pressure

fittings.

2. Energize the compressor.
3. The suction pressure should drop and the discharge pres-

sure should rise, as is normal on any start-up.

4. If the suction pressure does not drop and the discharge

pressure does not rise to normal levels, the compressor

may be rotating in the wrong direction.

5. Since the compressor and fan motors are connected in

phase during production, it is likely that the evaporator

and condenser fans are probably also rotating in the

wrong direction.

6. Turn off power to the unit, lock and tag disconnect per

standard safety procedures. 

7. Reverse any two of the unit power leads.
8. Remove lock and tag per standard safety procedures and

reapply power to the unit.

9. The suction and discharge pressure levels should now

move to their normal start-up levels.

NOTE: When the compressor is rotating in the wrong direc-

tion, the unit makes an elevated level of noise and does not

provide cooling.

Operating Sequence — 

All units require the addition

of a thermostat accessory package to complete the control cir-

cuit. The sequence of operation may vary depending on which

package is selected.
ROOM-MOUNTED THERMOSTAT — These units use an

electronic thermostat mounted in the conditioned space.
FAN CIRCULATION — The  indoor-fan  motor  is  energized

through G on the thermostat and the indoor-fan contactor is

energized. This starts the indoor-fan motor (IFM). The fan will

operate to provide continuous air circulation.
COOLING — The indoor fan will operate continuously or

when the compressor runs, depending on the setting of the ther-

mostat fan selector switch. When the thermostat closes (on a

call for cooling Y1 on the thermostat), the control relay (CR),

outdoor-fan contactor (OFC) and compressor contactor(s) (C1

and C2 on 50XCR12-16 units) close. The control relay will

start the indoor fan if it is not already running. The compressor

contactors will immediately start the first stage compressor(s).

A second stage on 50XCR12-16 units will close if addition-

al cooling demand is required, and will then start the second-

stage compressor. When the thermostat is satisfied, the second

stage compressor will stop first, and then the first stage com-

pressors will stop when cooling demand is satisfied.
ALL UNITS — The control circuit incorporates a current

sensing lockout relay (Cycle-LOC™ device) that locks off the

compressor(s) for 5 minutes when any safety device is activat-

ed (low or high pressure switches, or compressor internal over-

load). If any compressor safety device opens, the compressor

will stop. High and low-pressure switches and compressor mo-

tor overload protectors will reset automatically when the condi-

tion which caused the device to trip has dropped below the re-

set condition. To reset the Cycle-LOC control device, manually

turn the control power OFF, then back ON.

SERVICE

Cleaning Evaporator Coil — 

Do not use high-pressure

water or air. Damage to fins may result. Clean coils with a vac-

uum cleaner, fresh water, compressed air, or a bristle brush (not

wire). Backflush coil to remove debris. Commercial coil clean-

ers may also be used to help remove grease and dirt. Steam

cleaning is NOT recommended.

Units installed in corrosive environments should be cleaned

as part of a planned maintenance schedule. In this type of appli-

cation, all accumulations of dirt should be cleaned off the coil.

Take care not to get water in the system ducts or unit

insulation.

Lubrication — 

 Fan motors have permanently lubricated

bearings.

Indoor Fan Adjustment — 

To prevent personal injury,

be sure wire fan guards (provided by customer) are secured in

place over each fan discharge (or that fans are ducted) before

starting the unit.
TO CHANGE FAN SPEED

1. Shut off unit power supply. Lock out power supply and

tag disconnect locations.

2. Loosen fan belt by loosening fan motor belt adjusting

bolts. Do not loosen fan motor mounting bracket from

unit.

3. Loosen movable pulley flange setscrew (Fig. 11).
4. Screw movable flange toward fixed flange to increase fan

speed and away from fixed flange to decrease speed. In-

creasing fan speed increases load on motor. Do not ex-

ceed maximum allowable fan speed or motor full load

amps indicated on unit nameplate and in Table 5.

5. Set movable flange setscrew at nearest flat of pulley hub

and tighten setscrew.

6. Check pulley alignment and belt tension adjustment as

described below.

7. Check fan operation. Repeat above procedure as required.

Pulley Alignment — 

Shut off unit power supply. Lock

out power supply and tag disconnect locations. Loosen fan

motor pulley setscrews and slide fan pulley along fan shaft.

Make angular alignment by loosening motor from mounting

bracket (see Fig. 11). Check alignment with a straightedge.

Belt Tension Adjustment — 

Shut off unit power sup-

ply. Lock out power supply and tag disconnect locations. Loos-

en fan motor mounting plate bolts. Do not loosen motor

mounting bracket from unit. Adjust belt tensioning bolt until

proper belt tension is obtained.

Changing Fan Wheel  — 

 If a fan wheel should fail, it

may be replaced as follows:

1. Shut off unit power supply. Lock out power supply and

tag disconnect locations.

2. Remove belts from fan pulley.
3. Loosen locking collars on the fan bearings and set screws

on the fan wheels.

4. Remove the shaft through the access panel on either side

of the unit.

5. Remove the fan cut-off plate in the fan discharge.
6. Remove the fan wheel through the fan discharge opening.
7. Replace the wheel, and reverse Steps 1-5 above.

Fan Bearing Replacement — 

If a fan bearing fails,

replace it as follows:

1. Shut off unit power supply. Lock out power supply and

tag disconnect locations.

2. Remove belts from the fan pulley.
3. Support fan shaft.
4. Loosen locking collar on fan bearing.
5. Remove bearing from the shaft.
6. Install new bearing onto the shaft, and reverse Steps 1-3

above.

Summary of Contents for Omnizone 50XCR06

Page 1: ... labels attached to the equip ment Follow all safety codes Wear safety glasses and work gloves WARNING Electrical shock can cause personal injury and death Shut off all power to this equipment during installation There may be more than one disconnect switch Tag all discon nect locations to alert others not to restore power until work is completed CAUTION Use care in handling rigging and setting bu...

Page 2: ...ting weights Applicable installation codes may limit this cabinet to installation only in a single story residence Table 1 Condenser Usage Either the 09XC or the 09AZ condenser can be used NOTE Where there are no quantities of condensers listed the com bination is not recommended See Application Data literature for more information on condenser combinations UNIT 50XCR CONDENSER QUANTITY 09XC SIZE ...

Page 3: ...ON EVAP SECTION EVAP RETURN DUCT DISCH CONN LIQUID CONN EVAP SUPPLY DUCT Blower Opening DISCH DIAMETER SWAGE ID LIQUID DIAMETER SWAGE ID A B C D E F G H I J L N O P Q R S 12 68 0 64 0 31 2 28 35 5 61 1 31 8 29 4 5 5 11 1 13 9 12 5 13 8 8 5 13 6 0 875 0 625 14 68 0 64 0 31 2 28 35 5 61 1 31 8 29 4 5 5 11 1 13 9 12 5 13 8 8 5 13 6 0 875 0 625 ...

Page 4: ...ON EVAP SECTION EVAP RETURN DUCT DISCH CONN LIQUID CONN EVAP SUPPLY DUCT Blower Opening DISCH DIAMETER SWAGE ID LIQUID DIAMETER SWAGE ID A B C D E F G H I J L N O P Q R S 12 68 0 64 0 31 2 28 35 5 61 1 31 8 29 4 5 5 11 1 13 9 12 5 13 8 2 7 13 6 0 875 0 625 14 68 0 64 0 31 2 28 35 5 61 1 31 8 29 4 5 5 11 1 13 9 12 5 13 8 2 7 13 6 0 875 0 625 D ...

Page 5: ...VAP SECTION EVAP RETURN DUCT DISCH CONN LIQUID CONN EVAP SUPPLY DUCT Blower Opening DISCH DIA SWAGE ID LIQUID DIA SWAGE ID A B C D E F G H I J L N O P Q T R S 16 88 0 66 7 31 2 31 2 35 5 83 7 33 8 32 3 3 1 10 8 13 9 12 5 13 8 8 5 13 5 11 7 1 125 0 625 24 88 0 70 8 31 2 31 2 39 5 83 7 37 8 32 3 2 3 10 8 13 9 14 9 13 8 8 6 8 3 13 2 1 125 0 625 ...

Page 6: ... EVAP SECTION EVAP RETURN DUCT DISCH CONN LIQUID CONN EVAP SUPPLY DUCT Blower Opening DISCH DIA SWAGE ID LIQUID DIA SWAGE ID A B C D E F G H I J L N O P Q T R S 16 88 0 66 7 31 2 31 2 35 5 83 7 33 8 32 3 3 1 10 8 13 9 12 5 13 8 2 6 13 5 11 7 1 125 0 625 24 88 0 70 8 31 2 31 2 39 5 83 7 37 8 32 3 2 3 10 8 13 9 14 9 13 8 2 6 8 3 13 2 1 125 0 625 D ...

Page 7: ... provide inlet filters to protect the coils or locate the unit in an area free from airborne dirt or other foreign material which could clog the coils The units are designed to pass through most 36 in door openings The filter rack may also be removed for additional clearance UNIT 50XCR 5 7 5 10 12 15 20 UNIT OPERATING WEIGHT lb 600 799 1001 1079 1231 1629 COMPRESSOR Scroll Compressor Model ZPS60 Z...

Page 8: ...Condensate Drain Line The 50XCR unit has a drain connection for evaporator condensate When connecting condensate drains from the unit to floor drains sinks or hoppers connect drains downstream of trap to ensure that condensate does not drain back into the unit Make connections through the unit side panel Some appli cations may require connection to either galvanized steel or copper drain pipe cons...

Page 9: ...its must have adequate overcur rent protection fuses or HACR Heating Air Conditioning and Refrigeration breakers according to the national and ap plicable local codes For field power connections all main power wiring enters the unit through a factory punched access hole under the con trol box Attach power wires to the power connections on the main power terminal block in the unit control box Be su...

Page 10: ...2 575 3 60 518 632 5 8 39 5 1 39 14 208 230 3 60 187 253 19 6 136 19 2 136 460 3 60 414 506 8 2 66 8 7 66 575 3 60 518 632 6 6 55 6 9 55 16 208 230 3 60 187 253 28 7 191 23 0 149 460 3 60 414 506 13 3 100 11 0 75 575 3 60 518 632 10 0 78 8 0 54 24 208 230 3 60 187 253 40 7 240 28 7 191 460 3 60 414 506 19 3 140 13 3 100 575 3 60 518 632 15 6 107 10 0 78 FLA Full Load Amps LRA Locked Rotor Amps NEC...

Page 11: ...enum Install 3 screws along each plenum side and 5 screws along plenum front and rear mounting angles 4 Adjust four way deflection vanes as needed to ensure ad equate airflow distribution W1 Y1 G W3 CK1 CK2 R C W2 Y2 RS2 RS 5 RS1 RS GND UNIT GROUND 33CS250 01 R G Y1 C Y2 TB2 50XC 12 SIZE UNIT AND LARGER WIRE NUT SHIELD CUT AND TAPE BACK REMOTE ROOM SENSOR P N ZONECCORRS01 W1 W2 D1 D2 NOTE Remote s...

Page 12: ...79 0 96 1800 572 0 32 627 0 39 679 0 45 729 0 52 777 0 60 823 0 68 868 0 76 911 0 85 953 0 94 994 1 03 1900 604 0 38 656 0 45 706 0 52 754 0 59 800 0 67 844 0 75 887 0 83 929 0 92 970 1 01 1009 1 11 2000 636 0 44 685 0 51 733 0 58 779 0 66 823 0 74 866 0 83 908 0 91 948 1 01 988 1 10 1026 1 20 2100 668 0 51 715 0 58 760 0 66 804 0 74 847 0 82 888 0 91 929 1 00 968 1 09 1006 1 19 1044 1 29 2200 699...

Page 13: ...Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 2200 497 0 27 581 0 39 655 0 52 722 0 66 782 0 80 839 0 95 892 1 11 941 1 28 989 1 45 1034 1 62 2400 542 0 35 621 0 48 690 0 62 753 0 77 812 0 92 866 1 08 917 1 25 966 1 42 1012 1 60 1056 1 78 2600 587 0 45 660 0 59 726 0 74 787 0 89 843 1 06 895 1 22 945 1 40 992 1 58 1037 1 76 1080 1 95 2800 632 0 56 701 0 71 763 0 87 821 1 04 875 1 21 925 1 38 974 1 57 1019 1 75 ...

Page 14: ... 806 1 38 852 1 56 897 1 76 4000 508 0 63 547 0 71 588 0 81 632 0 92 677 1 04 722 1 17 768 1 31 814 1 47 859 1 65 903 1 85 4200 533 0 73 570 0 82 609 0 92 650 1 03 693 1 15 736 1 28 780 1 42 823 1 58 867 1 76 910 1 95 4400 559 0 83 594 0 93 631 1 03 670 1 15 710 1 27 751 1 40 792 1 54 834 1 70 876 1 87 917 2 06 4600 584 0 95 618 1 05 653 1 16 690 1 28 728 1 40 767 1 53 806 1 68 846 1 83 886 2 01 9...

Page 15: ...8 819 2 03 846 2 18 874 2 32 903 2 46 934 2 62 966 2 78 5700 733 1 28 763 1 61 789 1 85 815 2 05 841 2 22 867 2 37 894 2 52 921 2 67 950 2 82 980 2 98 5900 759 1 42 787 1 77 813 2 02 838 2 23 863 2 41 888 2 57 914 2 73 940 2 88 968 3 03 996 3 19 6100 784 1 57 812 1 93 838 2 20 862 2 42 886 2 62 910 2 79 934 2 95 960 3 11 986 3 27 1013 3 43 CFM ESP in wg 1 00 1 10 1 20 1 30 1 40 1 50 1 60 1 70 1 80...

Page 16: ...7 673 1 90 718 2 13 761 2 37 802 2 61 841 2 86 879 3 11 916 3 37 951 3 63 6500 598 1 63 647 1 86 693 2 10 737 2 34 778 2 59 818 2 84 857 3 09 894 3 35 929 3 62 964 3 89 6750 621 1 83 668 2 07 713 2 32 755 2 57 796 2 82 835 3 08 872 3 34 909 3 61 944 3 89 978 4 16 7000 644 2 04 689 2 29 733 2 55 774 2 81 814 3 07 852 3 34 888 3 61 924 3 89 958 4 17 992 4 46 7250 667 2 27 711 2 53 753 2 80 793 3 07 ...

Page 17: ...56 5 38 1091 5 77 8 000 743 2 60 790 2 96 835 3 32 878 3 69 918 4 07 958 4 45 996 4 84 1033 5 23 1068 5 63 1103 6 04 8 300 771 2 90 817 3 27 860 3 65 901 4 03 941 4 42 979 4 82 1017 5 22 1053 5 63 1087 6 04 1121 6 45 8 600 799 3 23 843 3 61 885 4 00 925 4 40 964 4 80 1001 5 21 1038 5 62 1073 6 04 1107 6 47 1140 6 89 8 900 827 3 58 869 3 98 910 4 38 949 4 79 987 5 20 1024 5 62 1059 6 05 1093 6 48 1...

Page 18: ...ion To reset the Cycle LOC control device manually turn the control power OFF then back ON SERVICE Cleaning Evaporator Coil Do not use high pressure water or air Damage to fins may result Clean coils with a vac uum cleaner fresh water compressed air or a bristle brush not wire Backflush coil to remove debris Commercial coil clean ers may also be used to help remove grease and dirt Steam cleaning i...

Page 19: ... reset button 4 Turn the Power Switch Disconnect Switch of the Start Stop Station to the ON Position Table 12 Evaporator and Condenser Motor Starter Settings Fig 11 Fan Pulley Adjustments a48 916tf Fig 12 Concentric Alignment a50 2177tf Fig 13 Fan Shaft Bearings a50 2178tf Fig 14 Motor Starter Setting a50 8659 1 9 1 6 1 3 M M O A O A RESET O CLASS 20 TEST OVERLOAD SETPOINT WHEEL MOTOR OVERLOAD RES...

Page 20: ...er the temperature allow a tolerance of 3 F Example Head pressure from gage 416 4 psig Saturated condensing temp from chart 120 F Liquid line temp from thermometer 100 F Subcooling by subtraction 20 F Table 13 Subcooling Temperature Saturated condensing temperature at compressor minus liquid line temperature NOTE Do not vent or depressurize unit refrigerant to atmo sphere Remove and recover refrig...

Page 21: ...g phase Check TXV Check temperature in suction discharge line Unit is Noisy Compressor noise Check TXV and replace if necessary Check internal noise Tube vibration or condenser water problem Check and correct Unit panel or part vibrating Check and tighten appropriate part Unit Runs Continuously but has Low Capacity Unit is undersized Check heat load calculation Low refrigerant or noncondensing gas...

Page 22: ...k building load Low refrigerant Check for and repair leaks and add refrigerant as necessary Low airflow in evaporator Clean filter Remove scale Check for blockage in ducts Check fan rotation Check motor operation Check belts Low refrigerant flow in evaporator Check for obstruction in filter drier Check for obstruction in TXV Check super heating Check position of TXV bulb and equalizer Suction Pres...

Page 23: ...ontinued on Low Voltage Diagram LEGEND AND NOTES FOR FIG 15 17 NOTES 1 Fan motors are inherently thermally protected 2 Three phase motors are protected under primary single phase conditions 3 Use conductors suitable for at least 194 F 90 C when replacing factory wiring 4 Use copper conductors only 5 Wiring for field power supply must be rated at 165 F 75 C minimum LEGEND C Compressor Contactor CH ...

Page 24: ...2 510 BLK 501 RED 501 RED 561 RED 509 BRN 510 BLK 521 BLU 530 PNK 3 LOGIC 1 2 CLO2 HPS2 FRZ2 LPS2 A B C2 534 PNK 535 PNK 539 BRN 538 PNK 533 PNK 540 BRN 540 BRN 537 BLK 536 BLK 532 PNK TB2 R Y1 R C G Start Stop Relay in Remote Condenser Y1 R C G FIELD T STAT Y2 Y2 Page 22 Fig 15 Typical Wiring Schematic 50XCR12 24 208 230 3 60 Units Shown cont NOTE See legend and notes on page 23 a50 8517 Continue...

Page 25: ...DISC1 L2 L3 L1 GND 100 BLK 101 BLK 102 BLK GND 2 1 3 COMP2 130 BLK 132 BLU 131 YEL 127 BLK 129 BLU 128 YEL C2 134 BLK 135 BLK CH2 CLO2 Loop T2 L2 T1 L1 T3 L3 2 1 3 Continued on Low Voltage Diagram TB3 Important Tran1 and Tran3 power separate 24V Circuits These circuits shall not be interconnected and separation shall be maintained 460V 3 60 Hz 152 BLK 153 YEL 154 BLK 155 YEL FU1 FU2 FU3 590 BRN 59...

Page 26: ...E ECONOMIZER HARNESS REPLACES THE FACTORY SHORTING PLUG FIELD INSTALLED SAT SENSOR CONNECTS TO CIRCUITS 6 7 Continued on Line Voltage Diagram 501 RED 561 RED 501 RED 1 3 CR1 531 BRN 609 PNK 609 PNK 9 4 2 CR1 3 LOGIC 1 2 CLO2 HPS2 FRZ2 LPS2 A B C2 534 PNK 535 PNK 539 BRN 538 PNK 540 BRN 537 BLK 536 BLK 532 PNK 561 RED Continued on Line Voltage Diagram 4 2 CR2 580 BLK A B SV1 581 BRN 563 RED 580 BLK...

Page 27: ...N 603 YEL 601 RED 550 BLK REMOVE JUMPER BLK 600 WHEN CONNECTING AIR SIDE ECONOMIZER OCCUPANCY CONTROL WHEN FIELD INSTALLED THE ECONOMIZER HARNESS REPLACES THE FACTORY SHORTING PLUG FIELD INSTALLED SAT SENSOR CONNECTS TO CIRCUITS 6 7 Continued on Line Voltage Diagram 501 RED 561 RED 1 3 CR1 531 BRN 609 PNK 609 PNK 9 4 2 CR1 3 LOGIC 1 2 CLO2 HPS2 FRZ2 LPS2 A B C2 534 PNK 535 PNK 539 BRN 538 PNK 537 ...

Page 28: ......

Page 29: ......

Page 30: ...ight to discontinue or change at any time specifications or designs without notice and without incurring obligations Catalog No 04 53500193 01 Printed in U S A Form 50XCR 6SI Pg 30 1 18 Replaces 50XCR 5SI Carrier Corporation 2018 ...

Page 31: ...ER WIRES TO THE UNIT SIZED AND INSTALLED PROPERLY Y N _______ HAVE EVAPORATOR FAN AND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENTAND DO THE FAN BELTS HAVE PROPER TENSION Y N _______ HAS CORRECT FAN ROTATION OR EVAPORATOR BEEN CONFIRMED Y N _______ VERIFY CONDENSATE DRAIN HAS BEEN INSTALLED PER INSTRUCTIONS Y N _______ HAS WATER BEEN PLACED IN DRAIN PAN TO CONFIRM PROPER DRAINAGE Y N _______ AR...

Page 32: ... 15 MINUTES RUNNING TIME RECORD THE FOLLOWING MEASUREMENTS COMPRESSOR AMPS NOTES _______________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________...

Reviews: