86
OAT Reset 3
R/W
Holding Regis-
ter (Float)
25
oat_reset3
AV
74
nviO-
atReset3
SNVT_count_inc(
9)
Outside Air Temperature
(Stage 2 Cooling) Opera-
tion in °F
Default: 70 °F
OAT Reset 4
R/W
Holding Regis-
ter (Float)
27
oat_reset4
AV
76
nviO-
atReset4
SNVT_count_inc(
9)
Outside Air Temperature
(Stage 3 Cooling) Opera-
tion in °F
Default: 78 °F
OAT Reset 5
R/W
Holding Regis-
ter (Float)
29
oat_reset5
AV
79
nviO-
atReset5
SNVT_count_inc(
9)
Outside Air Temperature
(Stage 4 Cooling) Opera-
tion in °F
Default: 84 °F
OAT Reset MA
R/W
Holding Regis-
ter (Float)
31
oat_reset_ht
AV
92
Select
Outside Air Mixed Air
Temperature (Pre-Heat-
ing) Operation in °F
Default: 40 °F
Occupancy Status
R
Discrete Input
56
occ_status
BV
21
nvoOc-
cStatus
SNVT_switch(95)
Network Parameter to
set Occupancy Status
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
Outside Air Reset
Mode Status
R
Input Register
(Float)
37
oat_rst_-
mode_stat
AV
89
Select
Return Air Temperature
Reset Mode Status
0 = Single
1 = Multiple
Overload
R
Discrete Input
57
blwr_ovr-
load_alm
BV
75
Select
Network Alarm of Supply
Fan Motor Overload
0 = Normal
1 = Motor Overload
Alarm
Overload Status
R
Discrete Input
58
blw_ovr-
load_status
BV
74
Select
Network Status of Supply
Fan Motor Overload
0 = Normal
1 = Motor Overload
Alarm
Point Name
R/W
Holding Regis-
ter (Float)
53
ao_two
AV
92002
Select
Factory Reserved
Point Name
R/W
Holding Regis-
ter (Float)
55
ao_one
AV
92001
Select
Factory Reserved
Point Name
R/W
Coil
13
do_one
BV
91001
Select
Factory Reserved
Point Name
R/W
Coil
15
do_two
BV
91002
Select
Factory Reserved
Point Name
R/W
Coil
16
do_three
BV
91003
Select
Factory Reserved
Point Name
R/W
Coil
17
do_six
BV
91006
Select
Factory Reserved
Point Name
R/W
Coil
18
do_five
BV
91005
Select
Factory Reserved
Point Name
R/W
Coil
19
do_four
BV
91004
Select
Factory Reserved
Point Name
R/W
Coil
20
do_one_one
BV
91007
Select
Factory Reserved
Point Name
R/W
Coil
21
do_one_three
BV
91009
Select
Factory Reserved
Point Name
R/W
Coil
22
do_one_two
BV
91008
Select
Factory Reserved
RA High Static
R
Discrete Input
76
raf_hi_stat-
ic_alm
BV
96
nvoRafHi-
StaticAl
SNVT_switch(95)
Network Alarm indicat-
ing return high return
duct static
0 = Normal
1 = High Static Alarm
RA Static Press
High Trip
R/W
Holding Regis-
ter (Float)
59
ra_sta_hi_trip
AV
164
nviRaSta-
HiTrip
SNVT_count_inc(
9)
Network Alarm indicat-
ing status of high levels
of static
RA Static Press Set
point
R/W
Holding Regis-
ter (Float)
61
ra_sta_-
press_stpt
AV
165
nviRaSta-
PressStp
SNVT_count_inc(
9)
Network Alarm indicat-
ing status of press levels
of static
RA_SENS_FAIL
R
Discrete Input
71
ras_sen
BV
84
Select
Network Parameter to
set RA SENSOR FAIL
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
RAS_HI
R
Discrete Input
72
ras_hi
BV
83
Select
Network Parameter set
RAS HI
0 = Hardwired Sensor
(Default)
1 = BAS Sensor Value
RAT Reset Mode
R/W
Holding Regis-
ter (Float)
33
rat_rst_mode
AV
71
Select
Network Parameter to
set Return Air Tempera-
ture reset mode
0 = Single Reset Value
1 = Multiple Reset Val-
ues (Default)
Table 66 — Integration Points List (cont)
PROTOCOL MAP
MODBUS
BACNET
LONWORKS
OPERATION
DISPLAY NAME
READ/
WRITE
REGISTER
TYPE
REGISTER
NUMBER
REFERENCE
NAME
OBJECT
TYPE
OBJECT
ID
NV NAME
SNVT
DESCRIPTION