background image

5

For any parts that need to be removed, use a mini tubing cutter.

Perform phos-copper brazing on all field-made connections while

protecting adjacent joints from heat.
REFRIGERANT LINE SIZING
Sizing depends on length of lines between various sections of the

refrigerant system. Consider the amount of liquid lift and drop in

the system as well as proper compressor oil return. Consult Carrier

System Design Manual, Part 3 for proper piping sizes and design.
PRESSURE RELIEF
The ASHRAE Standard 15, Safety Code for Mechanical Refriger

-

ation states: ‘‘Every refrigerating system shall be protected by a

pressure relief device or some other means designed to safely re

-

lieve pressure  due to  fire  or  other  abnormal  conditions.’’ Since

09XC condensers do not have pressure relief devices, one must be

field supplied  and  installed  either before the liquid  line  service

valve or  inside  the  09XC unit.  Each circuit must have its  own

pressure relief.

If desired, the pressure relief requirement can also be satisfied by

installing a fusible plug in the liquid line. To do so, install a tee in

the liquid line with a 

1

4

-in. NPT fitting on the tee side, and install a

fusible plug (part no. EK02KK105 or similar). The temperature

rating  of the  fusible  plug should  be  between 205°F and  220°F

(96°C and 104°C). If a service valve is used on the liquid line, be

sure that both the piping system and the condenser are protected

for relief if all service valves are closed. Note that if the condenser

is located indoors, requirements for venting the fusible plug to the

outdoors may apply. Consult local code requirements.
REFRIGERANT RECEIVER
A refrigerant receiver is not furnished with 09XC condensers and

is not recommended for normal applications as its use is detrimen

-

tal to adequate refrigerant storage volume and desired effects of

subcooling.
COIL CONNECTIONS
See Table 2 for the necessary connections.
LIQUID LIFT
Amount of liquid lift available before refrigerant flashing occurs

depends on amount of liquid subcooling in the system.

All 09XC condensers have positive subcooling when applied with

optimum charge. With subcooling, it is possible to overcome an

appreciable pressure drop and/or static head pressure (due to ele

-

vation of the liquid metering device above the condenser when

condenser is below evaporator coil).

When 09XC condensers are applied with minimum charge, they

do not provide positive subcooling. If subcooling is required, it

must be obtained by external means such as a liquid suction inter

-

changer.

It is recommended that the evaporator be either at the same level

as  the  condenser  or  lower  than  the  condenser  when  minimum

charge is used.
SWEAT CONNECTIONS
Connections are made outside the unit, and piping enters from the

right side. For ease in brazing, it is recommended that all internal

solder joints be made before unit is placed in its final position. See

50XCR (or other compressor-bearing unit) base unit installation

instructions for proper line sizing and piping procedures.
FIELD PIPING
For 09XC remote installation, select pipe sizes according to length

from Table 3. Use refrigerant grade piping. If tubing size is other

than unit connection sizes, use adapter fittings.

Refer to 50XCR (or other compressor-bearing unit) base unit in

-

stallation instructions to determine refrigerant charge adjustment

for remote and special piping applications.

NOTE: When installing 09XC units in systems, add charge for

other components (i.e., filter drier, moisture indicator, etc.) to de

-

termine system charge quantity. Record charge.
CHECK VALVE
When the 09XC condenser is installed with the condenser located

above the compressor evaporator, it is recommended that a field-

supplied check valve be installed on the hot gas discharge line.

This prevents refrigerant which condenses in the discharge line

during the off cycle from draining back into the compressor. In

-

stall the check valve at the compressor line before the line goes up

to the condenser. Check valve part no. EC37BP183 or similar may

be used.

Step 4 — Install Ductwork

The  09XC  unit  is  designed  for  use  either  with  or  without

ductwork. If ductwork is used, care must be taken to eliminate air

recirculation.  Recirculation  can  be  minimized  by  discharging

through an extension elbow. When properly designed, single de

-

flection discharge louvers can be applied to ductwork and to the

condenser air discharge. Fixed rain louvers over discharge outlets

can  cause  excessive  recirculation  and  nuisance  high  pressure

switch cutouts. Obstructions closer than 10 ft to the discharge air

pattern  can  also  cause  significant  recirculation.  See  Fig.  6  for

ductwork installation to prevent recirculation of air.
CONDENSER AIR DUCT
The condenser supply and discharge air duct should be as short as

possible. The cross section area of the duct should be the same as

the face area of the unit openings. For units with multiple fans, “a

pair of  pants” duct configuration  should be used in accordance

with  the  System  Design  Manual  and ASHRAE  guidelines;  in

some instances, settling media may be required to ensure uniform

airflow. Ductwork should be insulated to prevent moisture con

-

densation on the unit panels during cold weather.

Insulate as follows:

1. If metal ductwork is used, insulation may be applied on the

inside  of  the  duct. This  installation  should  be  extended  to

cover the inside of the duct flanges. It is necessary to insulate

the inside of the ducts at the duct flanges to reduce heat loss

from  the  metal  cabinet  by  conduction  through  the  duct

flanges and into the cold duct. Interior insulation allows the

metal  duct to  approach  room  temperature.  It  also  prevents

condensation from forming and collecting under the insula

-

tion which will occur with exterior duct insulation.

NOTE: Fiberglass duct board may also be used if permitted by lo

-

cal codes.

2. If insulation is applied to the outside of the metal duct, the

inside must be insulated for a length of 10 in. from the unit

(including the duct flanges) or up to the flexible duct vapor

barrier on the outside, which must be tightly sealed to prevent

condensation under the insulation.

Step 5 — Insulate the Unit

The  09XC  units  are  not  insulated.  If  the  unit  will  be  operated

during cold  weather and the equipment  room  is not at outdoor

temperatures, the unit cabinet should be insulated to prevent con

-

densation. Insulate the unit in the same manner as the ductwork in

-

sulation described in Condenser Air Duct section above.

Summary of Contents for Omnizone 09XC06

Page 1: ...des Wear safety glasses and work gloves WARNING Electrical shock can cause personal injury and death Shut off all power to this equipment during installation There may be more than one disconnect switch Tag all disconnect locations to alert others not to restore power until work is completed CAUTION Use care in handling rigging and setting bulky equipment Personal injury could result DANGER DO NOT...

Page 2: ...mbi nation is not recommended See Application Data literature for more information on condenser combinations Fig 1 Base Unit Dimensions 09XC06 24 UNIT 50XCR CONDENSER QUANTITY 09XC SIZE 06 08 12 14 16 24 06 1 08 1 12 1 14 1 16 1 24 1 UNIT 09XC WIDTH HEIGHT DEPTH CONDENSER INLET LIQUID OUTLET CONDENSER DISCHARGE DUCT BLOWER OPENING COND RETURN DUCT COND INLET DIAMETER OD LIQUID OUTLET DIAMETER OD A...

Page 3: ...BK85 Motor Pulley Type 1VP44 1VP34 1VP34 1VP34 1VL34 1VP50 Std HP 1 1 5 2 2 3 0 5 HP Range 1 1 5 1 5 2 2 3 2 3 3 5 5 7 5 Fan Shaft Size in 1 1 1 1 1875 1 4375 1 4375 Motor Shaft Size in 0 875 0 875 0 875 0 875 1 125 1 125 Center Distance in 27 1 27 1 29 8 29 8 29 8 35 1 CONDENSER COIL 3 8 in OD Enhanced Copper Tube Aluminum Fins Quantity Rows Fin in 6 16W 6 16W 6 16W 6 16W 5 16 6 16 Fin Block Size...

Page 4: ...4 Unit Clearances Either provide inlet filters to protect the coils or locate the unit in an area free from airborne dirt or other foreign material which could clog the coils The units are designed to pass through most 36 in door openings POSITIONING THE 09XC UNIT Refer to Fig 4 for typical service clearances To suspend the unit use 4 field supplied 1 2 in diameter or larger threaded rods Mount 2 ...

Page 5: ...iping If tubing size is other than unit connection sizes use adapter fittings Refer to 50XCR or other compressor bearing unit base unit in stallation instructions to determine refrigerant charge adjustment for remote and special piping applications NOTE When installing 09XC units in systems add charge for other components i e filter drier moisture indicator etc to de termine system charge quantity...

Page 6: ... HG LIQ HG LIQ HG LIQ HG LIQ HG LIQ 06 1 5 8 1 2 7 8 1 2 7 8 1 2 7 8 5 8 7 8 5 8 08 1 5 8 1 2 7 8 1 2 7 8 1 2 7 8 5 8 7 8 5 8 12 1 7 8 5 8 7 8 5 8 11 8 5 8 11 8 5 8 11 8 5 8 14 1 7 8 5 8 7 8 5 8 11 8 5 8 11 8 5 8 11 8 5 8 16 1 11 8 5 8 11 8 5 8 11 8 5 8 13 8 7 8 13 8 7 8 24 1 11 8 5 8 11 8 5 8 13 8 7 8 13 8 7 8 13 8 7 8 HG Hot Gas Refrigerant Discharge LIQ Liquid UNIT 09XC A B C D E F G 06 24 111 ...

Page 7: ...eld supplied wire nuts to make the connections to the terminal strip in the control box For field con trol connections all wiring enters the unit through a factory punched access hole on the right side of the unit See Fig 1 Table 4 Fan Electrical Data LEGEND NOTES 1 In compliance with NEC requirements for multimotor and combina tion load equipment NEC Articles 430 and 440 the overcurrent protectiv...

Page 8: ...eter by scrolling to that parameter and press ing EDIT 5 Select the New Value then press SAVE Table 5 Low Ambient Operation Parameters Check Operation of Condenser Fan Motor Controls and Rotation of Fans Rotation should be clockwise as viewed from belt access panel Adjust Fan Speed The 09XC units are belt driven condenser units and allow for a wide range of inlet static and condenser airflow requi...

Page 9: ...69 1 27 1018 1 43 1066 1 60 2600 577 0 40 644 0 51 708 0 62 767 0 75 824 0 89 878 1 03 930 1 18 980 1 34 1029 1 50 1075 1 67 2700 599 0 45 664 0 56 725 0 68 783 0 81 839 0 95 892 1 09 943 1 25 992 1 41 1039 1 57 1085 1 75 2800 621 0 50 684 0 61 744 0 74 800 0 87 854 1 01 906 1 16 956 1 32 1004 1 48 1050 1 65 1095 1 83 2900 644 0 56 704 0 67 762 0 80 817 0 94 870 1 08 920 1 23 969 1 39 1016 1 56 10...

Page 10: ...684 0 61 744 0 74 800 0 87 854 1 01 906 1 16 956 1 32 1004 1 48 2950 655 0 58 714 0 71 771 0 83 826 0 97 878 1 12 928 1 27 976 1 43 1023 1 60 3100 688 0 68 745 0 80 799 0 94 852 1 08 902 1 23 950 1 39 997 1 55 1042 1 72 3250 721 0 78 776 0 91 828 1 05 878 1 20 927 1 36 973 1 52 1019 1 69 1063 1 86 3400 755 0 89 807 1 03 857 1 18 905 1 33 952 1 49 997 1 66 1041 1 83 3550 788 1 02 838 1 16 886 1 31 ...

Page 11: ... 5300 503 0 88 552 1 04 597 1 20 640 1 37 680 1 54 719 1 72 757 1 90 793 2 10 5500 522 0 99 569 1 15 613 1 32 654 1 49 694 1 66 732 1 85 769 2 04 804 2 23 5700 541 1 10 587 1 27 629 1 44 670 1 62 708 1 80 745 1 98 781 2 18 816 2 38 5900 560 1 22 604 1 39 646 1 57 685 1 75 722 1 94 758 2 13 794 2 33 828 2 53 6100 578 1 35 622 1 53 662 1 71 700 1 90 737 2 09 772 2 29 807 2 49 840 2 70 6300 597 1 48 ...

Page 12: ...PM BHP 6000 496 1 03 533 1 17 570 1 36 608 1 58 646 1 82 683 2 06 719 2 31 755 2 56 6250 517 1 17 552 1 31 588 1 50 624 1 72 660 1 97 696 2 22 732 2 48 766 2 74 6500 537 1 31 571 1 46 605 1 65 640 1 88 675 2 13 710 2 39 744 2 66 778 2 93 6750 558 1 47 590 1 62 623 1 81 657 2 05 691 2 30 724 2 57 757 2 85 7000 579 1 64 610 1 79 642 1 99 674 2 23 707 2 49 739 2 76 7250 599 1 82 629 1 98 660 2 18 691...

Page 13: ... 853 3 71 883 3 95 7750 588 1 99 629 2 22 667 2 45 704 2 68 739 2 92 772 3 16 804 3 40 836 3 64 866 3 89 895 4 14 8000 607 2 15 646 2 38 684 2 62 720 2 86 754 3 10 787 3 34 818 3 59 849 3 83 878 4 08 907 4 33 8250 626 2 32 664 2 56 701 2 80 736 3 04 769 3 28 801 3 53 832 3 78 862 4 03 891 4 28 920 4 53 8500 645 2 50 682 2 74 718 2 98 752 3 23 784 3 48 816 3 73 846 3 98 876 4 23 905 4 48 933 4 74 8...

Page 14: ... mounting bracket Do not loosen fan motor mounting bracket from unit 3 Loosen movable pulley flange setscrew Fig 7 CFM ESP in wg 0 00 0 10 0 20 0 30 0 40 0 50 0 60 0 70 Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp Rpm Bhp 8 500 613 2 20 657 2 54 698 2 87 737 3 22 773 3 56 808 3 91 841 4 27 873 4 63 8 800 634 2 45 677 2 79 717 3 14 755 3 49 790 3 85 824 4 21 857 4 58 889 4 95 9 100 656 2...

Page 15: ...an wheels 4 Remove the shaft through the access panel on either side of the unit 5 Remove the fan cut off plate in the fan discharge 6 Remove the fan wheel through the fan discharge opening 7 Replace the wheel and reverse Steps 1 5 above Fan Bearing Replacement If a fan bearing fails replace it as follows 1 Shut off unit power supply Lock out power supply and tag disconnect locations 2 Remove belt...

Page 16: ...30V 0 50 1 8 2 2 1 1 0 9 0 75 2 5 2 6 1 3 1 0 1 00 3 4 3 0 1 5 1 1 1 50 4 6 4 2 2 1 1 6 2 00 6 0 5 6 2 8 2 1 3 00 9 2 8 6 4 3 3 4 5 00 14 5 13 6 6 8 5 4 7 50 21 5 19 4 9 7 7 5 10 00 28 0 12 6 10 1 PROBLEM POSSIBLE CAUSE CORRECTION PROCEDURE Unit will not Start Loss of unit power Check power source Check fuses circuit breakers disconnect switch Check electrical contacts Unit voltage not correct Che...

Page 17: ...e for at least 194 F 90 C when replacing factory wiring 4 Use copper conductors only 5 Wiring for field power supply must be rated at 165 F 75 C minimum LEGEND C Compressor Contactor DISC Disconnect GND Ground OFM Outdoor Fan Motor OFR Outdoor Fan Relay PRES Pressure Transducer TB Terminal Block VFD Variable Frequency Drive Terminal Block Connection Marked Terminal Unmarked Terminal Splice Factory...

Page 18: ...tly thermally protected 2 Three phase motors are protected under primary single phase conditions 3 Use conductors suitable for at least 194 F 90 C when replacing factory wiring 4 Use copper conductors only 5 Wiring for field power supply must be rated at 165 F 75 C minimum LEGEND C Compressor Contactor DISC Disconnect GND Ground OFM Outdoor Fan Motor OFR Outdoor Fan Relay PRES Pressure Transducer ...

Page 19: ...____ HAVE CONDENSER FANAND MOTOR PULLEYS BEEN CHECKED FOR PROPER ALIGNMENTAND DO THE FAN BELTS HAVE PROPER TENSION Y N _______ HAS CORRECT FAN ROTATION ON CONDENSER BEEN CONFIRMED Y N _______ ARE PROPERAIR FILTERS IN PLACE AND ARE FILTERS CLEAN Y N _______ VERIFY UNIT IS INSTALLED WITHIN LEVELING TOLERANCES Y N _______ CONTROLS HAVE CONTROL CONNECTIONS BEEN MADE AND CHECKED Y N _______ ARE ALL WIR...

Page 20: ...ST 15 MINUTES RUNNING TIME RECORD THE FOLLOWING MEASUREMENTS COMPRESSORAMPS NOTES _______________________________________________________________________________________ _______________________________________________________________________________________________ _______________________________________________________________________________________________ ______________________________________...

Reviews: